IMPACT OF DEPENDENT FAILURE ON SIL ASSESSMENT

Size: px
Start display at page:

Download "IMPACT OF DEPENDENT FAILURE ON SIL ASSESSMENT"

Transcription

1 IMPACT OF DEPENDENT FAILURE ON SIL ASSESSMENT Alan G King ABB Engineering Services, Pavilion 9, Belasis Hall Technology Park, Billingham, Cleveland TS23 4YS, UK; Tel: þ44 (0) , Fax: þ44 (0) , alan.g.king@gb.abb.com Over the last five years or so, the operators of chemical sites and other high hazard facilities have been considering the implications of functional safety standards such as IEC and the sector specific standards derived from IEC These standards offer guidance on the management of functional safety systems and provide an approach the demonstration that the risk to people and the environment is being managed appropriately. As part of the management process, it is necessary to undertake a hazard and risk assessment to determine the amount of risk reduction required to be provided by electrical, electronic or programmable electronic safety related systems. The output of this process is a Target Safety Integrity Level (SIL) for each safety instrumented function. The demonstration of appropriate management of risk then requires that the, as designed and implemented, safety function achieves a performance (designed or achieved SIL) that at least meets the target SIL. The methods and techniques commonly used for hazard and risk analysis and the determination of target SIL frequently make the assumption that all the relevant protective measures are considered to be independent. This paper will address the significance of dependent failure and the vital importance of its consideration both in relation to the assessment of the target SIL and with respect to the designed or achieved SIL. It will note that failure to consider dependent failure may lead to a level of risk that is one or more orders of magnitude higher than intended. The paper will conclude with some examples of the type of dependency that can be encountered and the significance of its impact. BACKGROUND Dependent failure has for several decades been recognised as a highly important issue but largely in the nuclear industry. In contrast, in the process sector it has not been recognised as an issue of importance to the extent that it really warrants. With the increasing use of techniques for the assessment of Safety Integrity Levels as part of the application of standards such as IEC [1] and IEC [2], it is vitally important that the process sector gains sufficient understanding of the issues raised by dependent failure and how to deal with them. Failure to do this will lead to increasing numbers of inadequate assessments and the hand-over of poor guidance to the next generation of engineers. Furthermore, assessments, that fail to recognise dependent failure and to take it into account, are likely to lead to the insufficient provision of risk reduction measures across the industry, with the resulting levels of risk significantly higher than the assessments indicate. These risk levels may well be higher by one or more order of magnitude. SCOPE This paper will cover some of the common cause or dependency issues that occur in SIL Assessments. It will also provide some examples to highlight these issues, showing where and how they can occur. #2007 ABB Engineering Services. Third parties have access for limited use and no right to copy any further. IChemE have intellectual property rights to make this paper avialable but ABB are the copyright owners WHAT IS DEPENDENT FAILURE Dependent failure can be classified in one of two types: (a) Classic Dependency and (b) Functional Dependency. CLASSIC DEPENDENCY Classic dependency is what is often referred to as common cause failure or common mode failure. It can occur where two or more functional units are similar and are operating under the same conditions. Classic dependency occurs when the trigger for the failure of one unit affects others and causes failure of them at or around the same time. For example, two pressure sensors sensing the pressure in a particular vessel will probably be of similar types, close together in the same environment and will be sensing the same process fluid. FUNCTIONAL DEPENDENCY Functional dependency is where a group of two or more functional units depend for their correct operation on the correct functioning of another single unit. Typical examples would include a single sensor used to provide a signal to operate both an alarm and a trip function. Failure of the sensor would affect both the alarm and the trip. DEPENDENCY RELATING TO PEOPLE Dependency affecting items of equipment is comparatively well recognised; what is much less well recognised is that there can be dependency associated with human actions. Examples include: 1

2 . People doing the same task can make the same error.. People, using the same equipment at different times, can make a similar error using it.. Two or more tasks carried out by the same person same error repeated on each task.. One person checking the work of another the checker fails to detect the error that the first person missed, for the same reason. Dependency can also affect a combination of equipment and people. For example, a sensor monitoring process pressure may be used to control the process pressure but also to provide an alarm for the control room operators on high pressure. The sensor fails and reads low. The control function will seek to increase the process pressure. The operator receives no alarm and is therefore not prompted to take action. Furthermore, any review of the pressure indication by the operator would suggest that the pressure is low and therefore no action is required 1. PROTECTION LAYER MODEL It is commonplace to consider the control and protective measures on a process as a Layered Model. A typical illustration of this is given in Figure 1. Simple analysis for safety integrity level assessments assumes that there is complete independence: (a) the failures of different measures within a single layer are independent and (b) the failure of measures in one layer is not linked to the failure of the measures in another layer 2. In reality, there is often dependency that needs to be considered. DEPENDENCY WITHIN A LAYER An example of dependency within a layer is shown in Figure 2. It shows part of an instrumented protective function with three identical pressure sensors monitoring the same process pressure. There is potential here for common cause failure of all three pressure transmitters. Figure 1. Protection layer model DEPENDENCY BETWEEN LAYERS Dependency between layers is often more difficult to recognise. In Figure 3, the same three pressure sensors are monitoring pressure but in this case, each is associated with a function in a different layer (1) a control function (2) an alarm function and (3) an automated trip function. The potential for common cause or dependent failure still exists, but the analysis is more challenging. In Figure 4, we have another example with potential dependency between layers. In this example, the control and alarm functions are sharing a transmitter. This is a functional dependency: dangerous failure of PT1 means immediate loss of control and no alarm due to sharing across layers. The potential for common cause failure of both pressure transmitters also exists and would result in a loss of control, alarm and trip functions. HOW IS THE MAGNITUDE OF DEPENDENT FAILURE ASSESSED A typical safety instrumented function is shown in Figure 5 with a 1oo2 voting arrangement between the sensors and also between the final elements. There may also be redundancy and voting within the logic solver. Wherever there is 1oo2 or other voting, dependency needs to be considered. If we look at the two sensors in Figure 5, the working and failure states can be illustrated as in Figure 6. The most widely used method for assessing the proportion dependent failures is the Beta Factor Method. 1 It is recognised that in some situations there will be other indications that the operator can use to assess whether there is a process problem or not. 2 This is the underlying assumption in Layer Of Protection Analysis, Event Tree Analysis etc. Figure 2. Dependency within a layer 2

3 Figure 5. Typical safety function provides what is a rather complex equation: Figure 3. Dependency between layers (1) BETA FACTOR METHOD In this method, the Beta Factor (b) is defined as: PFDavg ¼ 2 ((1 b D )l DD þ (1 b)l DU ) 2 l DU T i l D 2 þ MTTR þ l DDMTTR l D l DU T i l D 3 þ MTTR þ l DDMTTR l D þ (b D l DD MTTR) T i þ bl DU 2 þ MTTR Dependent Dangerous Failure Rate Beta FactorðbÞ ¼ Total Dangerous Failure Rate where: b l MTTR Ti Common Cause Beta Factor (b D is for detected by diagnostics) Failure Rate (D ¼ Total Dangerous Failures; DD ¼ Dangerous Detected; DU ¼ Dangerous Undetected) Mean Time to Repair Proof Test Interval For calculation of the average probability of failure on demand for a 1oo2 voting arrangement, IEC However, if we assume (a) that the mean time to repair is small compared with the Proof Test Interval and (b) that dangerous failures are only found at proof test (so that l DU ¼ l D and l DD ¼ 0), then the previous equation for 1oo2 simplifies and is more easily understood: PFDavg ¼ 4 3 (1 b)l T 2 i T i D þ bl D 2 2 fflfflfflfflfflfflfflfflfflfflfflfflffl{zfflfflfflfflfflfflfflfflfflfflfflfflffl} fflfflfflfflffl{zfflfflfflfflffl} Independent Common cause failure of both failure affecting sensors both sensors There are also similar equations for other voting arrangements: Figure 4. Dependency between layers (2) T 3 i T i 1oo3 PFDavg ¼ 2 (1 b)l D þ bl D 2 2 1oo4 PFDavg ¼ 16 5 (1 b)l T 4 i T i D þ bl D 2 2 3

4 Figure 6. Working and failure states for 1oo2 PUTTING SOME NUMBERS IN... For a single sensor with a PFDavg of and using a Beta Factor of 0.1, we can see in the following table the importance of including dependency in the calculation: Independent PFDavg Dependent PFDavg Total PFDavg 1oo2 2.43E-04 14% 1.50E-03 86% 1.74E-03 1oo3 4.92E % 1.50E % 1.50E-03 1oo4 1.06E % 1.50E % 1.50E-03 question is what is the probability that Person B does not detect the error that Person A has failed to notice? Answering these questions and taking dependency into account is not easy to do. The best guidance is Don t claim multiple layers of human reliability. This will avoid the issue of dependency. SOME EXAMPLES TO THINK ABOUT Here are two examples, to think about the implications of dependency on SIL Assessment. Omitting dependency makes a BIG difference in all the cases above, dependency is accounting for more than 85% of the total probability of failure. ASSESSING THE VALUE OF BETA The value of Beta is usually in the range from 30% down to 0.1%. The assessment of an appropriate value involves consideration of factors such as: Separation, Diversity & Redundancy, Complexity, Analysis, Procedures, Training, Environment Control, and Environmental Tests. There is some guidance in IEC Annex D. There is also guidance to be found in other publications [3]. Small Beta Factors are progressively more difficult to achieve. EXAMPLE 1 Figure 7 shows a process column with two notionally independent alarms: Level Alarm High (LAH) and Level Alarm High-High (LAHH). From a dependency perspective, the HUMAN DEPENDENCY If you include the impact of humans on functional safety (and one should in order to comply with standards) then dependency is an important factor. Dependency is when a failure at one step in a task makes the probability of failure at the a later step more likely than if the earlier step had been successful. Consider, for example, the task of Checking. Person A has completed a task and thinks it has been done fully and correctly. Person B is asked to check. Checking is only of value when Person A has made an error AND Person A has not realised the error has occurred. The key Figure 7. Example 1: two independent alarms 4

5 Figure 8. Example 2: section of plant alarm hardware will have some potential for common cause failure, especially if both use the same technology. However, both alarms are also dependent on the operator for any action to occur. This raises two critical questions: (1) How long does the operator have between the Level Alarm High (LAH) and a hazardous event 10 min, 20 min, 30 min or more? Is it enough for effective response? (2) If the operator fails to respond effectively to LAH in the time available but does notice LAHH, there is even less time for response; so does LAHH have any real risk reduction benefit? The answer to this last question is probably No. Figure 9. Initial analysis EXAMPLE 2 Figure 8 shows some pipework on a plant, which connects a high pressure (HP) section to a low pressure (LP) section. There is a defined start up routine to ensure that the two sections are isolated before the HP section pressure exceeds the rating of the LP section: (1) Check that block valves between HP and LP sections of plant are open (A&B) and bleed valve (C) is closed; (2) Raise pressure in HP section to 5 bar; (3) Close block valves (A&B), open bleed valve (C); (4) Continue raising HP pressure to 30 bar. Initial analysis of the potential frequency of over pressure of the LP section gives a value of 2.5 x / yr and is shown in Figure 9. It was then proposed that this be improved by the installation of a safety instrumented function to provide isolation in the event of an operator failing to close the manual valves. This is shown in Figure 10. The high pressure trip setting is 5.5 bar and is assumed in the analysis to have safety integrity level of SIL 1 and a failure probability of The analysis for Figure 10. Improved design 5

6 Figure 11. Analysis of improvement Figure 12. Revised analysis this is shown in Figure 11 and gives a frequency of 1.25 x /yr. However, at start-up the operators adopted the practice of (a) waiting for HP Trip to function as pressure increased and (b) then going to operate the manual isolation valves. The revised analysis for this is shown in Figure 12. The analysis now gives a frequency of 1.25 x /yr. The dependency between trip operation and manual valve closure is shown to increase the hazardous event frequency by a factor of 100. The analysis shown has been simplified to help illustrate the problem. In practice, there are a number of ways in which the situation may be improved. (a) Reinforcement of correct start-up procedure by management. (b) Recovery - the operators realising that the trip has not functioned and closing the manual valves late, but before damage to the LP section occurs. (c) Testing the trip just prior to start-up to achieve a significantly lower PFDavg. But the problem needs to be recognised before it can be addressed. CONCLUSIONS Dependency is very important in any form of SIL Assessment. The assessor needs to think carefully where it could occur this is often quite challenging. If you fail to consider it and omit dependency from your assessment, then the level of risk is likely to be significantly higher than you have assessed by one or more decades. Consideration of dependent failure is relevant no matter what technique for assessment you are using. Whether this be Event Trees, Fault Trees, LOPA or Risks Graphs dependent failure is important. ACKNOWLEDGEMENTS The author would like to acknowledge the many conversations with colleagues who have helped in the formulation of the matters discussed in this paper. REFERENCES 1. IEC 61508: Functional safety of electrical/electronic/ programmable electronic safety-related systems, International Electrotechnical Commission, Geneva, 1998 & IEC 61511: Functional safety Safety instrumented systems for the process industry sector, International Electrotechnical Commission, Geneva, UPM 3.1: A Pragmatic Approach to Dependent Failures Assessment for Standard Systems, V P Brand, AEA Technology,

Proof testing of safety-instrumented systems: New testing strategy induced by dangerous detected failures

Proof testing of safety-instrumented systems: New testing strategy induced by dangerous detected failures Proof testing of safety-instrumented systems: New testing strategy induced by dangerous detected failures Yiliu Liu, Marvin Rausand Department of Production and Quality Engineering, Norwegian University

More information

ISO INTERNATIONAL STANDARD. Non-destructive testing Qualification of personnel for limited applications of non-destructive testing

ISO INTERNATIONAL STANDARD. Non-destructive testing Qualification of personnel for limited applications of non-destructive testing INTERNATIONAL STANDARD ISO 20807 First edition 2004-03-01 Non-destructive testing Qualification of personnel for limited applications of non-destructive testing Essais non destructifs Qualification du

More information

ISO INTERNATIONAL STANDARD. Steel products Employer's qualification system for non-destructive testing (NDT) personnel

ISO INTERNATIONAL STANDARD. Steel products Employer's qualification system for non-destructive testing (NDT) personnel INTERNATIONAL STANDARD ISO 11484 Second edition 2009-02-15 Steel products Employer's qualification system for non-destructive testing (NDT) personnel Produits en acier Système de qualification, par l'employeur,

More information

ATyS Bypass Enclosed solution from 40 to 3200 A

ATyS Bypass Enclosed solution from 40 to 3200 A ATyS Bypass Enclosed solution from 40 to 3200 A A complete enclosed range of ATyS dedicated to bypass function Architecture SINGLE LINE DOUBLE LINE Voltage Sensing Voltage Sensing RANGE FROM 40 TO 3200

More information

Achieving Effective and Reliable NDT in the Context of RBI

Achieving Effective and Reliable NDT in the Context of RBI Achieving Effective and Reliable NDT in the Context of RBI S Smalley, Royal & SunAlliance & B W Kenzie, TWI 1. SCOPE Plant owners/operators are now managing the integrity of their plant and planning inspection

More information

ISO INTERNATIONAL STANDARD. Steel products Employer's qualification system for non-destructive testing (NDT) personnel

ISO INTERNATIONAL STANDARD. Steel products Employer's qualification system for non-destructive testing (NDT) personnel INTERNATIONAL STANDARD ISO 11484 Second edition 2009-02-15 Steel products Employer's qualification system for non-destructive testing (NDT) personnel Produits en acier Système de qualification, par l'employeur,

More information

Vibration och stöt Tillståndskontroll och diagnos av maskiner Allmänna riktlinjer för tolkning av data och diagnosteknik (utvärderingsmetoder)

Vibration och stöt Tillståndskontroll och diagnos av maskiner Allmänna riktlinjer för tolkning av data och diagnosteknik (utvärderingsmetoder) SVENSK STANDARD SS-ISO 13379 Fastställd 2003-09-19 Utgåva 1 Vibration och stöt Tillståndskontroll och diagnos av maskiner Allmänna riktlinjer för tolkning av data och diagnosteknik (utvärderingsmetoder)

More information

ISO INTERNATIONAL STANDARD

ISO INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO 26782 First edition 2009-07-15 Anaesthetic and respiratory equipment Spirometers intended for the measurement of time forced expired volumes in humans Matériel d'anesthésie et

More information

ISO INTERNATIONAL STANDARD. Implants for surgery Active implantable medical devices Part 2: Cardiac pacemakers

ISO INTERNATIONAL STANDARD. Implants for surgery Active implantable medical devices Part 2: Cardiac pacemakers INTERNATIONAL STANDARD ISO 14708-2 Second edition 2012-08-15 Implants for surgery Active implantable medical devices Part 2: Cardiac pacemakers Implants chirurgicaux Dispositifs médicaux implantables actifs

More information

ISPM No. 9 GUIDELINES FOR PEST ERADICATION PROGRAMMES (1998)

ISPM No. 9 GUIDELINES FOR PEST ERADICATION PROGRAMMES (1998) ISPM No. 9 INTERNATIONAL STANDARDS FOR PHYTOSANITARY MEASURES ISPM No. 9 GUIDELINES FOR PEST ERADICATION PROGRAMMES (1998) Produced by the Secretariat of the International Plant Protection Convention FAO

More information

XOSERVE LIMITED SERVICES SCHEDULE FOR THE PROVISION OF NON-CODE USER PAYS SERVICES (REFERENCE NUMBER XNCUP(SS)06) DATED 20 INTRODUCTION

XOSERVE LIMITED SERVICES SCHEDULE FOR THE PROVISION OF NON-CODE USER PAYS SERVICES (REFERENCE NUMBER XNCUP(SS)06) DATED 20 INTRODUCTION XOSERVE LIMITED SERVICES SCHEDULE FOR THE PROVISION OF NON-CODE USER PAYS SERVICES (REFERENCE NUMBER XNCUP(SS)06) DATED 20 INTRODUCTION 1 This services schedule forms part of the framework contract for

More information

ISO 5495 INTERNATIONAL STANDARD. Sensory analysis Methodology Paired comparison test. Analyse sensorielle Méthodologie Essai de comparaison par paires

ISO 5495 INTERNATIONAL STANDARD. Sensory analysis Methodology Paired comparison test. Analyse sensorielle Méthodologie Essai de comparaison par paires INTERNATIONAL STANDARD ISO 5495 Third edition 2005-11-15 Sensory analysis Methodology Paired comparison test Analyse sensorielle Méthodologie Essai de comparaison par paires Reference number ISO 2005 Provläsningsexemplar

More information

Scope of Practice for the Diagnostic Ultrasound Professional

Scope of Practice for the Diagnostic Ultrasound Professional Scope of Practice for the Diagnostic Ultrasound Professional Copyright 1993-2000 Society of Diagnostic Medical Sonographers, Dallas, Texas USA: All Rights Reserved Worldwide. Organizations which endorse

More information

Field data reliability analysis of highly reliable item

Field data reliability analysis of highly reliable item Field data reliability analysis of highly reliable item David Valis University of Defence, Czech Republic david.valis@unob.cz Miroslav Koucky Technical University of Liberec, Czech Republic miroslav.koucky@tul.cz

More information

Effective Airflow Visualization Studies. Gordon Farquharson, July 2017

Effective Airflow Visualization Studies. Gordon Farquharson, July 2017 Effective Airflow Visualization Studies Gordon Farquharson, July 2017 Slide 1 PharmOut 2017 Agenda Regulatory imperative Role of CFD Air velocity measurements Airflow visualisation to prove effectiveness

More information

ISO INTERNATIONAL STANDARD

ISO INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO 15197 First edition 2003-05-01 In vitro diagnostic test systems Requirements for blood-glucose monitoring systems for self-testing in managing diabetes mellitus Systèmes d'essais

More information

This document is a preview generated by EVS

This document is a preview generated by EVS INTERNATIONAL STANDARD ISO 14708-7 First edition 2013-01-15 Implants for surgery Active implantable medical devices Part 7: Particular requirements for cochlear implant systems Implants chirurgicaux Dispositifs

More information

ISO INTERNATIONAL STANDARD. Sterile hypodermic syringes for single use Part 4: Syringes with re-use prevention feature

ISO INTERNATIONAL STANDARD. Sterile hypodermic syringes for single use Part 4: Syringes with re-use prevention feature INTERNATIONAL STANDARD ISO 7886-4 First edition 2006-10-01 Sterile hypodermic syringes for single use Part 4: Syringes with re-use prevention feature Seringues hypodermiques stériles, non réutilisables

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD 7886- First edition 996-05-5 Sterile hypodermic syringes for Single use - Part : Syringes for use with power-driven Syringe Pumps Seringues hypodermiques st&iles, non r&mkables -

More information

Single market, regulatory environment, industries under vertical legislation Pharmaceuticals : regulatory framework and market authorisations

Single market, regulatory environment, industries under vertical legislation Pharmaceuticals : regulatory framework and market authorisations EUROPEAN COMMISSION ENTERPRISE DIRECTORATE-GENERAL Single market, regulatory environment, industries under vertical legislation Pharmaceuticals : regulatory framework and market authorisations Brussels,

More information

GUIDE TO THE APPLICATION TO POSSESS AND USE A SOURCE(S) FOR INDUSTRIAL APPLICATIONS

GUIDE TO THE APPLICATION TO POSSESS AND USE A SOURCE(S) FOR INDUSTRIAL APPLICATIONS ATOMIC ENERGY COUNCIL GUIDE TO THE APPLICATION TO POSSESS AND USE A SOURCE(S) FOR INDUSTRIAL APPLICATIONS Item Type of Application 1 Name and address of applicant 2 Radiation safety Officer (RSO) Guiding

More information

EPF s response to the European Commission s public consultation on the "Summary of Clinical Trial Results for Laypersons"

EPF s response to the European Commission s public consultation on the Summary of Clinical Trial Results for Laypersons EPF s response to the European Commission s public consultation on the "Summary of Clinical Trial Results for Laypersons" August 2016 This document received funding under an operating grant from the European

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60601-2-37 2001 AMENDMENT 1 2004-08 Amendment 1 Medical electrical equipment Part 2-37: Particular requirements for the safety of ultrasonic medical diagnostic and monitoring

More information

ISO INTERNATIONAL STANDARD. Ergonomics Accessible design Sound pressure levels of auditory signals for consumer products

ISO INTERNATIONAL STANDARD. Ergonomics Accessible design Sound pressure levels of auditory signals for consumer products INTERNATIONAL STANDARD ISO 24501 First edition 2010-12-15 Ergonomics Accessible design Sound pressure levels of auditory signals for consumer products Ergonomie Conception accessible Niveaux de pression

More information

Increasing the supply of Reseller Identification Codes (RIDs) A statement on ensuring there are sufficient RID administrative codes

Increasing the supply of Reseller Identification Codes (RIDs) A statement on ensuring there are sufficient RID administrative codes Increasing the supply of Reseller Identification Codes (RIDs) A statement on ensuring there are sufficient RID administrative codes Redactions are indicated by [ ] Statement Publication date: 5 March 2015

More information

BACKGROUND + GENERAL COMMENTS

BACKGROUND + GENERAL COMMENTS Response on behalf of Sobi (Swedish Orphan Biovitrum AB) to the European Commission s Public Consultation on a Commission Notice on the Application of Articles 3, 5 and 7 of Regulation (EC) No. 141/2000

More information

NANDTB-F012 Rev 0 Audit Checklist

NANDTB-F012 Rev 0 Audit Checklist NANDTB-F012 Rev 0 Audit Checklist 1. Foreword Minimum Requirements for the Structured Training of Non-Destructive Testing Institutes This document is based upon CEN Technical Report 25108:2006, which is

More information

Part 1: General requirements

Part 1: General requirements Provläsningsexemplar / Preview INTERNATIONAL STANDARD ISO 10555-1 Second edition 2013-06-15 Corrected version 2014-01-15 Intravascular catheters Sterile and single-use catheters Part 1: General requirements

More information

Analysis of the human risk factor which affects the reliability and safety of machinery

Analysis of the human risk factor which affects the reliability and safety of machinery Safety and Security Engineering VI 287 Analysis of the human risk factor which affects the reliability and safety of machinery G. Hotta 1, D. Ishibashi 1, Y. Ohbuchi 2 & H. Sakamoto 3 1 Department of Mechanical

More information

Provide body electrical treatments

Provide body electrical treatments Provide body electrical treatments US30B13 Learner name: Learner number: VTCT is the specialist awarding body for the Hairdressing, Beauty Therapy, Complementary Therapy and Sport and Active Leisure sectors,

More information

Control of Noise at Work Procedure

Control of Noise at Work Procedure WILTSHIRE POLICE FORCE PROCEDURE Control of Noise at Work Procedure Effective from: 11.05.2015 Page 1 of 12 TABLE OF CONTENTS Identification... 3 Ownership... 3 Revision History... 3 Approvals... 3 Distribution...

More information

TC65B, WG6. IEC Industrial Process Control Systems Guideline for evaluating process control systems. Micaela Caserza Magro Paolo Pinceti

TC65B, WG6. IEC Industrial Process Control Systems Guideline for evaluating process control systems. Micaela Caserza Magro Paolo Pinceti COMITATO ELETTROTECNICO ITALIANO TC65B, WG6 IEC 62603 Industrial Process Control s Guideline for evaluating process control systems Micaela Caserza Magro Paolo Pinceti The origin of the idea F UK Group

More information

FDAP Drug & Alcohol Professional Certification Workplace Assessment

FDAP Drug & Alcohol Professional Certification Workplace Assessment DANOS AB2 Support individuals who are substance users This unit is about supporting individuals who are substance users by enabling them to adopt safe practices, providing care and support following an

More information

ISO INTERNATIONAL STANDARD. Sterile single-use intravascular catheter introducers

ISO INTERNATIONAL STANDARD. Sterile single-use intravascular catheter introducers INTERNATIONAL STANDARD ISO 11070 First edition 1998-05-01 Sterile single-use intravascular catheter introducers Introducteurs de cathéters intravasculaires stériles, non réutilisables A Reference number

More information

Anaesthetic and respiratory equipment Nebulizing systems and components

Anaesthetic and respiratory equipment Nebulizing systems and components Provläsningsexemplar / Preview INTERNATIONAL STANDARD ISO 27427 Third edition 2013-12-15 Anaesthetic and respiratory equipment Nebulizing systems and components Matériel d anesthésie et de réanimation

More information

UKAS Guidance on the Application of ISO/IEC Dealing with Expressions of Opinions and Interpretations

UKAS Guidance on the Application of ISO/IEC Dealing with Expressions of Opinions and Interpretations LAB 13 Expression of opinions & interpretations UKAS Guidance on the Application of ISO/IEC 17025 Dealing with Expressions of Opinions and Interpretations [UKAS Publication ref: LAB 13] Contents Section

More information

ISO INTERNATIONAL STANDARD. Dentistry Powered toothbrushes General requirements and test methods

ISO INTERNATIONAL STANDARD. Dentistry Powered toothbrushes General requirements and test methods INTERNATIONAL STANDARD ISO 20127 First edition 2005-03-15 Dentistry Powered toothbrushes General requirements and test methods Art dentaire Brosses à dents électriques Exigences générales et méthodes d'essai

More information

Nuclear energy, nuclear technologies, and radiological protection Vocabulary. Part 4: Dosimetry for radiation processing

Nuclear energy, nuclear technologies, and radiological protection Vocabulary. Part 4: Dosimetry for radiation processing Provläsningsexemplar / Preview INTERNATIONAL STANDARD ISO 12749-4 First edition 2015-08-15 Nuclear energy, nuclear technologies, and radiological protection Vocabulary Part 4: Dosimetry for radiation processing

More information

European Medicines Agency COMMITTEE ON HERBAL MEDICINAL PRODUCTS (HMPC) FINAL

European Medicines Agency COMMITTEE ON HERBAL MEDICINAL PRODUCTS (HMPC) FINAL European Medicines Agency London, 12 November 2009 Doc. Ref. EMEA/HMPC/67644/2009 COMMITTEE ON HERBAL MEDICINAL PRODUCTS (HMPC) FINAL GUIDELINE ON SELECTION OF TEST MATERIALS FOR GENOTOXICITY TESTING FOR

More information

Deviations Inspection Observations & Issues to Consider for Achieving Compliance

Deviations Inspection Observations & Issues to Consider for Achieving Compliance Deviations Inspection Observations & Issues to Consider for Achieving Compliance Kevin O Donnell, Ph.D. Market Compliance Manager Irish Medicines Board IMB GMP & Market Compliance Information Day Dublin,

More information

MONITORING OF OCCUPATIONAL EXPOSURE AT NUCLEAR FACILITIES

MONITORING OF OCCUPATIONAL EXPOSURE AT NUCLEAR FACILITIES GUIDE YVL 7.10 / 29 JANUARY 2002 MONITORING OF OCCUPATIONAL EXPOSURE AT NUCLEAR FACILITIES 1 GENERAL 3 2 PROVISIONS OF THE RADIATION ACT AND DECREE 3 3 MONITORING OF RADIATION EXPOSURE 4 3.1 General requirements

More information

ISO/TR TECHNICAL REPORT. Non-destructive testing Guidelines for NDT personnel training organizations

ISO/TR TECHNICAL REPORT. Non-destructive testing Guidelines for NDT personnel training organizations TECHNICAL REPORT ISO/TR 25108 First edition 2006-07-01 Non-destructive testing Guidelines for NDT personnel training organizations Essais non destructifs Lignes directrices pour les organismes de formation

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO 8454 Third edition 2007-06-01 Cigarettes Determination of carbon monoxide in the vapour phase of cigarette smoke NDIR method Cigarettes Dosage du monoxyde de carbone dans la

More information

Control of Substances Hazardous to Health (COSHH) Regulations 2002

Control of Substances Hazardous to Health (COSHH) Regulations 2002 Control of Substances Hazardous to Health (COSHH) Regulations 2002 1. Purpose This document provides guidance to staff on how to comply with the COSHH Regulations 2002 (as amended) and in particular informs

More information

ISO INTERNATIONAL STANDARD

ISO INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO 16634-1 First edition 2008-11-01 Food products Determination of the total nitrogen content by combustion according to the Dumas principle and calculation of the crude protein

More information

ISO INTERNATIONAL STANDARD. Anaesthetic and respiratory equipment Nebulizing systems and components

ISO INTERNATIONAL STANDARD. Anaesthetic and respiratory equipment Nebulizing systems and components INTERNATIONAL STANDARD ISO 27427 First edition 2009-05-01 Anaesthetic and respiratory equipment Nebulizing systems and components Matériel d'anesthésie et de réanimation respiratoire Systèmes de nébulisation

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO 4074 First edition 2002-02-15 Natural latex rubber condoms Requirements and test methods Préservatifs masculins en latex de caoutchouc naturel Exigences et méthodes d'essai Reference

More information

Approval of Dosimetry Services in Ireland Guidelines for Applicants

Approval of Dosimetry Services in Ireland Guidelines for Applicants Approval of Dosimetry Services in Ireland Guidelines for Applicants Radiological Protection Institute of Ireland April 2012 Contents 1. Introduction 1 2. Information to be submitted with Applications 1

More information

COUNCIL OF THE EUROPEAN UNION. Brussels, 7 September 2009 (OR. en) 11261/09 Interinstitutional File: 2008/0002 (COD) DENLEG 51 CODEC 893

COUNCIL OF THE EUROPEAN UNION. Brussels, 7 September 2009 (OR. en) 11261/09 Interinstitutional File: 2008/0002 (COD) DENLEG 51 CODEC 893 COUNCIL OF THE EUROPEAN UNION Brussels, 7 September 2009 (OR. en) 11261/09 Interinstitutional File: 2008/0002 (COD) DLEG 51 CODEC 893 LEGISLATIVE ACTS AND OTHER INSTRUMTS Subject: Common Position with

More information

IAF Mandatory Document. Requirements for the Migration to ISO 45001:2018 from OHSAS 18001:2007 (IAF MD 21:2018)

IAF Mandatory Document. Requirements for the Migration to ISO 45001:2018 from OHSAS 18001:2007 (IAF MD 21:2018) IAF Mandatory Document Requirements for the Migration to ISO 45001:2018 from OHSAS 18001:2007 Issue 1 (IAF MD 21:2018) Issue 1 Requirements for the Migration to Page 2 of 12 The (IAF) facilitates trade

More information

This document is a preview generated by EVS

This document is a preview generated by EVS INTERNATIONAL STANDARD ISO 1996-1 Third edition 2016-03-01 Acoustics Description, measurement and assessment of environmental noise Part 1: Basic quantities and assessment procedures Acoustique Description,

More information

Atoms for Peace and Development

Atoms for Peace and Development Atoms for Peace and Development Vienna International Centre, PO Box 100, 1400 Vienna, Austria Phone: (+43 1) 2600 Fax: (+43 1) 26007 Email: Official.Mail@iaea.org Internet: http://www.iaea.org In reply

More information

Engaging with our stakeholders

Engaging with our stakeholders Engaging with our stakeholders Report to: Board Date: 27 June 2014 Report by: Report No: Jenny Copland, Senior Communications Adviser Agenda Item: 6.3 PURPOSE OF REPORT To propose a format and processes

More information

FMEA and RCA: the mantras * ; of modern risk management. FMEA and RCA really do work to improve patient safety. COMMENTARY FMEA and RCA.

FMEA and RCA: the mantras * ; of modern risk management. FMEA and RCA really do work to improve patient safety. COMMENTARY FMEA and RCA. pagina 1 van 5 HOME HELP FEEDBACK SUBSCRIPTIONS ARCHIVE SEARCH TABLE OF CONTENTS [Advanced] Qual Saf Health Care 2004;13:249-250 2004 BMJ Publishing Group Ltd & Institute for Healthcare Improvement COMMENTARY

More information

Best Practice Title: Reporting Programmatic And Repetitive Noncompliances in NTS and SSIMS

Best Practice Title: Reporting Programmatic And Repetitive Noncompliances in NTS and SSIMS Best Practice Title: Reporting Programmatic And Repetitive Noncompliances in NTS and SSIMS Facility: The guidance contained in this document is based upon philosophies used at multiple sites across the

More information

Regulatory Submission Strategies and Outlines For Ultrasonic Surgical Devices: Contact and HIFU Systems UIA Symposium Ronald R.

Regulatory Submission Strategies and Outlines For Ultrasonic Surgical Devices: Contact and HIFU Systems UIA Symposium Ronald R. Regulatory Submission Strategies and Outlines For Ultrasonic Surgical Devices: Contact and HIFU Systems 2006 UIA Symposium Ronald R. Manna Regulation Governing Medical Devices Europe: Council Directive

More information

Organisation Internationale de Métrologie Légale

Organisation Internationale de Métrologie Légale Organisation Internationale de Métrologie Légale OIML INTERNATIONAL RECOMMENDATION Equipment for speech audiometry Appareils pour l audiométrie vocale OIML R 122 Edition 1996 (E) CONTENTS Foreword... 3

More information

ISO 8420 INTERNATIONAL STANDARD. Animal and vegetable fats and oils Determination of content of polar compounds

ISO 8420 INTERNATIONAL STANDARD. Animal and vegetable fats and oils Determination of content of polar compounds INTERNATIONAL STANDARD ISO 8420 Second edition 2002-04-01 Animal and vegetable fats and oils Determination of content of polar compounds Corps gras d'origines animale et végétale Détermination de la teneur

More information

A Study of dose Distribution and Radiation Protection in Industrial Radiography in Ireland

A Study of dose Distribution and Radiation Protection in Industrial Radiography in Ireland A Study of dose Distribution and Radiation Protection in Industrial Radiography in Ireland L. Currivan, J. T. Duffy, D. Spain and D. Pollard Radiological Protection Institute of Ireland, 3 Clonskeagh Square,

More information

ISO INTERNATIONAL STANDARD

ISO INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO 11904-1 First edition 2002-10-01 Acoustics Determination of sound immission from sound sources placed close to the ear Part 1: Technique using a microphone in a real ear (MIRE

More information

EUROPEAN COMMISSION HEALTH AND FOOD SAFETY DIRECTORATE-GENERAL. PHARMACEUTICAL COMMITTEE 21 October 2015

EUROPEAN COMMISSION HEALTH AND FOOD SAFETY DIRECTORATE-GENERAL. PHARMACEUTICAL COMMITTEE 21 October 2015 EUROPEAN COMMISSION HEALTH AND FOOD SAFETY DIRECTORATE-GENERAL Health systems and products Medicinal products authorisations, European Medicines Agency PHARM 689 PHARMACEUTICAL COMMITTEE 21 October 2015

More information

Specific Accreditation Guidance OECD GLP

Specific Accreditation Guidance OECD GLP Specific Accreditation Guidance OECD GLP Information for GLP Study Sponsors January 2018 Copyright National Association of Testing Authorities, Australia 2013 This publication is protected by copyright

More information

Re: ENSC 440 Project Functional Specification for a Non-invasive Glucose Measuring Device

Re: ENSC 440 Project Functional Specification for a Non-invasive Glucose Measuring Device Lumen Medical Technologies Inc. 1154 Harold Rd. North Vancouver, B.C. V7K 1G3 February 20, 2006 Dr. Andrew Rawicz Simon Fraser University 8888 University Drive Burnaby, BC V5A 1S6 Re: ENSC 440 Project

More information

Accreditation Criteria

Accreditation Criteria Accreditation Criteria Occupational Health and Safety Management Systems Certification BCB 130 September 2009 Contents 0.0 Foreword 2 1.0 Scope 2 2.0 Criteria 2 3.0 Guidance on the requirements of OHSAS

More information

Methods of validation of occupational noise exposure measurement with multi aspect personal sound exposure meter

Methods of validation of occupational noise exposure measurement with multi aspect personal sound exposure meter Proceedings of ACOUSTICS 2016 Methods of validation of occupational noise exposure measurement with multi aspect personal sound exposure meter Marek Podgórski Svantek Sp. z o.o., Warsaw, Poland ABSTRACT

More information

SLEEP IMPROVING WRISTBAND. Item No Owner s Guide

SLEEP IMPROVING WRISTBAND. Item No Owner s Guide SLEEP IMPROVING WRISTBAND Item No. 205350 Owner s Guide Thank you for purchasing the Sharper Image Sleep Improving Wristband. Based on ancient Chinese acupuncture principles, this biofeedback device uses

More information

Market Survey. Technical Description Irradiation Tests

Market Survey. Technical Description Irradiation Tests EDMS No. 1959184 The R2E Project Group Code: EN-STI Market Survey Technical Description Irradiation Tests Abstract This Technical Description concerns the performance of irradiation testing of CERN samples.

More information

Justice Committee. Alternative Dispute Resolution. Written submission from Scottish Mediation

Justice Committee. Alternative Dispute Resolution. Written submission from Scottish Mediation Justice Committee Alternative Dispute Resolution Written submission from Scottish Mediation The Availability of Mediation in Scotland 1. Introduction Scottish Mediation are delighted to be invited to the

More information

AUG Expert responses to issues raised by British Gas during the query period for the first draft 2017/18 AUG Statement, 14 March 2017.

AUG Expert responses to issues raised by British Gas during the query period for the first draft 2017/18 AUG Statement, 14 March 2017. AUG Expert responses to issues raised by British Gas during the query period for the first draft 2017/18 AUG Statement, 14 March 2017. Below are the issues raised by British Gas. Following each issue is

More information

US30B14. Provide facial electrical treatments

US30B14. Provide facial electrical treatments US30B14 Provide facial electrical treatments This unit is about improving face and skin condition using direct high frequency, galvanic, EMS, micro-current, lymphatic drainage and micro-dermabrasion equipment.

More information

REPORT OF THE TECHNICAL MEETING: THE NEW DOSE LIMIT FOR THE LENS OF THE EYE IMPLICATIONS AND IMPLEMENTATION VIENNA, 2-4 OCTOBER 2012

REPORT OF THE TECHNICAL MEETING: THE NEW DOSE LIMIT FOR THE LENS OF THE EYE IMPLICATIONS AND IMPLEMENTATION VIENNA, 2-4 OCTOBER 2012 REPORT OF THE TECHNICAL MEETING: THE NEW DOSE LIMIT FOR THE LENS OF THE EYE IMPLICATIONS AND IMPLEMENTATION VIENNA, 2-4 OCTOBER 2012 Introduction A Technical Meeting on the The new dose limit for the lens

More information

Provide female intimate waxing services

Provide female intimate waxing services Provide female intimate waxing services Y/600/8764 Learner name: Learner number: VTCT is the specialist awarding body for the Hairdressing, Beauty Therapy, Complementary Therapy and Sport and Active Leisure

More information

Report of the Thoracic Medicine Clinical Committee. Submission from the Thoracic Society of Australia and New Zealand (TSANZ) EXECUTIVE SUMMARY

Report of the Thoracic Medicine Clinical Committee. Submission from the Thoracic Society of Australia and New Zealand (TSANZ) EXECUTIVE SUMMARY Report of the Thoracic Medicine Clinical Committee Submission from the Thoracic Society of Australia and New Zealand (TSANZ) EXECUTIVE SUMMARY Submission Date: 7 th October 2016 Table of Contents Report

More information

SECTION III GUIDELINES FOR SUBSIDIARY BODIES. SECTION III: Guidelines for Subsidiary Bodies

SECTION III GUIDELINES FOR SUBSIDIARY BODIES. SECTION III: Guidelines for Subsidiary Bodies SECTION III: Guidelines for Subsidiary Bodies SECTION III GUIDELINES FOR SUBSIDIARY BODIES Guidelines to Host Governments of Codex Committees and ad hoc Intergovernmental Task Forces. (Adopted in 2004)

More information

-SQA-SCOTTISH QUALIFICATIONS AUTHORITY. Hanover House 24 Douglas Street GLASGOW G2 7NG NATIONAL CERTIFICATE MODULE DESCRIPTOR

-SQA-SCOTTISH QUALIFICATIONS AUTHORITY. Hanover House 24 Douglas Street GLASGOW G2 7NG NATIONAL CERTIFICATE MODULE DESCRIPTOR -SQA-SCOTTISH QUALIFICATIONS AUTHORITY Hanover House 24 Douglas Street GLASGOW G2 7NG NATIONAL CERTIFICATE MODULE DESCRIPTOR -Module Number- 0069166 -Session-1986-87 -Superclass- PF -Title- DENTAL RADIOGRAPHY

More information

Interstate Interfacility Transport of a Patient with

Interstate Interfacility Transport of a Patient with Interstate Interfacility Transport of a Patient with Tabletop Exercise The gives elected and appointed officials, observers, media personnel, and players from participating organizations information they

More information

Cambridge International AS & A Level Global Perspectives and Research. Component 4

Cambridge International AS & A Level Global Perspectives and Research. Component 4 Cambridge International AS & A Level Global Perspectives and Research 9239 Component 4 In order to help us develop the highest quality Curriculum Support resources, we are undertaking a continuous programme

More information

ISO INTERNATIONAL STANDARD

ISO INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO 8529-3 First edition 1998-11-15 Reference neutron radiations Part 3: Calibration of area and personal dosimeters and determination of their response as a function of neutron

More information

This document is a preview generated by EVS

This document is a preview generated by EVS INTERNATIONAL STANDARD ISO 17510 First edition 2015-08-01 Medical devices Sleep apnoea breathing therapy Masks and application accessories Dispositifs médicaux Thérapie respiratoire de l apnée du sommeil

More information

workplace includes, any land, premises, location, vessel or thing, at, in, upon, or near which, a worker is, in the course of employment.

workplace includes, any land, premises, location, vessel or thing, at, in, upon, or near which, a worker is, in the course of employment. L.N. 25/2005 THE FACTORIES AND OTHER PLACES OF WORK (NOISE PREVENTION AND CONTROL) RULES 2005 Citation 1 These rules shall be cited as Factories and Other Places of Work (Noise Prevention and Control)

More information

ISO IDF 177 INTERNATIONAL STANDARD. Dried skimmed milk Determination of vitamin D content using high-performance liquid chromatography

ISO IDF 177 INTERNATIONAL STANDARD. Dried skimmed milk Determination of vitamin D content using high-performance liquid chromatography INTERNATIONAL STANDARD ISO 14892 IDF 177 First edition 2002-02-01 Dried skimmed milk Determination of vitamin D content using high-performance liquid chromatography Lait écrémé sec Détermination de la

More information

Policy for Connecting Customer-Provided Equipment to SaskTel s Network

Policy for Connecting Customer-Provided Equipment to SaskTel s Network NON-TARIED PRODUTS AND SERVIES Page 396 Policy for onnecting ustomer-provided Equipment to SaskTel s Network Purpose This document is designed to direct customers to sources of comprehensive information

More information

CIEH Professional Examinations Health & Safety 2 November 2006 CASE FILE

CIEH Professional Examinations Health & Safety 2 November 2006 CASE FILE CASE FILE You are an environmental health practitioner employed by Chadwick Valley MBC in the occupational health and safety division. You have been asked by your Manager to act as an occupational noise

More information

Fundamentals of Pulse Oximetry

Fundamentals of Pulse Oximetry Donald Gessling presents: Fundamentals of Pulse Oximetry Sponsored by: Fluke Biomedical Wednesday, September 14, 2016, 2:00pm ET PRESENTER: DONALD GESSLING, FLUKE BIOMEDICAL Donald Gessling, Senior Engineer

More information

ISO INTERNATIONAL STANDARD. Implants for surgery Active implantable medical devices Part 2: Cardiac pacemakers

ISO INTERNATIONAL STANDARD. Implants for surgery Active implantable medical devices Part 2: Cardiac pacemakers INTERNATIONAL STANDARD ISO 14708-2 Second edition 2012-08-15 Implants for surgery Active implantable medical devices Part 2: Cardiac pacemakers Implants chirurgicaux Dispositifs médicaux implantables actifs

More information

FACTORIES ACT (CHAPTER 104, SECTION 102 (1)) FACTORIES (NOISE) REGULATIONS

FACTORIES ACT (CHAPTER 104, SECTION 102 (1)) FACTORIES (NOISE) REGULATIONS FACTORIES ACT (CHAPTER 104, SECTION 102 (1)) FACTORIES (NOISE) REGULATIONS [1st January 1997] Arrangement of Provisions PART I PRELIMINARY 1 Citation 2 Definitions 3 Application PART II NOISE CONTROL 4

More information

This document is a preview generated by EVS

This document is a preview generated by EVS INTERNATIONAL STANDARD ISO 10555-5 Second edition 2013-06-15 Intravascular catheters Sterile and single-use catheters Part 5: Over-needle peripheral catheters Cathéters intravasculaires Cathéters stériles

More information

ISO 7885 INTERNATIONAL STANDARD. Dentistry Sterile injection needles for single use

ISO 7885 INTERNATIONAL STANDARD. Dentistry Sterile injection needles for single use Provläsningsexemplar / Preview INTERNATIONAL STANDARD ISO 7885 Third edition 2010-02-15 Dentistry Sterile injection needles for single use Médecine bucco-dentaire Aiguilles stériles pour injection, non

More information

Carry out massage using pre-blended aromatherapy oils

Carry out massage using pre-blended aromatherapy oils Carry out massage using pre-blended aromatherapy oils K/600/7523 Learner name: Learner number: VTCT is the specialist awarding body for the Hairdressing, Beauty Therapy, Complementary Therapy and Sport

More information

Environmental, Health and Safety

Environmental, Health and Safety Environmental, Health and Safety Codes of Practice The Environmental, Health and Safety (EHS) Codes of Practice set forth Zimmer EHS requirements for our business functions and facilities worldwide. In

More information

codex alimentarius commission

codex alimentarius commission codex alimentarius commission FOOD AND AGRICULTURE WORLD HEALTH ORGANIZATION ORGANIZATION OF THE UNITED NATIONS JOINT OFFICE: Via delle Terme di Caracalla 00100 Rome Tel.: 39.06.57051 Telex: 625825-625853

More information

WORLD TRADE ORGANIZATION

WORLD TRADE ORGANIZATION WORLD TRADE ORGANIZATION WT/DS321/R/Add.5 31 March 2008 (08-0912) Original: English CANADA CONTINUED SUSPENSION OF OBLIGATIONS IN THE EC HORMONES DISPUTE Report of the Panel Addendum This addendum contains

More information

UNIT TITLE: MANAGE RESPONSIBLE SERVICE OF ALCOHOL

UNIT TITLE: MANAGE RESPONSIBLE SERVICE OF ALCOHOL UNIT TITLE: MANAGE RESPONSIBLE SERVICE OF ALCOHOL NOMINAL HOURS: UNIT NUMBER: UNIT DESCRIPTOR: This unit deals with the skills and knowledge required to manage responsible service of alcohol in a range

More information

Consumers Association s response to the European Commission s Discussion paper on nutrition claims and functional claims

Consumers Association s response to the European Commission s Discussion paper on nutrition claims and functional claims Introduction Consumers Association s response to the European Commission s Discussion paper on nutrition claims and functional claims Consumers Association (CA), publisher of Which?, Health Which? and

More information

Draft Falls Prevention Strategy

Draft Falls Prevention Strategy Cheshire West & Chester Council Draft Falls Prevention Strategy 2017-2020 Visit: cheshirewestandchester.gov.uk Visit: cheshirewestandchester.gov.uk 02 Cheshire West and Chester Council Draft Falls Prevention

More information

ENROLMENT FORM. Title: First Name: Surname: Postal Address: Postcode: Emergency Contact: Relationship: Phone: What is your main fitness goal?

ENROLMENT FORM. Title: First Name: Surname: Postal Address: Postcode:   Emergency Contact: Relationship: Phone: What is your main fitness goal? ENROLMENT FORM Personal Information Title: First Name: Surname: Date of Birth: Sex: Female Male Postal Address: Postcode: Phone: Home: Work: Mobile: Email: Preferred method of contact: Letter Phone Email

More information

Common mistakes Cleanroom HVAC Design & Execution. Gordon Farquharson, July 2017

Common mistakes Cleanroom HVAC Design & Execution. Gordon Farquharson, July 2017 Common mistakes Cleanroom HVAC Design & Execution Gordon Farquharson, July 2017 Slide 1 PharmOut 2017 Agenda Sources - Experiences Documentation integrity Room pressure balancing & control HEPA filter

More information

Cerus P-Series General Specifications Section 15172

Cerus P-Series General Specifications Section 15172 Cerus P-Series s Section 15172 Variable Frequency Drives PART 1-GENERAL 1.01 SECTION INCLUDES A. Variable Frequency Drive(VFD) 1.02 RELATED SECTIONS A. Section 16195 1.03 REFERENCES A. NEMA250 B. EN 50178

More information

ASCO Power Control Systems Overview

ASCO Power Control Systems Overview ASCO Power Control Systems Overview POWER CONTROL CHALLENGES Today more than ever, continuous electrical power is essential for providing mission-critical services. Whether it s a hospital providing critical

More information

A New Participant s Guide to CVA Qualification

A New Participant s Guide to CVA Qualification Guidance A New Participant s Guide to CVA Qualification 1 Introduction 1.1 Overview This Guide to Central Volume Allocation (CVA) Qualification has been produced to assist new entrants with understanding

More information