Indoor Air Quality Testing. Horry County Schools

Size: px
Start display at page:

Download "Indoor Air Quality Testing. Horry County Schools"

Transcription

1 ! Report of: Indoor Air Quality Testing Horry y Schools Conway, SC Palme5o EHS Report No: Submi5ed Prepared for: Horry y Schools Prepared By: Palme5o EHS, LLC 100 Old Cherokee Rd. Suite F, Box 163 Lexington, SC (Phone) (Fax)

2 ! Horry y Schools 335 Four Mile Rd. Conway, SC 29528! Safety Industrial Hygiene OSHA Compliance Training Attention: Ms. Tammy Trulove Reference: REPORT OF INDOOR AIR QUALITY TESTING Palmetto EHS Report No Dear Ms. Trulove: Palmetto EHS, LLC (Palmetto EHS) is pleased to provide the enclosed report for the referenced site. The sampling was conducted on November 30, The report includes an executive summary, investigative methods, results and conclusions. This work was performed in general conformance with Palmetto EHS Proposal Number dated November 6, This report is provided for the sole use of Horry y Schools. Use of this report by any other parties will be at such party's sole risk and Palmetto EHS disclaims liability for any such use or reliance by third parties. The results presented in this report are indicative of conditions only during the time of the sampling period and of the specific areas referenced. We appreciate the opportunity to work with you. If you have any questions concerning this report, please call us at (803) Sincerely, Palmetto EHS, LLC! Rachel Schlachter, MPH, CSP Colleen Eubanks, CIH, CSP, CET EHS Specialist President! Palmetto EHS, LLC 100 Old Cherokee Rd. Ste. F #163 Lexington, SC (Phone) (Fax)

3 Table of Contents Executive Summary... 4 Scope of Work... 4 Materials and Methods... 5 Environmental Parameters... 5 Mold Samples... 5 Results and Discussion... 6 Visual Assessment... 6 Environmental Parameters... 6 Mold Samples... 7 Conclusions and Recommendations... 9 Appendix I Palmetto EHS, LLC! 3

4 Executive Summary Palmetto EHS conducted indoor air quality testing in the Reading Room, Conference Room, Room E-100, Room E-101, Room E-103, and Room E-104 at St. James Elementary School in Myrtle Beach, SC on November 30, The testing was conducted indoors and outdoors for comparison. We identified the following conditions during our visit: We did not observe visible mold or detect any musty or unusual odors in the Reading Room, Conference Room, Room E-100, Room E-101, Room E-103, or Room E-104 on the day of our visit. The results of the environmental parameter testing revealed that carbon dioxide, temperature, and relative humidity were within normal limits in all of the rooms visited at the time of our testing, however carbon dioxide was on the higher end of normal in the Conference Room. We observed staining on the HVAC return vent, supply diffusers, and the metal around the ceiling tiles surrounding the HVAC supply diffusers in Room E-100. A small amount of dust build up was observed on the HVAC supply diffuser and return vent in Room E-103. Mold spores were not amplified in Room E-103 on November 30, Curvularia mold spores were amplified in the Reading Room and Conference Room, Aspergillus/Penicillium-like mold spores were amplified in Room E-100 and Room E-104, and Pithomyces mold spores were amplified in Room E-101 on the day of our visit. Recommendations are provided in the Conclusions and Recommendations section of this report. Scope of Work Palmetto EHS conducted indoor air quality testing in the Reading Room, Conference Room, Room E-100, Room E-101, Room E-103, and Room E-104 at St. James Elementary School in Myrtle Beach, SC on November 30, The purpose of the sampling was to determine if airborne mold spores were elevated above outdoor levels. We conducted a walk-through visual assessment, environmental parameter testing, and air sampling for mold spores during our visit. Palmetto EHS, LLC! 4

5 Materials and Methods Environmental Parameters Carbon dioxide (CO2), temperature and relative humidity were measured using a TSI IAQ Calc direct reading instrument to determine the relative comfort parameters of the subject area and to evaluate conditions that may promote amplification of microorganisms. The American Society for Heating, Refrigeration, and Air-Conditioning Engineers (ASHRAE) has established guidelines for selected indoor air quality parameters such as temperature, relative humidity (RH) and carbon dioxide (CO2). These environmental parameters are important determinants for occupant s perceptions of thermal comfort, and ASHRAE Standard recommends ranges for temperature and RH that most occupants (>80%) will find comfortable. Acceptable temperature ranges differ from winter to summer and are a function of RH levels that range between 30% and 60%. RH below 30% is unacceptable because of the effect of dry air on the eyes, skin and mucous membranes, and RH above 60% may support the growth of pathogenic or allergenic microorganisms indoors. The following temperature ranges are considered acceptable based on the standard: Summer: 74ºF to 80ºF (for RH = 30%) and 73ºF to ºF (for RH = 60%). Winter: 69ºF to 76ºF (for RH = 30%) and 68ºF to 74ºF (for RH = 60%) The indoor concentration of CO2 is a surrogate for occupant-generated pollutants that may be odorous, and is an indicator of the adequacy of the rate of outside air supply per occupant (dilution ventilation). The higher the indoor concentrations of CO2, the less effective the ventilation system is in dilution of typical indoor air contaminants and body effluents. ASHRAE standard recommends an indoor to outdoor differential concentration of CO2 to be no greater than 700 parts per million (ppm) to meet comfort (odor) criteria. Mold Samples (viable and non-viable) airborne fungal (mold) spores were measured indoors and outdoors using Zefon Air-O-Cell spore traps with a calibrated vacuum pump. Air sampling was performed indoors and outdoors for comparison. The samples were immediately shipped for overnight delivery and analyzed by light microscopy for viable and non-viable mold spores by Scientific Analytical Institute, which is accredited by the American Industrial Hygiene Association (AIHA). Microbial testing as a part of this report included testing and analysis for some biological agents commonly present in indoor air. It did not include testing and analysis for all known biological agents. Testing for biological contaminants does not include viruses or bacteria, unless specifically noted otherwise, and then only those viruses and bacteria specified. Palmetto EHS, LLC! 5

6 Results and Discussion Visual Assessment We were asked to collect air samples for mold in the Reading Room, Conference Room, Room E-100, Room E-101, Room E-103, and Room E-104 at St. James Elementary School in Myrtle Beach, SC on November 30, Ms. Tammy Trulove, Director of Health and Safety Services for Horry y Schools, advised that there had been complaints from faculty/staff that they were having respiratory symptoms, headaches, and watering eyes when working in the Reading Room and Conference Room. In these areas, the ceiling tiles had been removed and replaced, the walls had been painted, the carpet was removed and replaced with tile, a charcoal filter was put into the HVAC system, and a UV light was installed in the ductwork. At the time of our visit, we did not observe any visible mold or detect any musty or unusual odors in the Reading Room, Conference Room, Room E-100, Room E-101, Room E-103, or Room E-104. We observed staining on the HVAC return vent, supply diffusers, and the metal around the ceiling tiles surrounding the HVAC supply diffusers in Room E-100. We also observed a small amount of dust build up on the HVAC supply diffuser and return vent in Room E-103. Environmental Parameters A summary of the environmental parameters tested (temperature, relative humidity, and carbon dioxide) are provided in Table I. The results of the environmental parameter testing revealed that carbon dioxide, temperature, and relative humidity were within normal limits in each of the areas we visited on November 30, 2018, however carbon dioxide was on the higher end of normal in the Conference Room. Table I: Environmental Parameter Results November 30, 2018 Location Carbon Dioxide (ppm) Relative Humidity (Percent) Temperature (Degrees F) Outdoors Criteria < % to 60% degrees F Reading Room Conference Room Room E Room E Room E Room E Palmetto EHS, LLC! 6

7 Mold Samples We are unaware of regulatory requirements pertaining to mold associated with indoor air quality at this time. However, there are recognized guidelines for mold remediation from the Environmental Protection Agency (EPA), and New York City Department of Health Bureau of Environmental & Occupational Disease Epidemiology. Additionally, indoor air quality guidelines have been suggested for remedial decision-making by the Occupational Safety and Health Administration (OSHA), and the American Conference of Government Industrial Hygienist (ACGIH). Some of these guidelines focus on indoor to outdoor comparison, and an evaluation of fungal types. The interpretation of the results normally relies upon the professional conducting the assessment. Airborne microorganisms are ubiquitous; the presence of microorganisms is of undue concern unless they are of a significant concentration or the predominant types found indoors differ from those found outdoors. When indoor levels are significantly elevated in relation to outdoor concentrations, they are considered to be amplified. Therefore, indoor environmental conditions are such that their growth is facilitated. In general, amplification of microorganisms is present when the fungi or bacteria concentration in the air substantially exceeds the outdoor air. Exposure to excessive amounts of some common microorganisms can result in allergic or respiratory irritation in some susceptible individuals. Air sampling was performed indoors and outdoors for comparison. fungal spore (nonviable and viable fungi) concentrations were monitored. Summary results of the air samples are provided in Table II and actual laboratory results are provided in the Appendix. Palmetto EHS, LLC! 7

8 Table II: Mold Air Sampling Results November 30, 2018 Sample Number Location Mold (c/m 3 ) Predominant Types E-M-1 Outdoors 4470 E-M-2 Outdoors 4150 E-M-3 Reading Room 235 Ascospores (2590) Basidiospores (1020) Cladosporium (862) Ascospores (1410) Basidiospores (1880) Cladosporium (705) Cladosporium (157) Curvularia () E-M-4 Conference Room Curvularia () E-M-5 Room E Aspergillus/Penicillium (549) E-M-6 Room E E-M-7 Room E E-M-8 Room E Ascospores () Pithomyces () Ascospores (235) Basidiospores (157) Ascospores () Aspergillus/Penicillium (1250) Cladosporium () Amplification: Indoor levels substantially exceed outdoor levels. Abbreviations: c/m 3 = total mold spore counts per cubic meter, ND= None Detected The total mold spore count in Room E-103 was well below outdoor levels, and mold types detected were similar to those found outdoors.therefore, mold spores were not considered amplified in Room E-103 on the day of our visit. The total mold spore counts in the Reading Room, Conference Room, Room E-100, Room E-101, and Room E-104 were well below outdoor levels, however, Curvularia mold spores were detected in the Reading Room and Conference Room, Aspergillus/Penicillium-like mold spores were detected in Room E-100 and Room E-104, and Pithomyces mold spores were detected in Room E-101, and none of these mold types were detected in the outdoor samples. Therefore, mold spores were considered amplified in the Reading Room, Conference Room, Room E-100, Room E-101, and Room E-104 on the day of our visit. Palmetto EHS, LLC! 8

9 Conclusions and Recommendations The results of the visual assessment and testing indicate the following: We did not observe visible mold or detect any musty or unusual odors in the Reading Room, Conference Room, Room E-100, Room E-101, Room E-103, or Room E-104 on the day of our visit. The results of the environmental parameter testing revealed that carbon dioxide, temperature, and relative humidity were within normal limits in all of the rooms visited at the time of our testing, however carbon dioxide was on the higher end of normal in the Conference Room. We observed staining on the HVAC return vent, supply diffusers, and the metal around the ceiling tiles surrounding the HVAC supply diffusers in Room E-100. A small amount of dust build up was observed on the HVAC supply diffuser and return vent in Room E-103. Mold spores were not amplified in Room E-103 on November 30, Curvularia mold spores were amplified in the Reading Room and Conference Room, Aspergillus/Penicillium-like mold spores were amplified in Room E-100 and Room E-104, and Pithomyces mold spores were amplified in Room E-101 on the day of our visit. The following recommendations are provided for Room E-103: 1. Clean the HVAC supply diffuser and return vent with a District approved antimicrobial cleaning agent. The following recommendations are provided for the Reading Room, Conference Room, Room E-100, Room E-104, and Room E-101: 1. Thoroughly clean and dry all of the surfaces (walls, floors, furniture, doors, book shelves, desks, chairs, etc) in these rooms with a District approved antimicrobial cleaning agent. This should include a cleaning of any HVAC supply diffusers and return vents, as well as a thorough cleaning and drying of the rugs and any porous items in the rooms (such as upholstered chairs, curtains, pillows, cushions, etc.). This may be performed by the regular cleaning staff as long as appropriate antimicrobial cleaning agents are used for the cleaning, otherwise, you may consider using a mold remediation contractor. 2. Once the cleaning has been completed, replace the HVAC filters. 3. You may consider running one HEPA filtered air scrubber in each room for 3-5 days, however it is not required. 4. Follow up air testing can be performed if requested. 5. We also recommend making adjustments to the HVAC serving the Conference Room to allow more fresh air into the area in order to reduce the carbon dioxide levels. Palmetto EHS, LLC! 9

10 Appendix I Analytical Results Palmetto EHS, LLC! 10

11 Direct Exam: Spore Trap Analysis SAI Method B-SOP-003 Client: Project: Palmetto EHS 100 Old Cherokee Rd Lexington, SC St. James Elem School IAQ Attn: Colleen Eubanks Lab Order ID: Analysis ID: Date Received: Date Reported: _STA 12/03/ /03/2018 Sample ID Lab Sample ID Description Lab Notes Volume(L) Analytical Sensitivity E-M _STA_001 Outdoors E-M _STA_002 Outdoors E-M _STA_003 Reading Room EXTERIOR AVERAGE IDENTIFICATION Ascospores Aspergillus/ Penicillium-like Basidiospores Cladosporium Curvularia Myxomycete/ Rust/ Smut-like Pithomyces % % % % % % % % % % % % % TOTAL Non-Cellulosic Fibers Hyphal Fragments Insect Parts Pollen Skin Cell % of Debris Debris in Background % 0-20% 0-20% % 0-20% 0-20% % % 60-80% % Disclaimer: This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. Unless otherwise noted blank sample correction was not performed on analytical results. Scientific Analytical Institute participates in the AIHA EMPAT program for fungi. EMPAT Laboratory ID: Reporting Limit equals Analytical Sensitivity. Palmer Hines (8) B-F-028 r15 1/16/2021 Analyst Scientific Analytical Institute, Inc Dundas Dr. Greensboro, NC (336) Approved Signatory Page 1 of 3

12 Direct Exam: Spore Trap Analysis SAI Method B-SOP-003 Client: Project: Palmetto EHS 100 Old Cherokee Rd Lexington, SC St. James Elem School IAQ Attn: Colleen Eubanks Lab Order ID: Analysis ID: Date Received: Date Reported: _STA 12/03/ /03/2018 Sample ID Lab Sample ID Description Lab Notes Volume(L) Analytical Sensitivity E-M _STA_004 Conference Room E-M _STA_005 Room E-100 E-M _STA_006 Room E-101 EXTERIOR AVERAGE IDENTIFICATION Ascospores Aspergillus/ Penicillium-like Basidiospores Cladosporium Curvularia Myxomycete/ Rust/ Smut-like Pithomyces % % % % % % % % TOTAL Non-Cellulosic Fibers Hyphal Fragments Insect Parts Pollen Skin Cell % of Debris Debris in Background % % 40-60% % % 20-40% % % 40-60% % Disclaimer: This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. Unless otherwise noted blank sample correction was not performed on analytical results. Scientific Analytical Institute participates in the AIHA EMPAT program for fungi. EMPAT Laboratory ID: Reporting Limit equals Analytical Sensitivity. Palmer Hines (8) B-F-028 r15 1/16/2021 Analyst Scientific Analytical Institute, Inc Dundas Dr. Greensboro, NC (336) Approved Signatory Page 2 of 3

13 Direct Exam: Spore Trap Analysis SAI Method B-SOP-003 Client: Project: Palmetto EHS 100 Old Cherokee Rd Lexington, SC St. James Elem School IAQ Attn: Colleen Eubanks Lab Order ID: Analysis ID: Date Received: Date Reported: _STA 12/03/ /03/2018 Sample ID Lab Sample ID Description Lab Notes Volume(L) Analytical Sensitivity E-M _STA_007 Room E-103 E-M _STA_008 Room E-104 EXTERIOR AVERAGE IDENTIFICATION Ascospores Aspergillus/ Penicillium-like Basidiospores Cladosporium Curvularia Myxomycete/ Rust/ Smut-like Pithomyces % % % % % % % % % TOTAL Non-Cellulosic Fibers Hyphal Fragments Insect Parts Pollen Skin Cell % of Debris Debris in Background % 60-80% 40-60% % % 40-60% % Disclaimer: This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. Unless otherwise noted blank sample correction was not performed on analytical results. Scientific Analytical Institute participates in the AIHA EMPAT program for fungi. EMPAT Laboratory ID: Reporting Limit equals Analytical Sensitivity. Palmer Hines (8) B-F-028 r15 1/16/2021 Analyst Scientific Analytical Institute, Inc Dundas Dr. Greensboro, NC (336) Approved Signatory Page 3 of 3

No visible mold or water intrusion/damage was found on the day of testing.

No visible mold or water intrusion/damage was found on the day of testing. January th, 0 Mr. Marty Foutch Facilities Director Bixby Public Schools 9 N. Armstrong Bixby, OK 008 CC: RE: Jarred Doubrava Operations Support Manager/District Safety Coordinator Bixby Northeast Elementary

More information

IAQ & MOLD AIR SAMPLING REPORT

IAQ & MOLD AIR SAMPLING REPORT IAQ & MOLD AIR SAMPLING REPORT LINCOLNSHIRE-PRAIRIE VIEW SCHOOL DISTRICT #103 Project Location: HALF DAY SCHOOL 239 Olde Half Day Road Testing Dates: January 10 17, 2018 MEC PROJECT #: 17-12-968-I.H. EXECUTIVE

More information

DATE: September 15, TO: Sarah Johnston, Director

DATE: September 15, TO: Sarah Johnston, Director DATE: September 15, 2015 TO: Sarah Johnston, Director SUBJECT: Purnell Service Center - IAQ - Air Test - Room 105, 4 Director's offices & Secretary office area. On Saturday 9/12, I received an E-mail from

More information

DATE: May 23, TO: Tommy Ellington, Executive Director

DATE: May 23, TO: Tommy Ellington, Executive Director DATE: May 23, 2016 TO: Tommy Ellington, Executive Director SUBJECT: SSAB- IAQ - Initial Contact - Sherah Robinson's office, Cinnamon Dilts' office and Storeroom SE corner On Wednesday 5/18, I received

More information

Analysis Report prepared for Quest Air

Analysis Report prepared for Quest Air contact@hayesmicrobial.com http://hayesmicrobial.com/ Analysis Report prepared for 103 Carnegie Center Suite 300 Princeton, NJ. 08540 Job Name: 76 Federal City Road Date Sampled: 05-30-2017 Date Analyzed:

More information

M. A. CECIL & ASSOCIATES, INC Shannon Way, Port Republic, Maryland (301) INDUSTRIAL HYGIENE AND ENVIRONMENTAL HEALTH

M. A. CECIL & ASSOCIATES, INC Shannon Way, Port Republic, Maryland (301) INDUSTRIAL HYGIENE AND ENVIRONMENTAL HEALTH M. A. CECIL & ASSOCIATES, INC. 4475 Shannon Way, Port Republic, Maryland 20676 (301) 855-7710 INDUSTRIAL HYGIENE AND ENVIRONMENTAL HEALTH October 17, 2013 Mr. Sean Yarup Montgomery County Public Schools

More information

Mastertech North Jersey

Mastertech North Jersey contact@hayesmicrobial.com http://hayesmicrobial.com/ Analysis Report prepared for Mastertech North Jersey Mount Arlington, NJ. 07856 Phone: (973) 346-650 I 18 MT1 Job Name: Indiana 18 Date Sampled: 03-09-018

More information

SUBJECT: Administration Building - IAQ - Initial Contact report - Room 217, Hallway outside Room 217, Room 201, Room 225, Room 212

SUBJECT: Administration Building - IAQ - Initial Contact report - Room 217, Hallway outside Room 217, Room 201, Room 225, Room 212 DATE: February 15, 2016 TO: Sandi Maddox, Director SUBJECT: Administration Building - IAQ - Initial Contact report - Room 217, Hallway outside Room 217, Room 201, Room 225, Room 212 I received Work Order

More information

A Healthy Home, LLC West Center Dr. Lakewood, CO

A Healthy Home, LLC West Center Dr. Lakewood, CO Mold Inspection and Testing Summary A Healthy Home, LLC 13520 West Center Dr. Lakewood, CO. 80228 303-989-6809 Robert Boyd, is certified by the American Council of Accredited Certification (ACAC), as a

More information

FUNGAL PARTICULATE AIR SAMPLING

FUNGAL PARTICULATE AIR SAMPLING November 19, 2016 Chuck Doan Yakima School District #7 104 N 4th Avenue Yakima, WA 98902 Via email: Regarding: doan.chuck@yakimaschools.org Fungal Sample Results Blue Wall Room 509 and Room 617 Eisenhower

More information

RE: Total Airborne Mould Spore Sampling Brookside Junior High 2239 Prospect Road, Hatchet Lake, NS

RE: Total Airborne Mould Spore Sampling Brookside Junior High 2239 Prospect Road, Hatchet Lake, NS 20 Duke Street, Suite 109 Tel: (902) 835-3727 Bedford, Nova Scotia Fax: (902) 835-5266 B4A 2Z5 Email: email@toalltech.com September 9 th, 2015 Tom Drury Assistant Regional Manager Operations Services Halifax

More information

DATE: February 14, TO: Amy Acosta, Principal

DATE: February 14, TO: Amy Acosta, Principal DATE: February 14, 2017 TO: Amy Acosta, Principal SUBJECT: Timber Creek ES - IAQ - Initial Contact - Media Room, Hallway between Principal Office & Library and Library On Friday 2/10, I received W.O. #403088:

More information

MOLD INSPECTION REPORT

MOLD INSPECTION REPORT MOLD INSPECTION REPORT Conducted at: 407 Canyon East Conducted for: Town of Taos Prepared By: Gary O leary Klean Force Project Number: #21054 Inspection Date: 02/04/2015 Report Date: 02/13/2015 915-474-0299

More information

DATE: September 12, TO: Curtis Martin, Principal. SUBJECT: Tom Hicks ES - IAQ - Air Test Results - Nurses' Office, Main Admin Office

DATE: September 12, TO: Curtis Martin, Principal. SUBJECT: Tom Hicks ES - IAQ - Air Test Results - Nurses' Office, Main Admin Office DATE: September 12, 2017 TO: Curtis Martin, Principal SUBJECT: Tom Hicks ES - IAQ - Air Test Results - Nurses' Office, Main Admin Office On Tuesday 9/5, Apex-Titan Air tested the Nurses Office and the

More information

EXPANDED FUNGAL REPORT

EXPANDED FUNGAL REPORT EXPANDED FUNGAL REPORT Prepared Exclusively For Report Date: 11/29/2007 Project: Accceditation"This report was generated in the EMSL Test Lab Page 1 of 23 1. Description of Analysis Analytical Laboratory

More information

Indiana University Environmental Health & Safety Beau Middaugh 2427 E. 2nd street Bloomington, IN USA (812)

Indiana University Environmental Health & Safety Beau Middaugh 2427 E. 2nd street Bloomington, IN USA (812) Indiana University Environmental Health & Safety Beau Middaugh 2427 E. 2nd street Bloomington, IN 47401 USA (812) 855-6316 Approved by: Dates of Analysis: MoldReport Spore trap: 12-19-2018 Technical Manager

More information

Air Sampling and Analysis for Mold in Hills Building UMass

Air Sampling and Analysis for Mold in Hills Building UMass Air Sampling and Analysis for Mold in Hills Building UMass Christine Rogers, PhD Environmental Health Science SPHHS First Floor Hills North Introduction Upon request, all of the rooms on the first floor

More information

Tape Lift and Swab Sampling of Items found at Glenwood Middle School Project #J15-876

Tape Lift and Swab Sampling of Items found at Glenwood Middle School Project #J15-876 October 21, 2015 Mr. Jeff Klenk Howard County Public School System 10910 Route 108 Ellicott City, MD 21043 RE: Tape Lift and Swab Sampling of Items found at Glenwood Middle School Project #J15-876 Dear

More information

DATE: April 21, TO: Lisa Moore, Executive Director

DATE: April 21, TO: Lisa Moore, Executive Director DATE: April 21, 2017 TO: Lisa Moore, Executive Director SUBJECT: Bolin - IAQ - Results report - Payroll - Moore Office - Dragisic Office - Large Room, Storage Room, Copy Room On Tuesday 4/4 and Friday

More information

Mycotech Biological, Inc.

Mycotech Biological, Inc. AIHA EMPAT NO: 03006 00 Main Street Any City, TX Andersen Malt /2/04 /0/04 Sample No: (0) A- Sample No: (02) A-2 Sample No: (03) A-3 (Living Area) Sample No: (04) A-4 (Bedroom) //04 //04 //04 //04 Date

More information

Schneider Laboratories Global, Inc

Schneider Laboratories Global, Inc Analysis Report Schneider Laboratories Global, Inc 2512 W. Cary Street Richmond, Virginia 23220-5117 804-353-6778 800-785-LABS (5227) Fax 804-359-1475 Customer Asbestos Science Technologies, Inc (4038)

More information

1251 Weatherstone Ct. Reston,VA Mold Reduction Report

1251 Weatherstone Ct. Reston,VA Mold Reduction Report GreenClean Air Weatherstone Ct. Reston,VA 094 70.97.7 Steve@GreenCleanAir.com Mold Reduction Report November, 0 Rodney Fugitt Strategic Property Systems 077 Alyssia Lane Waldorf, MD 060 Re: 90 Messina

More information

January 31, Mr. Mark LaFleur Director of Plant Operations Town of Needham 1330 Highland Avenue Needham, MA 02492

January 31, Mr. Mark LaFleur Director of Plant Operations Town of Needham 1330 Highland Avenue Needham, MA 02492 OccuHealth, Inc. 44 Wood Avenue Mansfield, MA 02048 Occupational Health & Safety, Environmental Consultants Tel. (508) 9-9119 Tel. (800) 729-105 Fax (508) 9-289 thamilton@occuhealth.com January 1, 2007

More information

RLB CIH, LLC. Final Report Microbial Contamination Sampling Taos Recreation Center Taos, New Mexico. March 9, 2007

RLB CIH, LLC. Final Report Microbial Contamination Sampling Taos Recreation Center Taos, New Mexico. March 9, 2007 Final Report Microbial Contamination Sampling Taos Recreation Center Taos, New Mexico RLB CIH, LLC Ronald L. Beethe, CIH 505-268-5829 400 Alvarado NE FAX 256-9554 Albuquerque, NM 87108 rlbcih@comcast.net

More information

April 28, Town of Wilton Board of Education 395 Danbury Road Wilton, CT 06897

April 28, Town of Wilton Board of Education 395 Danbury Road Wilton, CT 06897 Town of Wilton Board of Education 395 Danbury Road Wilton, CT 06897 RE: Indoor Air Quality Assessment Report Miller-Driscoll School 217 Wolf Pit Road, Wilton, Connecticut TRC Project No. 215883.1000 Board

More information

Analysis Report prepared for Mold-Spec

Analysis Report prepared for Mold-Spec contact@hayesmicrobial.com http://hayesmicrobial.com/ Analysis Report prepared for Ormond Beach, FL. 3173 Date Sampled: 03-06-018 Date Analyzed: 03-08-018 Report Date: 03-08-018 EPA Laboratory ID# VA01419

More information

Certificate of Mold Analysis

Certificate of Mold Analysis COASTAL ENVIRONMENTAL PO BOX 167 HAMMONTON, NJ 08330 Certificate of Mold Analysis Prepared for: COASTAL ENVIRONMENTAL Phone Number: (609) 820-9312 Fax Number: (609) 561-6197 Project Name: LEEDS CLEARANCE

More information

AIRBORNE FUNGAL STRUCTURE SAMPLE ANALYSIS Results reported as Structures per Cubic Meter of Air (structures/m 3 )

AIRBORNE FUNGAL STRUCTURE SAMPLE ANALYSIS Results reported as Structures per Cubic Meter of Air (structures/m 3 ) Field #: TM042709 Project #: 141186 Description: Background, Outside, Main Lab #: 1504110 Entrance Eagle #: E15042809 Results reported as per Cubic Meter of Air Structure Identification ascospores (undifferentiated)

More information

This test report contains the following four sections: Chain of Custody, Data Detail, Frequently Asked Questions, and Glossary.

This test report contains the following four sections: Chain of Custody, Data Detail, Frequently Asked Questions, and Glossary. This test report contains the following four sections: Chain of Custody, Data Detail, Frequently Asked Questions, and Glossary. Direct Exam Chain of Custody Page 1 1 Results apply only to samples tested.

More information

INDUSTRIAL HYGIENE ASSOCIATES, INC.

INDUSTRIAL HYGIENE ASSOCIATES, INC. (215) 672-6088 Fax (215) 443-0899 INDUSTRIAL HYGIENE ASSOCIATES, INC. June 21, 2016 Mr. David Hansel New Hope-Solebury School District Office: Email: 215-862-5372 x3119 dhansel@nhsd.org Re: Eagle Industrial

More information

Occupational Health & Safety, Environmental Consultants Tel. (508) Tel. (800) Fax (508)

Occupational Health & Safety, Environmental Consultants Tel. (508) Tel. (800) Fax (508) OccuHealth, Inc. 44 Wood Avenue Mansfield, MA 02048 Occupational Health & Safety, Environmental Consultants Tel. (508) 339-9119 Tel. (800) 729-1035 Fax (508) 339-2893 t_hamilton@occuhealth.com December

More information

FUNGAL (MOLD) TESTING RESULT REPORT* Cover Page

FUNGAL (MOLD) TESTING RESULT REPORT* Cover Page FUNGAL (MOLD) TESTING RESULT REPORT* Cover Page RESULT TABLES ANALYTICAL REPORT (Spore trap report) MOLD BRIEF DESCRIPTIONS (In a separate file) Verified By: Wei Cohen, B.S. Approved By: Jian (Young) Bao,

More information

Airborne Mould Sampling Moncton High School 207 Church Street Moncton, NB E1C 5A3. November 01, 2013

Airborne Mould Sampling Moncton High School 207 Church Street Moncton, NB E1C 5A3. November 01, 2013 Project # 18578 Airborne Mould Sampling Moncton High School 207 Church Street Moncton, NB E1C 5A3 November 01, 2013 Attention: Serge Melanson Transportation and Infrastructure Facilities Management Moncton

More information

Legally Defensible Strategies for Mold Investigations

Legally Defensible Strategies for Mold Investigations Legally Defensible Strategies for Mold Investigations Metro New York AIHA Bull Moose Meeting September 10, 2014 Jack Springston, CIH, CSP TRC Environmental, Inc. www.trcsolutions.com Disclaimer The contents

More information

Environmental Assessment, Timothy Dwight Elementary School 1600 Redding Road, Fairfield, Connecticut

Environmental Assessment, Timothy Dwight Elementary School 1600 Redding Road, Fairfield, Connecticut COMMITMENT & INTEGRITY DRIVE RESULTS 40 Shattuck Road Suite 110 Andover, Massachusetts 01810 www.woodardcurran.com T 866.702.6371 T 978.557.8150 F 978.557.7948 Via Electronic Mail November 6, 2018 Thomas

More information

EDLab. Re: 0 Any Street, # 100 Laboratory Analysis Report Work Authorization #

EDLab. Re: 0 Any Street, # 100 Laboratory Analysis Report Work Authorization # EDLab Environmental Diagnostics Laboratory January 6, 2017 Jane Example 0 Any Street, # 100 Clearwater, FL Laboratory Advisory Board Alan L. Wozniak, CIAQP President/CEO Mark D. Wozniak, MBA, CIAQP Vice

More information

Certificate of Mold Analysis (941) (941) SAMPLE REPORT

Certificate of Mold Analysis (941) (941) SAMPLE REPORT BUILDING INSPECTION OF FLORIDA PO BOX 380955 MURDOCK, FL 33938 Certificate of Mold Analysis Prepared for: Phone Number: Fax Number: BUILDING INSPECTION OF FLORIDA (941)743-3164 (941)743-4236 Currently

More information

Airborne Mould Sampling Moncton High School 207 Church Street Moncton, NB E1C 5A3. November 25, 2013

Airborne Mould Sampling Moncton High School 207 Church Street Moncton, NB E1C 5A3. November 25, 2013 Project # 18578 Airborne Mould Sampling Moncton High School 207 Church Street Moncton, NB E1C 5A3 November 25, 2013 Attention: Serge Melanson Transportation and Infrastructure Facilities Management Moncton

More information

Certificate of Mold Analysis

Certificate of Mold Analysis HEARTLAND INSPECTIONS 3515 HUMBOLDT AVE SO MINNEAPOLIS, MN 55408 Certificate of Mold Analysis Prepared for: HEARTLAND INSPECTIONS Phone Number: (612) 860-4578 Fax Number: Project Name: CORRIGAN Test Location:

More information

Schneider Laboratories Global, Inc

Schneider Laboratories Global, Inc Analysis Report Schneider Laboratories Global, Inc 2512 W. Cary Street Richmond, Virginia 23220-5117 804-353-6778 800-785-LABS (5227) Fax 804-359-1475 Customer: Asbestos Science Technologies, Inc (4038)

More information

March 01, Re: Mold Sampling. Dear Mr. Jon Lewis,

March 01, Re: Mold Sampling. Dear Mr. Jon Lewis, 1990 S. Garrison St. Suite 6 Lakewood, CO 80227 Office 303-980-4401 Fax 303-980-4402 March 01, 2013 Re: Mold Sampling Dear Mr. Jon Lewis, Aspen Environmental, Inc. representatives completed the mold air

More information

Industrial Hygiene Sampling. Husqvarna Construction Products

Industrial Hygiene Sampling. Husqvarna Construction Products Report of: Industrial Hygiene Sampling Husqvarna Construction Products Olathe, KS Palmetto EHS Report No: 2017102 (Project 3) Submitted Prepared for: Husqvarna Construction Products Prepared By:! Palmetto

More information

Industrial Hygiene Sampling. Husqvarna Construction Products

Industrial Hygiene Sampling. Husqvarna Construction Products Report of: Industrial Hygiene Sampling Husqvarna Construction Products Olathe, KS Palmetto EHS Report No: 2017069 (Project 2) Submitted Prepared for: Husqvarna Construction Products Prepared By:! Palmetto

More information

Certificate of Mold Analysis

Certificate of Mold Analysis CHICAGO INSPECTION AGENCY 815 N SCHOOL ST PROSPECT HEIGHTS, IL 60070 Certificate of Mold Analysis Prepared for: CHICAGO INSPECTION AGENCY Phone Number: (847) 459-9387 Fax Number: (847) 459-9443 Project

More information

Certificate of Mold Analysis

Certificate of Mold Analysis COASTAL ENVIRONMENTAL PO BOX 167 HAMMONTON, NJ 08330 Certificate of Analysis Prepared for: COASTAL ENVIRONMENTAL Phone Number: (609) 820-9312 Fax Number: (609) 561-6197 Project Name: Test Location: NORTH

More information

Regulatory Compliance 245 Albany Avenue Thornwood, New York (914) Indoor Air Quality Screening At. Scarsdale UFSD

Regulatory Compliance 245 Albany Avenue Thornwood, New York (914) Indoor Air Quality Screening At. Scarsdale UFSD Regulatory Compliance 245 Albany Avenue Thornwood, New York 10594 (914) 439-6513 Indoor Air Quality Screening At DRAFT Scarsdale UFSD High School 1057 East post Road Scarsdale, NY 10583 Various Rooms RegCom

More information

MOLD SCREEN CHECK SAMPLE LAB REPORT

MOLD SCREEN CHECK SAMPLE LAB REPORT MOLD SCREEN CHECK SAMPLE LAB REPORT PRESENTED BY: www.edlab.org 1-800-422-7873 Ext. 301 Copyright 2010 Pure Air Control Services April 11, 2008 Alan L. Wozniak, CIAQP President/CEO Mark D. Wozniak, M.B.A.,

More information

This test report contains the following four sections: Chain of Custody, Data Detail, Frequently Asked Questions, and Glossary.

This test report contains the following four sections: Chain of Custody, Data Detail, Frequently Asked Questions, and Glossary. This test report contains the following four sections: Chain of Custody, Data Detail, Frequently Asked Questions, and Glossary. Direct Exam Chain of Custody Page 1 1 Results apply only to samples tested.

More information

AladdinEnvironmentalLLC

AladdinEnvironmentalLLC "" 1 AladdinEnvironmentalLLC 321 W. Josephine * San Antonio. TX 78212 * 2107361826x218 * Fax 2107323667 Texas Mold Assessment Consultant MAC0383 June 16,2008 San Antonio Housing Authority Attn: Bart Swider,

More information

Certificate of Mold Analysis

Certificate of Mold Analysis ACE ENVIRONMENTAL 49 SHADOWCREEK WAY ORMOND BEACH, FL 32174 Certificate of Mold Analysis Prepared for: ACE ENVIRONMENTAL Phone Number: (904) 859-9211 Fax Number: Project Name: TOM HARTSFIELD Test Location:

More information

Program Title Indoor Air Quality. Classification General Safety. Program No INTRODUCTION

Program Title Indoor Air Quality. Classification General Safety. Program No INTRODUCTION ENVIRONMENTAL HEALTH AND SAFETY EHS PROGRAM MANUAL Program Title 1.0 INTRODUCTION 7.7 General Safety As part of the Weill Cornell Medical College (WCMC) Environmental Health and Safety (EHS) Program Manual,

More information

Certificate of Mold Analysis

Certificate of Mold Analysis ACE ENVIRONMENTAL 49 SHADOWCREEK WAY ORMOND BEACH, FL 32174 Certificate of Mold Analysis Prepared for: ACE ENVIRONMENTAL Phone Number: (904) 859-9211 Fax Number: Project Name: NIA NETANE Test Location:

More information

Certificate of Mold Analysis

Certificate of Mold Analysis HOLMES INSPECTION COMPANY PO BOX 12787 SHAWNEE MISSION, KS 66282 Certificate of Mold Analysis Prepared for: HOLMES INSPECTION COMPANY Phone Number: (816) 455-8787 Fax Number: (267) 222-7185 Project Name:

More information

Certificate of Mold Analysis

Certificate of Mold Analysis BULLSEYE INSPECTION 1802 INGRAM AVE SARASOTA, FL 34232 Certificate of Mold Analysis Prepared for: BULLSEYE INSPECTION Phone Number: (941)341-0577 Fax Number: (941)341-0577 Project Name: SARASOTA, FL 34238

More information

AIRBORNE MOLD SPORE ANALYSIS

AIRBORNE MOLD SPORE ANALYSIS 11080 SW Allen Blvd, Suite, Beaverton, OR 97005 P: 503.292.5346 F: 503.203.1516 Tuesday, May 23, 2017 Ken Studnick Address: 38875 N 1st Ave, Scio, OR 97374 Projects 17-16079 and 16-14152 Dear Ken: SUMMARY

More information

Literature Building Mold Sampling Report

Literature Building Mold Sampling Report Literature Building Mold Sampling Report University of California, San Diego Prepared By: Aurora Industrial Hygiene San Diego, CA Prepared By: Date: April 6, 2009 Karen G. Shockley, CIH #6766 TABLE OF

More information

Indiana University Environmental Health & Safety Beau Middaugh 2427 E. 2nd street Bloomington, IN USA (812)

Indiana University Environmental Health & Safety Beau Middaugh 2427 E. 2nd street Bloomington, IN USA (812) Indiana University Environmental Health & Safety Beau Middaugh 2427 E. 2nd street Bloomington, IN 47401 USA (812) 855-6316 Approved by: Dates of Analysis: MoldReport Spore trap: 11-08-2018 Technical Manager

More information

Certificate of Mold Analysis

Certificate of Mold Analysis CHICAGO INSPECTION AGENCY 815 N SCHOOL ST PROSPECT HEIGHTS, IL 60070 Certificate of Mold Analysis Prepared for: CHICAGO INSPECTION AGENCY Phone Number: (847)459-9387 Fax Number: (847)459-9443 Project Name:

More information

Regulatory Compliance 245 Albany Avenue Thornwood, New York (914) Indoor Air Quality Screening At. Scarsdale UFSD

Regulatory Compliance 245 Albany Avenue Thornwood, New York (914) Indoor Air Quality Screening At. Scarsdale UFSD Regulatory Compliance 245 Albany Avenue Thornwood, New York 10594 (914) 439-6513 Indoor Air Quality Screening At Scarsdale UFSD Greenacres School 41 Huntington Avenue Scarsdale, NY 10583 RegCom s Project

More information

C E R T I F I C A T E O F M O L D A N A L Y S I S

C E R T I F I C A T E O F M O L D A N A L Y S I S C E R T I F I C A T E O F M O L D A N A L Y S I S PREPARED FOR: A Plus Inspections of Texas Phone Number: (713) 249-2618 Email: paul@inspec4.net Test Location: Phil Homebuyer 123 Mold City Dr Houston,

More information

Certificate of Mold Analysis

Certificate of Mold Analysis COASTAL ENVIRONMENTAL PO BOX 167 HAMMONTON, NJ 08330 Certificate of Mold Analysis Prepared for: COASTAL ENVIRONMENTAL Phone Number: (609) 820-9312 Fax Number: (609) 561-6197 Project Name: SOUTH MAIN CLEAR

More information

Antelope Valley College Joel I. Berman, CIH, CSP, CIAQM, CAC February 26 and 27, 2014

Antelope Valley College Joel I. Berman, CIH, CSP, CIAQM, CAC February 26 and 27, 2014 Mold and Fungi Awareness (Fungus 101) Antelope Valley College Joel I. Berman, CIH, CSP, CIAQM, CAC February 26 and 27, 2014 2 Mold and Fungi Awareness Fungus Mushrooms Yeasts Rusts Molds Smut Characterized

More information

Certificate of Mold Analysis

Certificate of Mold Analysis PRISTINE HOME INSPECTIONS 1817 S NEIL #104-2 CHAMPAIGN, IL 61820 Certificate of Mold Analysis Prepared for: PRISTINE HOME INSPECTIONS Phone Number: (217) 722-5883 Fax Number: (217) 2-9851 Project Name:

More information

test address: P R E PAR E D F OR : CalPro Inspection Group Phone Number: (800)

test address: P R E PAR E D F OR : CalPro Inspection Group Phone Number: (800) 3 3 0 1 N.W. 5 5 th S t., F t. Lauderdale, FL 3 3 3 0 9 ( 8 8 8 ) 8 5 4-0 4 7 7 prepared for: test address: CalPro Inspection Group 1234 Any Name St. Sacrameto, Ca 95835 C e r t i f i c a t e o f m o l

More information

C e r t i f i c a te o f m o ld Ana l y s i s

C e r t i f i c a te o f m o ld Ana l y s i s 3 3 0 1 N.W. 5 5 th S t., F t. Lauderdale, FL 3 3 3 0 9 ( 8 8 8 ) 8 5 4-0 4 7 7 C e r t i f i c a te o f m o ld Ana l y s i s P R E PARED F O R : TLC Home Inspections Phone Number: (512) 900-2191 Email:

More information

Protect your biggest investment. Live healthier. Because you re not only buying a home, you're also buying the air in it.

Protect your biggest investment. Live healthier. Because you re not only buying a home, you're also buying the air in it. Protect your biggest investment Live healthier Because you re not only buying a home, you're also buying the air in it. Most people spend as much as 90% of their time indoors and are not aware of the health

More information

Certificate of Mold Analysis

Certificate of Mold Analysis WILCOX INSPECTIONS Certificate of Mold Analysis Prepared for: Phone Number: Fax Number: Project Name: Test Location: WILCOX INSPECTIONS Chain of Custody #: Received Date: September 4, 2015 Report Date:

More information

Certificate of Mold Analysis

Certificate of Mold Analysis ACE ENVIRONMENTAL 49 SHADOWCREEK WAY ORMOND BEACH, FL 32174 Certificate of Mold Analysis Prepared for: ACE ENVIRONMENTAL Phone Number: (904) 859-9211 Fax Number: Project Name: PINNAMENENI Test Location:

More information

Certificate of Mold Analysis

Certificate of Mold Analysis COASTAL ENVIRONMENTAL PO BOX 167 HAMMONTON, NJ 08330 Certificate of Mold Analysis Prepared for: COASTAL ENVIRONMENTAL Phone Number: (609) 820-9312 Fax Number: (609) 561-6197 Project Name: PVIL MIDDLE SCHOOL

More information

Submitted By: test test Submittal Date: 2/2/2017 1:47:53 PM Sample Date: 2/1/2017 Lab Job No.: Page 1 1

Submitted By: test test Submittal Date: 2/2/2017 1:47:53 PM Sample Date: 2/1/2017 Lab Job No.: Page 1 1 CLIENT INFORMATION Moldlab 2501 Mayes Road Suite #110 Project No.: 555 PROJECT INFORMATION John Smith 123 North Street This test report contains the following sections: Chain of Custody, Report (and optionally

More information

Schneider Laboratories Global, Inc

Schneider Laboratories Global, Inc Received PO 195016-001 1 Library - Middle 12/6/2016 Torula 9 75 9 75 5 75 4 75 50 Non-fungal particulates present. *4 387 spores/m3 120 spores/m3 67 spores/m3 53 spores/m3 667 spores/m3 195016-002 2 Library

More information

Joseph T. Burkeson. Tuesday, November 19th, Total Professional Installation 1293 N. 60th St Tampa Fl, 33619

Joseph T. Burkeson. Tuesday, November 19th, Total Professional Installation 1293 N. 60th St Tampa Fl, 33619 Tuesday, November 19th, 2013 Total Professional Installation 1293 N. 60th St Tampa Fl, 33619 Mold Sample Survey 37612 Oak Terrace, St Petersburg, FL 33703 On Friday, November 15th, 2013 I performed a Mold

More information

MSES consultants, inc.

MSES consultants, inc. MSES consultants, inc. 609 West Main Street P.O. Drawer 190 Clarksburg, WV 26302-0190 304.624.9700 304.622.0981 304.842.3325 http://www.msesinc.com Office September 13, 2012 Project Number: 12-437 Mr.

More information

Based on our review, the following primary chemical constituents were identified for sampling: Acetone Toluene Xylenes Heptane

Based on our review, the following primary chemical constituents were identified for sampling: Acetone Toluene Xylenes Heptane December 15, 2017 Mr. Jeremy McDevitt Kenston Local Schools 1719 Snyder Road Chagrin Falls, Ohio 44022 RE: Indoor Air Quality Evaluation Kenston Middle School, 17425 Snyder Road, Kenston, Ohio OH41465

More information

PRO-TEC MOLD REPORT. Mold Evaluation

PRO-TEC MOLD REPORT. Mold Evaluation PRO-TEC MOLD REPORT CLIENT & SITE INFORMATION: DATE OF INSPECTION: 09/17/20. CLIENT NAME:. NUMBER & STREET: CITY/STATE/ZIP: Reston VA 20191. INSPECTED BY: Rob Hopkin. CLIMATIC CONDITIONS: WEATHER: Clear.

More information

STC Environmental Services Inc. Environmental Scientists and Engineers

STC Environmental Services Inc. Environmental Scientists and Engineers Environmental Services Inc. Environmental Scientists and Engineers 4754 RESEARCH DRIVE SAN ANTONIO, TEXAS 78240 Office (210) 69tHi286/ FAX (210) 696-8761 May 3, 2007 Mr. Henry A. Alvarez III SAHA 818 S.

More information

MSES consultants, inc.

MSES consultants, inc. MSES consultants, inc. 609 West Main Street P.O. Drawer 190 Clarksburg, WV 26302-0190 304.624.9700 304.622.0981 304.842.3325 http://www.msesinc.com Office December 5, 2013 Project Number: 13-441 Mr. Joe

More information

Limited Indoor Air Quality Assessment

Limited Indoor Air Quality Assessment Limited Indoor Air Quality Assessment SALINAS ELEMENTARY SCHOOL 1000 Century Drive Laredo, Texas January 11, 2011 Terracon Project No. 90107328 Prepared for: United Independent School District 3501 East

More information

CERTIFICATE OF MOLD ANALYSIS

CERTIFICATE OF MOLD ANALYSIS CERTIFICATE OF MOLD ANALYSIS PREPARED FOR: Doc Shane Test Client Account Phone Number: (888) 854-0478 Email: docshane@inspectorlab.com Test Location: Max Headroom 1234 John Muir Street Hayward, CA 94544

More information

Certificate of Mold Analysis

Certificate of Mold Analysis Tri-State Smart Home Solutions LLC CHRIS FARVER GALLIPOLIS, OH 45631 Certificate of Analysis Prepared for: CHRIS FARVER Phone Number: (74) 28-3966 Fax Number: Project Name: Test Location: Address City,

More information

Certificate of Mold Analysis

Certificate of Mold Analysis CERTIFIED INSPECTION SERVICES 1211 NE 19TH TER. CAPE CORAL, FL 33909 Certificate of Mold Analysis Prepared for: CERTIFIED INSPECTION SERVICES Phone Number: (239) 458-9876 Fax Number: (239) 673-7964 Project

More information

MSES consultants, inc.

MSES consultants, inc. MSES consultants, inc. 609 West Main Street P.O. Drawer 190 Clarksburg, WV 26302-0190 304.624.9700 304.622.0981 304.842.3325 http://www.msesinc.com Office December 30, 2013 Project Number: 13-441 Mr. Joe

More information

MYCOLOGY REPORT. Report: / 3503 Wgaon Wheel, Wichita Falls, TX

MYCOLOGY REPORT. Report: / 3503 Wgaon Wheel, Wichita Falls, TX MYCOLOGY REPORT Date: May 28, 15 Flint Inspection Consulting Services, Inc. Report: 6315-1694 15-036 / 3503 Wgaon Wheel, Wichita Falls, TX This document shall be considered a duly signed original report

More information

Certificate of Mold Analysis

Certificate of Mold Analysis Certificate of Mold Analysis Prepared for: Phone Number: Fax Number: Project Name: Test Location: TEXINSPEC Chain of Custody #: Received Date: November 6, 2018 Report Date: November 6, 2018 Elena Santiago,

More information

C e r t i f i c a t e o f m o l d A n a l y s i s

C e r t i f i c a t e o f m o l d A n a l y s i s 3 3 0 1 N.W. 5 5 t h S t., F t. L a u d e r d a l e, F L 3 3 3 0 9 3301 N.W. 55th St., Ft. Lauderdale, ( 8 0 0 ) 5FL 4 433309-8 1 5 6888-854-0477 C e r t i f i c a t e o f m o l d A n a l y s i s P R E

More information

Indoor Air Quality: Mold, Patients

Indoor Air Quality: Mold, Patients Indoor Air Quality: Mold, Patients and Elevators? Matthew L. Berkheiser, DrPH, CIH, CSP Executive Director & Chief Safety Officer Environmental Health & Safety May 2012 Background Cost of hospital-acquired

More information

Certificate of Mold Analysis

Certificate of Mold Analysis INDOOR AIR QUALITY CORPORATION 1675 N COMMERCE PKWY WESTON, FL 33326 Certificate of Mold Analysis Prepared for: INDOOR AIR QUALITY CORPORATION Phone Number: (407) 463-8666 Fax Number: (954) 332-1005 Project

More information

CONCENTRATIONS OF VIABLE FUNGAL SPORES ON PAPER DOCUMENTS

CONCENTRATIONS OF VIABLE FUNGAL SPORES ON PAPER DOCUMENTS 1 INTRODUCTION CONCENTRATIONS OF VIABLE FUNGAL SPORES ON PAPER DOCUMENTS This work was performed as part of a broader Indoor Air Quality (IAQ) response action, which lasted in excess of eight months. A

More information

CITY OF FORT PIERCE HOUSING REHABILATION PROJECT FOR 2802 AVENUE I BID NO ADDENDUM NO. 4

CITY OF FORT PIERCE HOUSING REHABILATION PROJECT FOR 2802 AVENUE I BID NO ADDENDUM NO. 4 March 10, 2015 CITY OF FORT PIERCE HOUSING REHABILATION PROJECT FOR 2802 AVENUE I BID NO. 2015-022 ADDENDUM NO. 4 The purpose of this addendum is to extend the bid due date from 3:00PM, Tuesday, March

More information

INDOOR AIR QUALITY CLEARANCE SAMPLING

INDOOR AIR QUALITY CLEARANCE SAMPLING 5 Route, Suite C4 Brewster, NY 0509 845.78.770 90 State Street, Suite 700 Albany, NY 07 58.874.067 967 Wehrle Drive, Suite One Buffalo, NY 4 76..4580 E-mail: adelaidemail@adelaidellc.com Fax: 845.78.7750

More information

AGENDA REQUEST. November 7, 2016

AGENDA REQUEST. November 7, 2016 AGENDA HEADING: Unfinished Business AGENDA REQUEST COMMISSION MEETING DATE: November 7, 2016 AGENDA ITEM NO: BY City Auditor and Clerk Pamela M. Nadalini Tonya Erbland, CIAQP, Senior Environmental Scientist,

More information

Certificate of Mold Analysis

Certificate of Mold Analysis COASTAL ENVIRONMENTAL PO BOX 167 HAMMONTON, NJ 08330 Certificate of Mold Analysis Prepared for: COASTAL ENVIRONMENTAL Phone Number: Fax Number: Project Name: DECANTOR AVE SCHOOL Test Location:, Chain of

More information

STC Environmental Services Inc. Environmental Scientists and Engineers

STC Environmental Services Inc. Environmental Scientists and Engineers Environmental Services nc. Environmental Scientists and Engineers 4754 RESEARCH DRVE SAN ANTONO, TEXAS 78240 Office (210) 69(Hi286/ FAX (210) 696-8761 May 3, 2007 Mr. Henry A. Alvarez SAHA 818 S. Flores

More information

AIR PURIFICATION AND AROMATHERAPY SYSTEM

AIR PURIFICATION AND AROMATHERAPY SYSTEM AIR PURIFICATION AND AROMATHERAPY SYSTEM Dusty Air! It is widely acknowledged that the air in today s homes is filled with dust, pollen, mold and thousands of other pollutants. Regardless of their state

More information

Asbestos Containing Materials Assessment 294 Earle Drive Greenville, South Carolina

Asbestos Containing Materials Assessment 294 Earle Drive Greenville, South Carolina Asbestos Containing Materials Assessment 294 Earle Drive Greenville, South Carolina Prepared for: Habitat for Humanity 49 Greenland Drive Greenville, South Carolina Prepared by: Apex Environmental Management,

More information

IAQ Mold Concerns. CAPT Don Hagen, USN, MS, CIH Navy Marine Corp Public Health Center

IAQ Mold Concerns. CAPT Don Hagen, USN, MS, CIH Navy Marine Corp Public Health Center IAQ Mold Concerns CAPT Don Hagen, USN, MS, CIH Navy Marine Corp Public Health Center 0 Disclaimer The views expressed in this presentation are those of the author and do not necessarily reflect the official

More information

Introduction: PCR Air Sampling: November 12, Carrie E Tompkins Elementary School PCR Fungi Study:

Introduction: PCR Air Sampling: November 12, Carrie E Tompkins Elementary School PCR Fungi Study: 23 STATE STREET OSSINING, NEW YORK 10562 TEL.: (914) 762-6333 FAX: (914) 762-5578 W W W. E M S O F N Y. C O M November 12, 2014 Environmental Science Safety Engineering Industrial Hygiene Environmental

More information

Influence of Environmental Parameters on Mold Sampling Results

Influence of Environmental Parameters on Mold Sampling Results University of South Florida Scholar Commons Graduate Theses and Dissertations Graduate School June 2017 Influence of Environmental Parameters on Mold Sampling Results Benjamin Fishman University of South

More information

Indiana University Environmental Health & Safety Beau Middaugh 2427 E. 2nd street Bloomington, IN USA (812)

Indiana University Environmental Health & Safety Beau Middaugh 2427 E. 2nd street Bloomington, IN USA (812) Indiana University Environmental Health & Safety Beau Middaugh 2427 E. 2nd street Bloomington, IN 47401 USA (812) 855-6316 Approved by: Dates of Analysis: MoldReport Spore trap: 10-31-2018 and 10-31-2018

More information

Certificate of Mold Analysis

Certificate of Mold Analysis ACE ENVIRONMENTAL 300 BELLA HARBOR CT #111 PALM COAST, FL 32137 Certificate of Mold Analysis Prepared for: ACE ENVIRONMENTAL Phone Number: (904) 859-9211 Fax Number: Project Name: Test Location: 1745 WINDSONG

More information