1 OccuHealth, Inc. 44 Wood Avenue Mansfield, MA Occupational Health & Safety, Environmental Consultants Tel. (508) Tel. (800) Fax (508) January 1, 2007 Mr. Mark LaFleur Director of Plant Operations Town of Needham 10 Highland Avenue Needham, MA RE: Indoor Air Quality Testing Room 211 Newman Elementary School 1155 Central Avenue Needham, Massachusetts Dear Mr. LaFleur: OccuHealth, Inc. (OHI) is submitting the enclosed report for the indoor air quality testing conducted on January 15, 2007 in Room 211 at the Newman Elementary School located at 1155 Central Avenue in Needham, Massachusetts. Please call me at (508) with any questions regarding this report. Thank you for the opportunity to be of continued service. Regards, OCCUHEALTH, INC. Enclosure Thomas E. Hamilton, CIH

2 OccuHealth INDOOR AIR QUALITY TESTING ROOM 211 NEWMAN ELEMENTARY SCHOOL 1155 CENTRAL AVENUE NEEDHAM, MASSACHUSETTS Prepared for: MR. MARK LAFLEUR DIRECTOR OF PLANT OPERATIONS TOWN OF NEEDHAM 10 HIGHLAND AVENUE NEEDHAM, MA Conducted by: OCCUHEALTH, INC. 4 4 W OOD AVENUE MANSFIELD, MA (508) Report Date: JANUARY 1, 2007

3 AIRBORNE MOLD SPORE TESTING ROOM 211 NEWMAN ELEMENTARY SCHOOL 1155 CENTRAL AVENUE NEEDHAM, MASSACHUSETTS TABLE OF CONTENTS SECTION DESCRIPTION PAGE 1.0 Introduction Inspection Airborne Mold Spore Testing Airborne Viable Fungi Testing Carpet Dust Mite Allergen Analysis Conclusions Limitations...4 Attachments Airborne Mold Spore Testing Laboratory Report EAA Chain-of-Custody Form Airborne Viable Fungi Testing Laboratory Report Carpet Dust Mite Allergen Testing Laboratory Report Aerotech P&K Chain-of-Custody Form

4 Indoor Air Quality Testing Page 1 Room 211, Newman Elementary School, Needham, MA Report Date: January 1, 2007 Report Synopsis: OccuHealth, Inc. was requested to evaluate the air quality in Room 211 in the Newman Elementary School in Needham, Massachusetts. An inspection of the air handling system servicing the room was also conducted. Based on observed conditions and the results of analytical testing, OHI concludes that the air quality in Room 211 was acceptable on the date of testing with respect to airborne mold and viable fungi levels and dust mite allergen concentrations. OHI does not offer any recommendations. 1.0 INTRODUCTION OccuHealth, Inc. (OHI) was requested to conduct indoor air quality testing in Room 211 in the Newman Elementary School located at 1155 Central Avenue in Needham, Massachusetts. OHI inspected the room and collected an air sample for mold spore analysis in the room. OHI collected two air samples for airborne viable fungi analysis in Room 211. OHI collected a sample of carpet dust from Room 211 for mite allergen analysis. OHI also conducted an inspection of the air handling system that services the room. The assessment was conducted on January 15, 2007 by Mr. Thomas Hamilton, Certified Industrial Hygienist (CIH), of OHI. OHI previously inspected the room on December 6, 2006 after a steam leak impacted the room. This project was requested and authorized by Mr. Mark LaFleur of the Town of Needham, Massachusetts. 2.0 INSPECTION OHI observed that the room had been cleaned since our last inspection of December OHI noted that water-damaged papers, books and other damaged items had been removed. On the day of the assessment, the heat was operating. OHI did not observe any evidence of mold growth in the room. With the assistance of Mr. Jack Hastings, OHI did an inspection of the mechanical room where the air handling system for Room 211 is located. OHI inspected the system and no unusual conditions were noted with regard to operation and cleanliness. The steam pipe that broke and led to the steam problems in Roon 211 was also inspected..0 AIRBORNE MOLD SPORE TESTING Sampling and Analytical Methodology OHI collected an air sample for mold spore analysis in Room 211. OHI collected an outdoor air sample for comparison. The air samples were collected using a high volume pump with Zefon Air-O-Cell cassettes. An Air-O-Cell cassette is a spore and dust trap which allows

5 Indoor Air Quality Testing Page 2 Room 211, Newman Elementary School, Needham, MA Report Date: January 1, 2007 for rapid detection and identification of mold spores using bright light microscopy. Culturable and non-viable mold spores are collected and counted. The analytical results can be compared to data from available studies and to levels seen outdoors. The sample pump was calibrated to a flow rate of 15 liters per minute and the samples were collected for 5 minutes. The sample pump utilized for the air sampling was calibrated before the sampling event using a precision rotameter. This rotameter was in turn calibrated using a primary standard. The samples were submitted under chain-of-custody for analysis to Environmental Analysis Associates (EAA) of San Diego, California. Copies of the EAA laboratory report and chain-of-custody form are attached. Analytical Results The analytical results are summarized in Table 1 below. To interpret the results, an airborne mold spore concentration of less than 2,000 counts per cubic meter of air (cts/m ) as a total spore count, and less than 1,000 cts/m for any one genera of mold is considered low or clean for an indoor environment. Counts above 2,000 cts/m in indoor air samples are considered elevated if they are different genera from those detected outdoors. Table 1: Airborne Mold Spore Testing Results Location Sample Number Total Mold Spores (cts/m ) Identified Mold Genera (cts/m ) Room Not detected Outdoors ,555 Ascospores/Basidiospores (29,62) Ascospores, pigmented (9) cts/m = counts per cubic meter of air The laboratory did not detect mold spores in the air sample collected in Room 211. The analytical results are consistent with the conditions observed in the room. 4.0 AIRBORNE VIABLE FUNGI TESTING Sampling and Analytical Methodology OHI collected two side-by-side bioaerosol air samples with a Buck BioAire Impactor in Room 211. OHI also collected an outdoor bioaerosol air sample for comparison. The plates were forwarded under chain-of-custody for incubation and speciation to Aerotech/P&K Laboratories, Inc. (Aerotech/P&K) in Cherry Hill, New Jersey. The bioaerosol samples were

6 Indoor Air Quality Testing Page Room 211, Newman Elementary School, Needham, MA Report Date: January 1, 2007 analyzed by a process similar to that published by the Bioaerosols Committee of the American Conference of Governmental Industrial Hygienists. The samples were incubated in the laboratory and enumeration of viable organisms was reported in colony forming units per sample. Since the air sample volume for each sample was 600 liters of air, the results must be multiplied by a conversion factor of approximately 1.6 in order to report the results in colony forming units per cubic meter of air (CFU/m ). Copies of the Aerotech/P&K laboratory report and chain-of-custody form are attached. Data Analysis The most important task during the data interpretation is to distinguish between the sources of these pathogens. Each fungal species must be categorized as either a common environmental or an uncommon species. Common environmental associated fungal organisms include Cladosporium and Penicillium. The source of these organisms is typically vegetation. Possible amplification of fungal organisms in indoor office or home environments is considered when the concentration is above 200 colony forming units per cubic meter of air (CFU/m ) and is at least two times (200%) of that detected outdoors. The typical level of airborne fungi in indoor environments such as offices and schools is less than 500 CFU/m. Analytical Results The results of the culture and speciation of the air samples are presented in Table 2 below. Table 2: Airborne Viable Fungi Testing Results Location Total Airborne Viable Fungi Identified Genera Concentration (CFU/m ) (CFU/m ) Room 211, Sample A 4 Sterile fungi (4) Room 211,Sample B 8 Cladosporium (4) Sterile fungi (4) Outdoors 700 Basidiomycetes (696) Sterile fungi (4) CFU/m = colony forming units per cubic meter of air The laboratory identified very low, acceptable levels of viable fungi in the two side-byside air samples collected in Room 211.

7 Indoor Air Quality Testing Page 4 Room 211, Newman Elementary School, Needham, MA Report Date: January 1, CARPET DUST MITE ALLERGEN TESTING OHI collected a sample of carpet dust from Room 211 for indoor allergen analysis. The sample was forwarded under chain-of-custody for analysis to Aerotech/P&K. A copy of the Aerotech/P&K laboratory report is attached. The laboratory did not detect Der p1 dust mite allergen above the laboratory detection limit in the dust sample. The laboratory detected 1.1 micrograms per gram of dust (µg/g) of Der f1 dust mite allergen in the dust sample. Levels below 2.0 µg/g are considered low and acceptable; consequently, OHI does not offer any recommendations. 6.0 CONCLUSIONS Based on the inspection findings and the results of analytical testing, OHI concludes that the air quality in Room 211 was acceptable on the date of testing with respect to airborne mold and viable fungi levels and dust mite allergen concentrations. OHI does not offer any recommendations. 7.0 LIMITATIONS The contents of this report are based on OccuHealth, Inc. s best professional judgement, comparison of collected data with established industry guidelines, and information obtained from representatives of the Town of Needham.

8 ATTACHMENTS Airborne Mold Spore Analysis Laboratory Report EAA Chain-of-Custody Form Airborne Viable Fungi Testing Laboratory Report Carpet Dust Mite Allergen Testing Laboratory Report Aerotech P&K Chain-of-Custody Form

9

10

11

12

13

14

15

16

Occupational Health & Safety, Environmental Consultants Tel. (508) Tel. (800) Fax (508)

Occupational Health & Safety, Environmental Consultants Tel. (508) Tel. (800) Fax (508) OccuHealth, Inc. 44 Wood Avenue Mansfield, MA 02048 Occupational Health & Safety, Environmental Consultants Tel. (508) 339-9119 Tel. (800) 729-1035 Fax (508) 339-2893 t_hamilton@occuhealth.com December

More information

MSES consultants, inc.

MSES consultants, inc. MSES consultants, inc. 609 West Main Street P.O. Drawer 190 Clarksburg, WV 26302-0190 304.624.9700 304.622.0981 304.842.3325 http://www.msesinc.com Office December 30, 2013 Project Number: 13-441 Mr. Joe

More information

Indoor Air Quality Testing. Horry County Schools

Indoor Air Quality Testing. Horry County Schools ! Report of: Indoor Air Quality Testing Horry y Schools Conway, SC Palme5o EHS Report No: 2018376 Submi5ed Prepared for: Horry y Schools Prepared By: Palme5o EHS, LLC 100 Old Cherokee Rd. Suite F, Box

More information

MSES consultants, inc.

MSES consultants, inc. MSES consultants, inc. 609 West Main Street P.O. Drawer 190 Clarksburg, WV 26302-0190 304.624.9700 304.622.0981 304.842.3325 http://www.msesinc.com Office December 5, 2013 Project Number: 13-441 Mr. Joe

More information

MSES consultants, inc.

MSES consultants, inc. MSES consultants, inc. 609 West Main Street P.O. Drawer 190 Clarksburg, WV 26302-0190 304.624.9700 304.622.0981 304.842.3325 http://www.msesinc.com Office September 13, 2012 Project Number: 12-437 Mr.

More information

FUNGAL PARTICULATE AIR SAMPLING

FUNGAL PARTICULATE AIR SAMPLING November 19, 2016 Chuck Doan Yakima School District #7 104 N 4th Avenue Yakima, WA 98902 Via email: Regarding: doan.chuck@yakimaschools.org Fungal Sample Results Blue Wall Room 509 and Room 617 Eisenhower

More information

Literature Building Mold Sampling Report

Literature Building Mold Sampling Report Literature Building Mold Sampling Report University of California, San Diego Prepared By: Aurora Industrial Hygiene San Diego, CA Prepared By: Date: April 6, 2009 Karen G. Shockley, CIH #6766 TABLE OF

More information

A Healthy Home, LLC West Center Dr. Lakewood, CO

A Healthy Home, LLC West Center Dr. Lakewood, CO Mold Inspection and Testing Summary A Healthy Home, LLC 13520 West Center Dr. Lakewood, CO. 80228 303-989-6809 Robert Boyd, is certified by the American Council of Accredited Certification (ACAC), as a

More information

M. A. CECIL & ASSOCIATES, INC Shannon Way, Port Republic, Maryland (301) INDUSTRIAL HYGIENE AND ENVIRONMENTAL HEALTH

M. A. CECIL & ASSOCIATES, INC Shannon Way, Port Republic, Maryland (301) INDUSTRIAL HYGIENE AND ENVIRONMENTAL HEALTH M. A. CECIL & ASSOCIATES, INC. 4475 Shannon Way, Port Republic, Maryland 20676 (301) 855-7710 INDUSTRIAL HYGIENE AND ENVIRONMENTAL HEALTH October 17, 2013 Mr. Sean Yarup Montgomery County Public Schools

More information

Introduction: PCR Air Sampling: November 12, Carrie E Tompkins Elementary School PCR Fungi Study:

Introduction: PCR Air Sampling: November 12, Carrie E Tompkins Elementary School PCR Fungi Study: 23 STATE STREET OSSINING, NEW YORK 10562 TEL.: (914) 762-6333 FAX: (914) 762-5578 W W W. E M S O F N Y. C O M November 12, 2014 Environmental Science Safety Engineering Industrial Hygiene Environmental

More information

Indiana University Environmental Health & Safety Beau Middaugh 2427 E. 2nd street Bloomington, IN USA (812)

Indiana University Environmental Health & Safety Beau Middaugh 2427 E. 2nd street Bloomington, IN USA (812) Indiana University Environmental Health & Safety Beau Middaugh 2427 E. 2nd street Bloomington, IN 47401 USA (812) 855-6316 Approved by: Dates of Analysis: MoldReport Spore trap: 12-19-2018 Technical Manager

More information

C E R T I F I C A T E O F M O L D A N A L Y S I S

C E R T I F I C A T E O F M O L D A N A L Y S I S C E R T I F I C A T E O F M O L D A N A L Y S I S PREPARED FOR: A Plus Inspections of Texas Phone Number: (713) 249-2618 Email: paul@inspec4.net Test Location: Phil Homebuyer 123 Mold City Dr Houston,

More information

EDLab. Re: 0 Any Street, # 100 Laboratory Analysis Report Work Authorization #

EDLab. Re: 0 Any Street, # 100 Laboratory Analysis Report Work Authorization # EDLab Environmental Diagnostics Laboratory January 6, 2017 Jane Example 0 Any Street, # 100 Clearwater, FL Laboratory Advisory Board Alan L. Wozniak, CIAQP President/CEO Mark D. Wozniak, MBA, CIAQP Vice

More information

C e r t i f i c a te o f m o ld Ana l y s i s

C e r t i f i c a te o f m o ld Ana l y s i s 3 3 0 1 N.W. 5 5 th S t., F t. Lauderdale, FL 3 3 3 0 9 ( 8 8 8 ) 8 5 4-0 4 7 7 C e r t i f i c a te o f m o ld Ana l y s i s P R E PARED F O R : TLC Home Inspections Phone Number: (512) 900-2191 Email:

More information

1251 Weatherstone Ct. Reston,VA Mold Reduction Report

1251 Weatherstone Ct. Reston,VA Mold Reduction Report GreenClean Air Weatherstone Ct. Reston,VA 094 70.97.7 Steve@GreenCleanAir.com Mold Reduction Report November, 0 Rodney Fugitt Strategic Property Systems 077 Alyssia Lane Waldorf, MD 060 Re: 90 Messina

More information

test address: P R E PAR E D F OR : CalPro Inspection Group Phone Number: (800)

test address: P R E PAR E D F OR : CalPro Inspection Group Phone Number: (800) 3 3 0 1 N.W. 5 5 th S t., F t. Lauderdale, FL 3 3 3 0 9 ( 8 8 8 ) 8 5 4-0 4 7 7 prepared for: test address: CalPro Inspection Group 1234 Any Name St. Sacrameto, Ca 95835 C e r t i f i c a t e o f m o l

More information

Legally Defensible Strategies for Mold Investigations

Legally Defensible Strategies for Mold Investigations Legally Defensible Strategies for Mold Investigations Metro New York AIHA Bull Moose Meeting September 10, 2014 Jack Springston, CIH, CSP TRC Environmental, Inc. www.trcsolutions.com Disclaimer The contents

More information

Influence of Environmental Parameters on Mold Sampling Results

Influence of Environmental Parameters on Mold Sampling Results University of South Florida Scholar Commons Graduate Theses and Dissertations Graduate School June 2017 Influence of Environmental Parameters on Mold Sampling Results Benjamin Fishman University of South

More information

Certificate of Mold Analysis

Certificate of Mold Analysis HEARTLAND INSPECTIONS 3515 HUMBOLDT AVE SO MINNEAPOLIS, MN 55408 Certificate of Mold Analysis Prepared for: HEARTLAND INSPECTIONS Phone Number: (612) 860-4578 Fax Number: Project Name: CORRIGAN Test Location:

More information

Certificate of Mold Analysis

Certificate of Mold Analysis INDOOR AIR QUALITY CORPORATION 1675 N COMMERCE PKWY WESTON, FL 33326 Certificate of Mold Analysis Prepared for: INDOOR AIR QUALITY CORPORATION Phone Number: (407) 463-8666 Fax Number: (954) 332-1005 Project

More information

Certificate of Mold Analysis

Certificate of Mold Analysis CHICAGO INSPECTION AGENCY 815 N SCHOOL ST PROSPECT HEIGHTS, IL 60070 Certificate of Mold Analysis Prepared for: CHICAGO INSPECTION AGENCY Phone Number: (847) 459-9387 Fax Number: (847) 459-9443 Project

More information

Analysis Report prepared for Quest Air

Analysis Report prepared for Quest Air contact@hayesmicrobial.com http://hayesmicrobial.com/ Analysis Report prepared for 103 Carnegie Center Suite 300 Princeton, NJ. 08540 Job Name: 76 Federal City Road Date Sampled: 05-30-2017 Date Analyzed:

More information

EDLab. Re: 0 Any Street, # 100 Laboratory Analysis Report Work Authorization #

EDLab. Re: 0 Any Street, # 100 Laboratory Analysis Report Work Authorization # EDLab Environmental Diagnostics Laboratory January 6, 2017 Jane Example 0 Any Street, # 100 Clearwater, FL Laboratory Advisory Board Alan L. Wozniak, CIAQP President/CEO Mark D. Wozniak, MBA, CIAQP Vice

More information

Air Sampling and Analysis for Mold in Hills Building UMass

Air Sampling and Analysis for Mold in Hills Building UMass Air Sampling and Analysis for Mold in Hills Building UMass Christine Rogers, PhD Environmental Health Science SPHHS First Floor Hills North Introduction Upon request, all of the rooms on the first floor

More information

Tape Lift and Swab Sampling of Items found at Glenwood Middle School Project #J15-876

Tape Lift and Swab Sampling of Items found at Glenwood Middle School Project #J15-876 October 21, 2015 Mr. Jeff Klenk Howard County Public School System 10910 Route 108 Ellicott City, MD 21043 RE: Tape Lift and Swab Sampling of Items found at Glenwood Middle School Project #J15-876 Dear

More information

C e r t i f i c a t e o f m o l d A n a l y s i s

C e r t i f i c a t e o f m o l d A n a l y s i s 3 3 0 1 N.W. 5 5 t h S t., F t. L a u d e r d a l e, F L 3 3 3 0 9 3301 N.W. 55th St., Ft. Lauderdale, ( 8 0 0 ) 5FL 4 433309-8 1 5 6888-854-0477 C e r t i f i c a t e o f m o l d A n a l y s i s P R E

More information

Certificate of Mold Analysis

Certificate of Mold Analysis CHICAGO INSPECTION AGENCY 815 N SCHOOL ST PROSPECT HEIGHTS, IL 60070 Certificate of Mold Analysis Prepared for: CHICAGO INSPECTION AGENCY Phone Number: (847)459-9387 Fax Number: (847)459-9443 Project Name:

More information

Certificate of Mold Analysis

Certificate of Mold Analysis COASTAL ENVIRONMENTAL PO BOX 167 HAMMONTON, NJ 08330 Certificate of Mold Analysis Prepared for: COASTAL ENVIRONMENTAL Phone Number: (609) 820-9312 Fax Number: (609) 561-6197 Project Name: PVIL MIDDLE SCHOOL

More information

Certificate of Mold Analysis

Certificate of Mold Analysis COASTAL ENVIRONMENTAL PO BOX 167 HAMMONTON, NJ 08330 Certificate of Mold Analysis Prepared for: COASTAL ENVIRONMENTAL Phone Number: (609) 820-9312 Fax Number: (609) 561-6197 Project Name: LEEDS CLEARANCE

More information

Environmental Assessment, Timothy Dwight Elementary School 1600 Redding Road, Fairfield, Connecticut

Environmental Assessment, Timothy Dwight Elementary School 1600 Redding Road, Fairfield, Connecticut COMMITMENT & INTEGRITY DRIVE RESULTS 40 Shattuck Road Suite 110 Andover, Massachusetts 01810 www.woodardcurran.com T 866.702.6371 T 978.557.8150 F 978.557.7948 Via Electronic Mail November 6, 2018 Thomas

More information

Certificate of Mold Analysis

Certificate of Mold Analysis HOLMES INSPECTION COMPANY PO BOX 12787 SHAWNEE MISSION, KS 66282 Certificate of Mold Analysis Prepared for: HOLMES INSPECTION COMPANY Phone Number: (816) 455-8787 Fax Number: (267) 222-7185 Project Name:

More information

Certificate of Mold Analysis

Certificate of Mold Analysis PRISTINE HOME INSPECTIONS 1817 S NEIL #104-2 CHAMPAIGN, IL 61820 Certificate of Mold Analysis Prepared for: PRISTINE HOME INSPECTIONS Phone Number: (217) 722-5883 Fax Number: (217) 2-9851 Project Name:

More information

Certificate of Mold Analysis

Certificate of Mold Analysis CERTIFIED INSPECTION SERVICES 1211 NE 19TH TER. CAPE CORAL, FL 33909 Certificate of Mold Analysis Prepared for: CERTIFIED INSPECTION SERVICES Phone Number: (239) 458-9876 Fax Number: (239) 673-7964 Project

More information

No visible mold or water intrusion/damage was found on the day of testing.

No visible mold or water intrusion/damage was found on the day of testing. January th, 0 Mr. Marty Foutch Facilities Director Bixby Public Schools 9 N. Armstrong Bixby, OK 008 CC: RE: Jarred Doubrava Operations Support Manager/District Safety Coordinator Bixby Northeast Elementary

More information

AIRBORNE FUNGAL STRUCTURE SAMPLE ANALYSIS Results reported as Structures per Cubic Meter of Air (structures/m 3 )

AIRBORNE FUNGAL STRUCTURE SAMPLE ANALYSIS Results reported as Structures per Cubic Meter of Air (structures/m 3 ) Field #: TM042709 Project #: 141186 Description: Background, Outside, Main Lab #: 1504110 Entrance Eagle #: E15042809 Results reported as per Cubic Meter of Air Structure Identification ascospores (undifferentiated)

More information

MOLD INSPECTION REPORT

MOLD INSPECTION REPORT MOLD INSPECTION REPORT Conducted at: 407 Canyon East Conducted for: Town of Taos Prepared By: Gary O leary Klean Force Project Number: #21054 Inspection Date: 02/04/2015 Report Date: 02/13/2015 915-474-0299

More information

March 01, Re: Mold Sampling. Dear Mr. Jon Lewis,

March 01, Re: Mold Sampling. Dear Mr. Jon Lewis, 1990 S. Garrison St. Suite 6 Lakewood, CO 80227 Office 303-980-4401 Fax 303-980-4402 March 01, 2013 Re: Mold Sampling Dear Mr. Jon Lewis, Aspen Environmental, Inc. representatives completed the mold air

More information

Certificate of Mold Analysis

Certificate of Mold Analysis COASTAL ENVIRONMENTAL PO BOX 167 HAMMONTON, NJ 08330 Certificate of Mold Analysis Prepared for: COASTAL ENVIRONMENTAL Phone Number: Fax Number: Project Name: DECANTOR AVE SCHOOL Test Location:, Chain of

More information

Analysis Report prepared for Mold-Spec

Analysis Report prepared for Mold-Spec contact@hayesmicrobial.com http://hayesmicrobial.com/ Analysis Report prepared for Ormond Beach, FL. 3173 Date Sampled: 03-06-018 Date Analyzed: 03-08-018 Report Date: 03-08-018 EPA Laboratory ID# VA01419

More information

Certificate of Mold Analysis

Certificate of Mold Analysis ACE ENVIRONMENTAL 49 SHADOWCREEK WAY ORMOND BEACH, FL 32174 Certificate of Mold Analysis Prepared for: ACE ENVIRONMENTAL Phone Number: (904) 859-9211 Fax Number: Project Name: TOM HARTSFIELD Test Location:

More information

Indiana University Environmental Health & Safety Beau Middaugh 2427 E. 2nd street Bloomington, IN USA (812)

Indiana University Environmental Health & Safety Beau Middaugh 2427 E. 2nd street Bloomington, IN USA (812) Indiana University Environmental Health & Safety Beau Middaugh 2427 E. 2nd street Bloomington, IN 47401 USA (812) 855-6316 Approved by: Dates of Analysis: MoldReport Spore trap: 11-08-2018 Technical Manager

More information

Certificate of Mold Analysis

Certificate of Mold Analysis COASTAL ENVIRONMENTAL PO BOX 167 HAMMONTON, NJ 08330 Certificate of Mold Analysis Prepared for: COASTAL ENVIRONMENTAL Phone Number: (609) 820-9312 Fax Number: (609) 561-6197 Project Name: SOUTH MAIN CLEAR

More information

Mycotech Biological, Inc.

Mycotech Biological, Inc. AIHA EMPAT NO: 03006 00 Main Street Any City, TX Andersen Malt /2/04 /0/04 Sample No: (0) A- Sample No: (02) A-2 Sample No: (03) A-3 (Living Area) Sample No: (04) A-4 (Bedroom) //04 //04 //04 //04 Date

More information

Certificate of Mold Analysis

Certificate of Mold Analysis WILCOX INSPECTIONS Certificate of Mold Analysis Prepared for: Phone Number: Fax Number: Project Name: Test Location: WILCOX INSPECTIONS Chain of Custody #: Received Date: September 4, 2015 Report Date:

More information

Certificate of Mold Analysis

Certificate of Mold Analysis Certificate of Mold Analysis Prepared for: Phone Number: Fax Number: Project Name: Test Location: TEXINSPEC Chain of Custody #: Received Date: November 6, 2018 Report Date: November 6, 2018 Elena Santiago,

More information

Certificate of Mold Analysis (941) (941) SAMPLE REPORT

Certificate of Mold Analysis (941) (941) SAMPLE REPORT BUILDING INSPECTION OF FLORIDA PO BOX 380955 MURDOCK, FL 33938 Certificate of Mold Analysis Prepared for: Phone Number: Fax Number: BUILDING INSPECTION OF FLORIDA (941)743-3164 (941)743-4236 Currently

More information

AIRBORNE MOLD SPORE ANALYSIS

AIRBORNE MOLD SPORE ANALYSIS 11080 SW Allen Blvd, Suite, Beaverton, OR 97005 P: 503.292.5346 F: 503.203.1516 Tuesday, May 23, 2017 Ken Studnick Address: 38875 N 1st Ave, Scio, OR 97374 Projects 17-16079 and 16-14152 Dear Ken: SUMMARY

More information

Certificate of Mold Analysis

Certificate of Mold Analysis ACE ENVIRONMENTAL 49 SHADOWCREEK WAY ORMOND BEACH, FL 32174 Certificate of Mold Analysis Prepared for: ACE ENVIRONMENTAL Phone Number: (904) 859-9211 Fax Number: Project Name: NIA NETANE Test Location:

More information

Certificate of Mold Analysis

Certificate of Mold Analysis COASTAL ENVIRONMENTAL PO BOX 167 HAMMONTON, NJ 08330 Certificate of Analysis Prepared for: COASTAL ENVIRONMENTAL Phone Number: (609) 820-9312 Fax Number: (609) 561-6197 Project Name: Test Location: NORTH

More information

Certificate of Mold Analysis

Certificate of Mold Analysis BULLSEYE INSPECTION 1802 INGRAM AVE SARASOTA, FL 34232 Certificate of Mold Analysis Prepared for: BULLSEYE INSPECTION Phone Number: (941)341-0577 Fax Number: (941)341-0577 Project Name: SARASOTA, FL 34238

More information

Airborne Mould Sampling Moncton High School 207 Church Street Moncton, NB E1C 5A3. November 25, 2013

Airborne Mould Sampling Moncton High School 207 Church Street Moncton, NB E1C 5A3. November 25, 2013 Project # 18578 Airborne Mould Sampling Moncton High School 207 Church Street Moncton, NB E1C 5A3 November 25, 2013 Attention: Serge Melanson Transportation and Infrastructure Facilities Management Moncton

More information

CONCENTRATIONS OF VIABLE FUNGAL SPORES ON PAPER DOCUMENTS

CONCENTRATIONS OF VIABLE FUNGAL SPORES ON PAPER DOCUMENTS 1 INTRODUCTION CONCENTRATIONS OF VIABLE FUNGAL SPORES ON PAPER DOCUMENTS This work was performed as part of a broader Indoor Air Quality (IAQ) response action, which lasted in excess of eight months. A

More information

IAQ & MOLD AIR SAMPLING REPORT

IAQ & MOLD AIR SAMPLING REPORT IAQ & MOLD AIR SAMPLING REPORT LINCOLNSHIRE-PRAIRIE VIEW SCHOOL DISTRICT #103 Project Location: HALF DAY SCHOOL 239 Olde Half Day Road Testing Dates: January 10 17, 2018 MEC PROJECT #: 17-12-968-I.H. EXECUTIVE

More information

CERTIFICATE OF MOLD ANALYSIS PRISTINE INSPECTIONS & TESTING PHONE NUMBER: [

CERTIFICATE OF MOLD ANALYSIS PRISTINE INSPECTIONS & TESTING PHONE NUMBER: [ OINSPECTORLAB 3301 N.W. 55TH ST., FT. LAUDERDALE, H 33309 (800)544-8156 CERTIFICATE OF MOLD ANALYSIS PREPARED FOR: PRISTINE INSPECTIONS & TESTING PHONE NUMBER: [2171 352-3743 EMAIL INSPECTORS@PRISTINEHLGOM

More information

Mastertech North Jersey

Mastertech North Jersey contact@hayesmicrobial.com http://hayesmicrobial.com/ Analysis Report prepared for Mastertech North Jersey Mount Arlington, NJ. 07856 Phone: (973) 346-650 I 18 MT1 Job Name: Indiana 18 Date Sampled: 03-09-018

More information

DATE: May 23, TO: Tommy Ellington, Executive Director

DATE: May 23, TO: Tommy Ellington, Executive Director DATE: May 23, 2016 TO: Tommy Ellington, Executive Director SUBJECT: SSAB- IAQ - Initial Contact - Sherah Robinson's office, Cinnamon Dilts' office and Storeroom SE corner On Wednesday 5/18, I received

More information

Index. Immunol Allergy Clin N Am 23 (2003) Note: Page numbers of article titles are in boldface type.

Index. Immunol Allergy Clin N Am 23 (2003) Note: Page numbers of article titles are in boldface type. Immunol Allergy Clin N Am 23 (2003) 549 553 Index Note: Page numbers of article titles are in boldface type. A Acari. See Mites; Dust mites. Aeroallergens, floristic zones and. See Floristic zones. Air

More information

FUNGAL (MOLD) TESTING RESULT REPORT* Cover Page

FUNGAL (MOLD) TESTING RESULT REPORT* Cover Page FUNGAL (MOLD) TESTING RESULT REPORT* Cover Page RESULT TABLES ANALYTICAL REPORT (Spore trap report) MOLD BRIEF DESCRIPTIONS (In a separate file) Verified By: Wei Cohen, B.S. Approved By: Jian (Young) Bao,

More information

CERTIFICATE OF MOLD ANALYSIS

CERTIFICATE OF MOLD ANALYSIS CERTIFICATE OF MOLD ANALYSIS PREPARED FOR: Doc Shane Test Client Account Phone Number: (888) 854-0478 Email: docshane@inspectorlab.com Test Location: Max Headroom 1234 John Muir Street Hayward, CA 94544

More information

DATE: September 15, TO: Sarah Johnston, Director

DATE: September 15, TO: Sarah Johnston, Director DATE: September 15, 2015 TO: Sarah Johnston, Director SUBJECT: Purnell Service Center - IAQ - Air Test - Room 105, 4 Director's offices & Secretary office area. On Saturday 9/12, I received an E-mail from

More information

This test report contains the following four sections: Chain of Custody, Data Detail, Frequently Asked Questions, and Glossary.

This test report contains the following four sections: Chain of Custody, Data Detail, Frequently Asked Questions, and Glossary. This test report contains the following four sections: Chain of Custody, Data Detail, Frequently Asked Questions, and Glossary. Direct Exam Chain of Custody Page 1 1 Results apply only to samples tested.

More information

Certificate of Analysis

Certificate of Analysis YOUR GREAT COMPANY 1234 ANY STREET CHICAGO, IL 60616 Certificate of Analysis Prepared for: YOUR GREAT COMPANY Phone Number: (888) 765-4321 Fax Number: (888) 123-4567 Email Address: your_email@email.com

More information

April 28, Town of Wilton Board of Education 395 Danbury Road Wilton, CT 06897

April 28, Town of Wilton Board of Education 395 Danbury Road Wilton, CT 06897 Town of Wilton Board of Education 395 Danbury Road Wilton, CT 06897 RE: Indoor Air Quality Assessment Report Miller-Driscoll School 217 Wolf Pit Road, Wilton, Connecticut TRC Project No. 215883.1000 Board

More information

This test report contains the following four sections: Chain of Custody, Data Detail, Frequently Asked Questions, and Glossary.

This test report contains the following four sections: Chain of Custody, Data Detail, Frequently Asked Questions, and Glossary. This test report contains the following four sections: Chain of Custody, Data Detail, Frequently Asked Questions, and Glossary. Direct Exam Chain of Custody Page 1 1 Results apply only to samples tested.

More information

Airborne Mould Sampling Moncton High School 207 Church Street Moncton, NB E1C 5A3. November 01, 2013

Airborne Mould Sampling Moncton High School 207 Church Street Moncton, NB E1C 5A3. November 01, 2013 Project # 18578 Airborne Mould Sampling Moncton High School 207 Church Street Moncton, NB E1C 5A3 November 01, 2013 Attention: Serge Melanson Transportation and Infrastructure Facilities Management Moncton

More information

EXPANDED FUNGAL REPORT

EXPANDED FUNGAL REPORT EXPANDED FUNGAL REPORT Prepared Exclusively For Report Date: 11/29/2007 Project: Accceditation"This report was generated in the EMSL Test Lab Page 1 of 23 1. Description of Analysis Analytical Laboratory

More information

Certificate of Mold Analysis

Certificate of Mold Analysis Tri-State Smart Home Solutions LLC CHRIS FARVER GALLIPOLIS, OH 45631 Certificate of Analysis Prepared for: CHRIS FARVER Phone Number: (74) 28-3966 Fax Number: Project Name: Test Location: Address City,

More information

Certificate of Analysis

Certificate of Analysis YOUR GREAT COMPANY 1234 ANY STREET CHICAGO, IL 60616 Certificate of Analysis Prepared for: YOUR GREAT COMPANY Phone Number: (888) 765-4321 Fax Number: (888) 123-4567 Email Address: your_email@email.com

More information

RLB CIH, LLC. Final Report Microbial Contamination Sampling Taos Recreation Center Taos, New Mexico. March 9, 2007

RLB CIH, LLC. Final Report Microbial Contamination Sampling Taos Recreation Center Taos, New Mexico. March 9, 2007 Final Report Microbial Contamination Sampling Taos Recreation Center Taos, New Mexico RLB CIH, LLC Ronald L. Beethe, CIH 505-268-5829 400 Alvarado NE FAX 256-9554 Albuquerque, NM 87108 rlbcih@comcast.net

More information

CITY OF FORT PIERCE HOUSING REHABILATION PROJECT FOR 2802 AVENUE I BID NO ADDENDUM NO. 4

CITY OF FORT PIERCE HOUSING REHABILATION PROJECT FOR 2802 AVENUE I BID NO ADDENDUM NO. 4 March 10, 2015 CITY OF FORT PIERCE HOUSING REHABILATION PROJECT FOR 2802 AVENUE I BID NO. 2015-022 ADDENDUM NO. 4 The purpose of this addendum is to extend the bid due date from 3:00PM, Tuesday, March

More information

Cer tif ica te of mold Anal y sis

Cer tif ica te of mold Anal y sis 3301 N.W. 55th S t., Ft. Lauderdale, FL 3 3 3 0 9 ( 8 0 0 ) 5 4 4-8 1 5 6 Cer tif ica te of mold Anal y sis P REPARED FOR : Professional Home Inspections Phone Number: (423) 306-0508 Email: kc@prohitn.com

More information

Indiana University Environmental Health & Safety Beau Middaugh 2427 E. 2nd street Bloomington, IN USA (812)

Indiana University Environmental Health & Safety Beau Middaugh 2427 E. 2nd street Bloomington, IN USA (812) Indiana University Environmental Health & Safety Beau Middaugh 2427 E. 2nd street Bloomington, IN 47401 USA (812) 855-6316 Approved by: Dates of Analysis: MoldReport Spore trap: 10-31-2018 and 10-31-2018

More information

SanAir Technologies Laboratory. Analysis Report. Hudson Valley Property Inspections, LLC

SanAir Technologies Laboratory. Analysis Report. Hudson Valley Property Inspections, LLC SanAir Technologies Laboratory Analysis Report prepared for Hudson Valley Property Inspections, LLC 8/3/2011 SanAir ID#: 804.897.1177 www.sanair.com August 3, 2011 SanAir ID # Dear Kevin Michaels, We at

More information

Berman Inspection, LLC

Berman Inspection, LLC Berman Inspection, LLC 5197 Palazzo Place Residential and Commercial Real Estate Inspections Boynton Beach, 33437-2073 Florida Licenses: HI10081 215-605-4380 MRSA 2560 BermanInspections@comcast.net MRSR

More information

Comments: Your Results

Comments: Your Results Pro-Lab Number: 2174-34 Date Collected: 2/12/24 Collection Location: BELL H 2 Sample Submitted: Micro 5 Volume (L): 25 Chain of Custody# 13234 Serial #: 74772 Results M5 Results M5 Spore Identification

More information

RE: Total Airborne Mould Spore Sampling Brookside Junior High 2239 Prospect Road, Hatchet Lake, NS

RE: Total Airborne Mould Spore Sampling Brookside Junior High 2239 Prospect Road, Hatchet Lake, NS 20 Duke Street, Suite 109 Tel: (902) 835-3727 Bedford, Nova Scotia Fax: (902) 835-5266 B4A 2Z5 Email: email@toalltech.com September 9 th, 2015 Tom Drury Assistant Regional Manager Operations Services Halifax

More information

Dealing With Dampness in Buildings

Dealing With Dampness in Buildings Dealing With Dampness in Buildings Excessive Moisture and its Affect on the Home Environment 1of 68 How Long Has Mold Been a Problem? Leviticus 14:45 A house desecrated by mildew, mold, or fungus would

More information

Joseph T. Burkeson. Tuesday, November 19th, Total Professional Installation 1293 N. 60th St Tampa Fl, 33619

Joseph T. Burkeson. Tuesday, November 19th, Total Professional Installation 1293 N. 60th St Tampa Fl, 33619 Tuesday, November 19th, 2013 Total Professional Installation 1293 N. 60th St Tampa Fl, 33619 Mold Sample Survey 37612 Oak Terrace, St Petersburg, FL 33703 On Friday, November 15th, 2013 I performed a Mold

More information

SDRP JOURNAL OF EARTH SCIENCES & ENVIRONMENTAL STUDIES (ISSN: )

SDRP JOURNAL OF EARTH SCIENCES & ENVIRONMENTAL STUDIES (ISSN: ) SDRP JOURNAL OF EARTH SCIENCES & ENVIRONMENTAL STUDIES (ISSN: 2472-6397) 2017 RESEARCH Seasonal Impacts on Indoor Fungal Concentrations After Mold Remediation DOI: 10.15436/JESES.2.1.2 G.T. Kleinheinz*

More information

IAQ Mold Concerns. CAPT Don Hagen, USN, MS, CIH Navy Marine Corp Public Health Center

IAQ Mold Concerns. CAPT Don Hagen, USN, MS, CIH Navy Marine Corp Public Health Center IAQ Mold Concerns CAPT Don Hagen, USN, MS, CIH Navy Marine Corp Public Health Center 0 Disclaimer The views expressed in this presentation are those of the author and do not necessarily reflect the official

More information

Certificate of Mold Analysis

Certificate of Mold Analysis ACE ENVIRONMENTAL 49 SHADOWCREEK WAY ORMOND BEACH, FL 32174 Certificate of Mold Analysis Prepared for: ACE ENVIRONMENTAL Phone Number: (904) 859-9211 Fax Number: Project Name: PINNAMENENI Test Location:

More information

Schneider Laboratories Global, Inc

Schneider Laboratories Global, Inc Analysis Report Schneider Laboratories Global, Inc 2512 W. Cary Street Richmond, Virginia 23220-5117 804-353-6778 800-785-LABS (5227) Fax 804-359-1475 Customer: Asbestos Science Technologies, Inc (4038)

More information

EFFECT OF DIFFERENT AIR FLOW RATES ON THE COLLECTION OF ATMOSPHERIC MOLD SPORES OF DIFFERENT SIZES BY A SLIT IMPACTOR

EFFECT OF DIFFERENT AIR FLOW RATES ON THE COLLECTION OF ATMOSPHERIC MOLD SPORES OF DIFFERENT SIZES BY A SLIT IMPACTOR Air Pollution XXV 243 EFFECT OF DIFFERENT AIR FLOW RATES ON THE COLLECTION OF ATMOSPHERIC MOLD SPORES OF DIFFERENT SIZES BY A SLIT IMPACTOR ATIN ADHIKARI, BUSHRA SHAH, TEDDYE GANDY, OREOLUWA ADEYINKA &

More information

FINAL REPORT- Part 1 & Part 2

FINAL REPORT- Part 1 & Part 2 FINAL REPORT- Part 1 & Part 2 Customer Name Customer Address Contact Shaw Industries Group Inc 1010 VD Parrott Jr Pkwy, Dalton, GA 10722, USA Paul Murray Sample Description Carpet Number of Samples 9 Commencement

More information

Certificate of Mold Analysis

Certificate of Mold Analysis ACE ENVIRONMENTAL 300 BELLA HARBOR CT #111 PALM COAST, FL 32137 Certificate of Mold Analysis Prepared for: ACE ENVIRONMENTAL Phone Number: (904) 859-9211 Fax Number: Project Name: Test Location: 1745 WINDSONG

More information

Overcoming the Barriers to Establishing Quantitative Health Guidance Values for Airborne Mold 2019 IAQA Annual Meeting

Overcoming the Barriers to Establishing Quantitative Health Guidance Values for Airborne Mold 2019 IAQA Annual Meeting Bill Sothern, DrPH, MS, CIH Microecologies, Inc. bsothern@microecologies.com Overcoming the Barriers to Establishing Quantitative Health Guidance Values for Airborne Mold The Association Between Mold and

More information

Certificate of Analysis

Certificate of Analysis HOME INSPECTION COMPANY 1234 HOME INSPECTION PKWY ANYTOWN, FL 33326 Certificate of Analysis Prepared for: HOME INSPECTION COMPANY Phone Number: (888) 222-2222 Fax Number: (888) 222-3333 Email Address:

More information

49 Woodside Street Stamford, CT 06902

49 Woodside Street Stamford, CT 06902 Environmental Consultants And Laboratory Services 11 HYGENIX, INC. 49 Woodside Street Stamford, CT 06902 (203) 324-2222 Fax (203) 324-3876 Westport Public Schools Attn. Craig Schmarr 110 Myrtle Ave Westport,

More information

Energy & Environmental Solutions, Inc. Mold Facts/Fiction/Who Knows

Energy & Environmental Solutions, Inc. Mold Facts/Fiction/Who Knows Energy & Environmental Solutions, Inc. Mold Facts/Fiction/Who Knows Cincinnati Bar Association - Construction Law Committee September 14, 2004 Hi, my name is Introductions Brian J. O Connell, Esq. Dinsmore

More information

WHAT DOES MOLD MEAN? J&M Environmental Control Group 14 Monarch Bay Plaza, #470 Monarch Beach, CA 92629

WHAT DOES MOLD MEAN? J&M Environmental Control Group 14 Monarch Bay Plaza, #470 Monarch Beach, CA 92629 WHAT DOES MOLD MEAN? by J&M Environmental Control Group 14 Monarch Bay Plaza, #470 Monarch Beach, CA 92629 800-214 214-9959 Black killer mold eats husband s brain, poisons crystal chandelier, woman given

More information

Aerobiologia Intetnltla~l Journal of Aerobiology

Aerobiologia Intetnltla~l Journal of Aerobiology Aerobiologia Intetnltla~l Journal of Aerobiology ELSEVIER Aerobiologia 11 (1995) 27-34 Indoor air quality in schools: exposure to fungal allergens Estelle Levetin *a, Richard Shaughnessy h, Eugene Fisher

More information

SUBJECT: Administration Building - IAQ - Initial Contact report - Room 217, Hallway outside Room 217, Room 201, Room 225, Room 212

SUBJECT: Administration Building - IAQ - Initial Contact report - Room 217, Hallway outside Room 217, Room 201, Room 225, Room 212 DATE: February 15, 2016 TO: Sandi Maddox, Director SUBJECT: Administration Building - IAQ - Initial Contact report - Room 217, Hallway outside Room 217, Room 201, Room 225, Room 212 I received Work Order

More information

Certificate of Analysis

Certificate of Analysis YOUR GREAT COMPANY 1234 ANY STREET CHICAGO, IL 60616 Certificate of Analysis Prepared for: YOUR GREAT COMPANY Phone Number: (888) 765-4321 Fax Number: (888) 123-4567 Email Address: your_email@email.com

More information

DATE: September 12, TO: Curtis Martin, Principal. SUBJECT: Tom Hicks ES - IAQ - Air Test Results - Nurses' Office, Main Admin Office

DATE: September 12, TO: Curtis Martin, Principal. SUBJECT: Tom Hicks ES - IAQ - Air Test Results - Nurses' Office, Main Admin Office DATE: September 12, 2017 TO: Curtis Martin, Principal SUBJECT: Tom Hicks ES - IAQ - Air Test Results - Nurses' Office, Main Admin Office On Tuesday 9/5, Apex-Titan Air tested the Nurses Office and the

More information

PRO-TEC MOLD REPORT. Mold Evaluation

PRO-TEC MOLD REPORT. Mold Evaluation PRO-TEC MOLD REPORT CLIENT & SITE INFORMATION: DATE OF INSPECTION: 09/17/20. CLIENT NAME:. NUMBER & STREET: CITY/STATE/ZIP: Reston VA 20191. INSPECTED BY: Rob Hopkin. CLIMATIC CONDITIONS: WEATHER: Clear.

More information

Regulatory Compliance 245 Albany Avenue Thornwood, New York (914) Indoor Air Quality Screening At. Scarsdale UFSD

Regulatory Compliance 245 Albany Avenue Thornwood, New York (914) Indoor Air Quality Screening At. Scarsdale UFSD Regulatory Compliance 245 Albany Avenue Thornwood, New York 10594 (914) 439-6513 Indoor Air Quality Screening At DRAFT Scarsdale UFSD High School 1057 East post Road Scarsdale, NY 10583 Various Rooms RegCom

More information

Based on our review, the following primary chemical constituents were identified for sampling: Acetone Toluene Xylenes Heptane

Based on our review, the following primary chemical constituents were identified for sampling: Acetone Toluene Xylenes Heptane December 15, 2017 Mr. Jeremy McDevitt Kenston Local Schools 1719 Snyder Road Chagrin Falls, Ohio 44022 RE: Indoor Air Quality Evaluation Kenston Middle School, 17425 Snyder Road, Kenston, Ohio OH41465

More information

Antelope Valley College Joel I. Berman, CIH, CSP, CIAQM, CAC February 26 and 27, 2014

Antelope Valley College Joel I. Berman, CIH, CSP, CIAQM, CAC February 26 and 27, 2014 Mold and Fungi Awareness (Fungus 101) Antelope Valley College Joel I. Berman, CIH, CSP, CIAQM, CAC February 26 and 27, 2014 2 Mold and Fungi Awareness Fungus Mushrooms Yeasts Rusts Molds Smut Characterized

More information

Regulatory Compliance 245 Albany Avenue Thornwood, New York (914) Indoor Air Quality Screening At. Scarsdale UFSD

Regulatory Compliance 245 Albany Avenue Thornwood, New York (914) Indoor Air Quality Screening At. Scarsdale UFSD Regulatory Compliance 245 Albany Avenue Thornwood, New York 10594 (914) 439-6513 Indoor Air Quality Screening At Scarsdale UFSD Greenacres School 41 Huntington Avenue Scarsdale, NY 10583 RegCom s Project

More information

EVALUATION OF THE CYCLEX IMPACTOR PHASE 2: REPORT 3

EVALUATION OF THE CYCLEX IMPACTOR PHASE 2: REPORT 3 EVALUATION OF THE CYCLEX IMPACTOR PHASE 2: COLLECTION EFFICIENCY EVALUATION WITH MICROBIAL SPORES (IMPACTOR S CONFIGURATIONS 1, 2, AND 3) REPORT 3 Submitted to: ENVIRONMENTAL MONITORING SYSTEMS, INC. Prepared

More information