Literature Building Mold Sampling Report

Size: px
Start display at page:

Download "Literature Building Mold Sampling Report"

Transcription

1 Literature Building Mold Sampling Report University of California, San Diego Prepared By: Aurora Industrial Hygiene San Diego, CA Prepared By: Date: April 6, 2009 Karen G. Shockley, CIH #6766

2 TABLE OF CONTENTS USE OF THIS REPORT Introduction Executive Summary Observations... 4 Table 1. Observations Mold Sampling Methodology... 5 Total Spore Air Samples... 6 Viable Air Samples... 6 Moisture Readings Laboratory Results for Mold Sampling... 7 Table 2. Indoor and Outdoor Total Spore Air Sampling Results March 5, Table 3. Indoor and Outdoor Viable Spore Air Sampling Results March 5, Table 4. Indoor Total Spore Air Sampling Results 4 th Floor Table 5. Indoor Total Spore Air Sampling Results 3 rd Floor Table 6. Indoor Total Spore Air Sampling Results 2 nd & 1 st Floors Table 7. Indoor Total Spore Air Sampling Results 1 st Floor Table 8. Outdoor Total Spore Air Sampling Results March 10 and 12, Mold Discussion Limitations Appendix One Photographs Appendix Two Site Diagrams Appendix Three Laboratory Reports of Analysis and Chains of Custody Literature Building Page 2

3 USE OF THIS REPORT This report is intended to provide an understanding of the potential hazards that the property evaluated in this report may pose to human health due to airborne mold. This report is based primarily upon data and information obtained during a three site visits by Aurora Industrial Hygiene, Inc. (Aurora) to the property identified herein on March 5, 10, and 12, 2009 and is based solely upon the condition of the property on the dates of such assessments. Aurora has performed the work, made the findings, and proposed recommendations described in this report in accordance with generally accepted industrial hygiene and environmental science practices for mold in effect at the time the work was performed. This warrantee stands in lieu of all other warranties, expressed or implied. While this report can be used as a guide by the client, it must be understood that changing circumstances in the environment and in property usage can alter radically the conclusions and information contained in this report. 1.0 Introduction This report documents the findings from mold sampling conducted by Aurora in the Literature Building (#627) on the UCSD La Jolla Campus in San Diego, California. The purposes of the survey were to visually assess the condition of the rooms sampled for signs of water damage or intrusion, and to conduct sampling to indicate whether mold was compromising the indoor air quality in selected rooms throughout all four floors of the building. The survey was limited to a list of rooms provided by UCSD personnel. Per the scope of work as outlined by UCSD, the remainder of the Literature Building was not assessed. In the course of completing this inspection, Aurora met with Steve Benedict and Sarah Meyer, UCSD Environment, Health and Safety Department; and Nancy Ho-Wu and Nancy Daly, Literature Department. Karen Shockley and Rick Shockley visited the site on March 5, Rick Shockley returned to the site on March 10 and 12, 2009 to complete the inspection and collect samples. All work was completed under the supervision of Certified Industrial Hygienist Karen Shockley (CIH #6766). 2.0 Executive Summary Aurora was provided a list of rooms by UCSD. In each room, Aurora conducted a visual assessment and air sampling for mold. Moisture measurements were conducted if there was a visual indication of water intrusion and randomly of carpet and drywall walls in some of the rooms that were assessed. Air samples for total mold spores and viable mold spores were collected in the building and outdoors. The outdoor air samples were collected to provide an indication of background levels of airborne mold in the area. Surface tape lift samples for mold were not collected because no visible suspect mold was observed by Mr. Shockley. Literature Building Page 3

4 Air sample results indicated that the airborne mold spores indoors were comparable to the outdoor/background sample locations. Results did not indicate any degradation of the air quality from mold. Moisture readings were all in the safe/dry range. # 3.0 Observations Aurora conducted a visual assessment of the rooms on the list provided by UCSD. Aurora conducted moisture measurements if there was a visual indication of water intrusion and randomly of carpet and drywall walls in some of the rooms that were assessed. The visual assessment included looking above drop ceiling tiles only if stained tiles were noted. The following table indicates the number of operable windows, whether they were opened or closed during the assessment, and any other notable observations found by Mr. Shockley. Surface tape lift samples for mold were not collected because visible suspect mold was not observed by Mr. Shockley. Number of Operable Window Closed or Open Table 1. Observations Other Comments 454 None Office is dusty Slightly open Closed Closed Closed Open Could be a dog routinely in room, photo on shelf and bowl on floor Closed Open Office is messy, dog food in room Closed Tea cup and honey on a table Closed Closed Closed Not used, pretty empty 410 None New office space 354 None Sink in the room Closed Closed Closed Closed Slightly open Office is messy, stain on carpet and wall near door appear to be from coffee 337 None Literature Building Page 4

5 # Number of Operable Window Closed or Open 336 None Open Open Closed Closed Closed Closed Other Comments 310 None Recent remodel (18 months), sink/kitchenette in area 254 None Sink in room, water staining on ceiling tile above sink but everything looked dry above it Closed Fan on desk turned off prior to sampling Closed Slightly open 223 None 210 None There is a kitchen area with microwave and there was a food odor during sampling 110 None Closed Closed Closed Dirty on top of filing cabinets Closed Computer server room Closed Closed Closed Closed Closed 137 Double door Closed Sink in room 138 Double door Open Refrigerator and microwave in room Double doors Closed Closed Closed Closed Closed 4.0 Mold Sampling Methodology On March 5, 2009 Mr. Shockley collected air samples from ten sample locations, eight inside the building (two on each floor) and two outside of the building. On March 10, 2009 Mr. Shockley collected air samples from 45 sample locations, 42 inside the building (several on each floor) and Literature Building Page 5

6 three outside of the building. On March 12, 2009 Mr. Shockley collected air samples from two sample locations, one inside room 242, which was inaccessible on March 10, 2009, and one outside of the building. The outdoor air samples were collected to provide an indication of background levels of airborne mold in the area. At each of the sample locations on March 5, one air sample was collected to assess total airborne spores and one was collected to assess viable airborne spores. On March 10 and 12, only air sampling for total mold spores was conducted. Surface tape lift samples for mold were not collected because visible suspect mold was not observed by Mr. Shockley. Moisture measurements were collected randomly of carpet and drywall walls in some of the rooms that were assessed and all of the readings were in the Safe/Dry range. Total Spore Air Samples Air-O-Cell spore trap 37-mm cassettes are used to assess total spores. A sampling pump calibrated to a flow rate of 15 liters per minute draws a known volume of air over a sampling period of up to five (5) minutes. Once collected, the sample is submitted to a microbial laboratory where a small glass slide is removed from the cassette for direct examination. Viable Air Samples Air sampling for viable airborne mold spores and bacteria is performed using the Aerotech A-6 Single Stage Microbial Sampler, through which a known volume of air is collected and recorded. A sampling pump calibrated to a flow rate of 28.3 liters per minute is used to draw air through the A-6 sampling device. Within the A-6 sampling device is a petri dish that contains a laboratory prepared agar gel. Airborne particulates are deposited onto the agar gel. The sample is then sealed and submitted to a microbial laboratory where it is incubated in a controlled environment for 7-14 days. The petri dish samples are then assessed for viable mold and/or bacteria colonies, and reported in colony forming units, or CFUs. All of the collected mold samples were assigned a unique sample identification number, placed in sealed containers, labeled, and hand-delivered by Aurora Industrial Hygiene personnel to EMLab P&K Laboratory (EMLab), located at 9089 Clairemont Mesa Blvd, Suite 106, San Diego, CA EMLab is accredited by the American Industrial Hygiene Association for microbiological analyses. Moisture Readings Moisture readings were collected using a Protometer penetrating moisture meter. In wood, the instrument measures the material s actual percent moisture content (%H2O). When testing material other than wood, the meter measures the wood moisture equivalent (WME) value of the material. WME is the moisture level that would be attained by a piece of wood in equilibrium with the material being tested. As the critical moisture levels for wood are known, WME measurements enable the moisture meter user to establish if materials are in a safe air dry, borderline or damp condition. <18% (Green Zone) The material is in a Safe Dry condition, moisture related problems of decay/deterioration should not occur. Literature Building Page 6

7 18 20% (Yellow Zone) The material is in a Borderline condition, decay/deterioration may occur under certain conditions. >20% (Red Zone) The material is in a Wet condition, decay/deterioration is inevitable in time unless the moisture level of the material is reduced. 5.0 Laboratory Results for Mold Sampling Tables 2, 3, 4, 5, 6, 7 and 8 summarize the laboratory results for mold air sampling. Photographs of some of the sample locations are included in Appendix One, a sample location diagram is included in Appendix Two and laboratory reports of analysis are included in Appendix Three. Literature Building Page 7

8 Table 2. Indoor and Outdoor Total Spore Air Sampling Results March 5, 2009 Sample Identification A Outdoors, West of Building A A A A A A A A A Outdoors, South of Building Fungi Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Alternaria 13 Ascospores Basidiospores Cladosporium Other brown Penicillium/ Aspergillus types Pithomyces 13 Rusts 13 Smuts, Periconia, Myxomycetes Ulocladium Background Debris Sample Volume(liters) Spores/ m Background debris is an indication of the amount of non-biological particulate matter present on the slide (dust in the air) and is graded from 1+ to 4+ with 4+ indicating the largest amounts. To evaluate dust levels it is important to account for differences in sample volume. This background material is also an indication of visibility for the analyst and resultant difficulty reading the slide. For example, high background debris may obscure the small spores such as Penicillium/ Aspergillus group. Counts from areas with 4+ background debris should be regarded as minimal counts and may actually be higher than reported. Literature Building Page 8

9 Table 3. Indoor and Outdoor Viable Spore Air Sampling Results March 5, 2009 Sample Identification B Outdoors, West of Building B B B B B B B B B Outdoors, South of Building Fungi CFU 2 /m 3 CFU/m 3 CFU/m 3 CFU/m 3 CFU/m 3 CFU/m 3 CFU/m 3 CFU/m 3 CFU/m 3 CFU/m 3 Aureobasidium 12 Cladosporium Non-sporulating fungi Penicillium Yeasts 12 Sample Volume(liters) CFU/ m <12 < CFU = colony forming units Literature Building Page 9

10 Table 4. Indoor Total Spore Air Sampling Results 4 th Floor Sample Identification Fungi Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Alternaria 13 Ascospores Basidiospores Cladosporium Other brown Penicillium/ Aspergillus types Pithomyces Rusts 13 Smuts, Periconia, Myxomycetes 13 Ulocladium Background Debris Sample Volume(liters) Spores/ m < <13 3 Background debris is an indication of the amount of non-biological particulate matter present on the slide (dust in the air) and is graded from 1+ to 4+ with 4+ indicating the largest amounts. To evaluate dust levels it is important to account for differences in sample volume. This background material is also an indication of visibility for the analyst and resultant difficulty reading the slide. For example, high background debris may obscure the small spores such as Penicillium/ Aspergillus group. Counts from areas with 4+ background debris should be regarded as minimal counts and may actually be higher than reported. Literature Building Page 10

11 Sample Identification Table 5. Indoor Total Spore Air Sampling Results 3 rd Floor Fungi Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Spores/m Alternaria Basidiospores Bipolaris/ Drechlera group Cladosporium Other brown Penicillium/ Aspergillus types 53 Rusts 13 Smuts, Periconia, Myxomycetes Stachybotrys 13 Torula 13 Trichocladium Background Debris Sample Volume (liters) Spores/ m Background debris is an indication of the amount of non-biological particulate matter present on the slide (dust in the air) and is graded from 1+ to 4+ with 4+ indicating the largest amounts. To evaluate dust levels it is important to account for differences in sample volume. This background material is also an indication of visibility for the analyst and resultant difficulty reading the slide. For example, high background debris may obscure the small spores such as Penicillium/ Aspergillus group. Counts from areas with 4+ background debris should be regarded as minimal counts and may actually be higher than reported. Literature Building Page 11

12 Table 6. Indoor Total Spore Air Sampling Results 2 nd & 1 st Floors Sample Identification Fungi Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Alternaria 13 Ascospores Basidiospores Bipolaris/ Drechlera group 13 Cladosporium Epicoccum Other brown Penicillium/ Aspergillus types Rusts Smuts, Periconia, Myxomycetes Ulocladium Background Debris Sample Volume(liters) Spores/ m Background debris is an indication of the amount of non-biological particulate matter present on the slide (dust in the air) and is graded from 1+ to 4+ with 4+ indicating the largest amounts. To evaluate dust levels it is important to account for differences in sample volume. This background material is also an indication of visibility for the analyst and resultant difficulty reading the slide. For example, high background debris may obscure the small spores such as Penicillium/ Aspergillus group. Counts from areas with 4+ background debris should be regarded as minimal counts and may actually be higher than reported. Literature Building Page 12

13 Table 7. Indoor Total Spore Air Sampling Results 1 st Floor Sample Identification Fungi Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Alternaria Ascospores 13 Basidiospores Cladosporium Curvularia 13 Epicoccum 13 Other brown Penicillium/ Aspergillus types Rusts Smuts, Periconia, Myxomycetes Ulocladium Background Debris Sample Volume(liters) Spores/ m 3 < < Background debris is an indication of the amount of non-biological particulate matter present on the slide (dust in the air) and is graded from 1+ to 4+ with 4+ indicating the largest amounts. To evaluate dust levels it is important to account for differences in sample volume. This background material is also an indication of visibility for the analyst and resultant difficulty reading the slide. For example, high background debris may obscure the small spores such as Penicillium/ Aspergillus group. Counts from areas with 4+ background debris should be regarded as minimal counts and may actually be higher than reported. Literature Building Page 13

14 Table 8. Outdoor Total Spore Air Sampling Results March 10 and 12, 2009 Sample Identification Outdoors, East of building Outdoors, West of building Outdoors, South of building Outdoors, South of building Fungi Spores/m 3 Spores/m 3 Spores/m 3 Spores/m 3 Alternaria 13 Ascospores Basidiospores Bipolaris/ Drechlera group Cladosporium Curvularia Epicoccum Other brown 27 Penicillium/ Aspergillus types Pithomyces Rusts Smuts, Periconia, Myxomycetes Stachybotrys Torula Trichocladium Ulocladium Background Debris Sample Volume(liters) Spores/ m Background debris is an indication of the amount of non-biological particulate matter present on the slide (dust in the air) and is graded from 1+ to 4+ with 4+ indicating the largest amounts. To evaluate dust levels it is important to account for differences in sample volume. This background material is also an indication of visibility for the analyst and resultant difficulty reading the slide. For example, high background debris may obscure the small spores such as Penicillium/ Aspergillus group. Counts from areas with 4+ background debris should be regarded as minimal counts and may actually be higher than reported. Literature Building Page 14

15 6.0 Mold Discussion No regulatory standards exist for air or surface mold spores. High variability in mold spore concentrations will exist in different geographic locations, seasons, local weather patterns, and on a diurnal basis. The following basic guide provided by ETA Laboratories was used as a reference. Typical Indoor Mold Spore Concentration Ranges Description Spores /m3 Predominant Types "Clean" building Less than 2,000 Less than 700 Less than 500 Total for all spore types Penicillium, Aspergillus "Outdoor spores": alternaria, ascospores, basidiospores, cladosporium Possible Indoor Amplification 1,000-5,000 Penicillium, Aspergillus, Cladosporium Indoor amplification present 5,000-10,000 Penicillium, Aspergillus, Cladosporium Chronic Indoor Amplification 10,000-6,000,000 Penicillium, Aspergillus, Cladosporium, Stachybotrys, Basidiospores As a general rule, indoor fungal problems are usually indicated when a significant difference is demonstrated between indoor and outdoor airborne spore concentrations or types of spore genera or species. Mold spores concentrations indoors were comparable to outdoor samples and results did not indicate an indoor amplification of mold. Surface tape lift samples for mold were not collected because visible suspect mold was not observed by Mr. Shockley. Moisture measurements were collected randomly of carpet and drywall walls in some of the rooms that were inspected and all of the readings were in the Safe/Dry range. Literature Building Page 15

16 7.0 Limitations The data and observations collected during the course of this assessment have been gathered to provide the Client with information pertaining to the areas of the subject property identified in this report. Although Aurora believes that the findings and conclusions provided in this report are reasonable, the assessment is limited to the conditions observed and to the information available at the time of the work. Due to the nature of the work, there is a possibility that there may exist conditions which could not be identified within the scope of the assessment or which were not apparent at the time of our site work. The assessment is also limited to information available from the client at the time it was conducted. It is also possible that the testing methods employed at the time of the report may later be superceded by other methods. Aurora does not accept responsibility for changes in the state of the art. Aurora does not guarantee that all mold contaminated areas in the subject property were recognized during our evaluation. This report is limited to the samples taken and locations sampled. Additional sampling may be needed to further identify other pollutants or other mold contaminated areas at the subject property. Microbial growth may occur if sources of moisture are not remediated. We hope that this information is helpful. Please feel free to contact us at (619) if you have any questions. Literature Building Page 16

17 Appendix One Photographs Interstate 805 Interstate 5 Photo One Satellite photo. The dashed box is around the section of the UCSD La Jolla Campus that includes the Literature Building. Literature Building Page 17

18 Genesee Avenue Interstate 5 Photo Two Another satellite photo. The red arrow indicates the Literature Building. Literature Building Page 18

19 Sample location west of the building Sample location east of the building Sample location south of the building Photo Three Close-up photo of the Literature Building. The locations of the outdoor samples are indicated. Literature Building Page 19

20 Photo Four Outdoor sample location east of the building. Photo Five Outdoor sample location south of the building. Literature Building Page 20

21 Photo Six Outdoor sample location west of the building. Photo Seven Samples A and 09B collected in room 438. The red arrow points towards a water dish and cup of dog food found in the room. Literature Building Page 21

22 Photo Eight Sample collected in room 434. The red arrow points to the tea cup and honey on the table. Photo Nine Samples A and 06B collected in room 310. Literature Building Page 22

23 Photo Ten Sample collected in room 341. Photo Eleven Staining on carpet and wall in room 341 that appear to be from coffee. Literature Building Page 23

24 Photo Twelve Samples A and 05B collected in room 254. Photo Thirteen Staining on ceiling tile in room 254, everything looked dry above the stain. Literature Building Page 24

25 Photo Fourteen Sample collected in room 210. Photo Fifteen Samples A and 02B collected in room 134. Literature Building Page 25

26 Photo Sixteen Sample collected in room 123. Literature Building Page 26

27 Appendix Two Site Diagrams DIAGRAM NOT TO SCALE Literature Building Page 27

28 Literature Building Page 28

29 Literature Building Page 29

30 Literature Building Page 30

31 Appendix Three Laboratory Reports of Analysis and Chains of Custody Literature Building Page 31

32 EMLab P&K Report for: Ms. Karen Shockley Aurora Industrial Hygiene, Inc Cudahy Place Suite 120 San Diego, CA Regarding: Project: UCSD-Literature Building EML ID: Approved by: Dates of Analysis: Culturable air fungi (Incl. Asp spp.): Spore trap analysis: Lab Manager Malcolm Moody Project SOPs: Culturable air fungi (Incl. Asp spp.) (I100002), Spore trap analysis (I100000) This coversheet is included with your report in order to comply with AIHA and ISO accreditation requirements. For clarity, we report the number of significant digits as calculated; but, due to the nature of this type of biological data, the number of significant digits that is used for interpretation should generally be one or two. All samples were received in acceptable condition unless noted in the Report Comments portion in the body of the report. Due to the nature of the analyses performed, field blank corrections of results is not a standard practice. The results relate only to the items tested. EMLab P&K ("the Company") shall have no liability to the client or the client's customer with respect to decisions or recommendations made, actions taken or courses of conduct implemented by either the client or the client's customer as a result of or based upon the Test Results. In no event shall the Company be liable to the client with respect to the Test Results except for the Company's own willful misconduct or gross negligence nor shall the Company be liable for incidental or consequential damages or lost profits or revenues to the fullest extent such liability may be disclaimed by law, even if the Company has been advised of the possibility of such damages, lost profits or lost revenues. In no event shall the Company's liability with respect to the Test Results exceed the amount paid to the Company by the client therefor. Document Number: Revision Number: 5

33 Client: Aurora Industrial Hygiene, Inc. C/O: Ms. Karen Shockley Re: UCSD-Literature Building SPORE TRAP REPORT: NON-VIABLE METHODOLOGY Location: A: Outdoors, near main entrance A: 134 EMLab P&K 1010 N Central Avenue, Glendale, CA (866) Fax (858) Date of Sampling: Date of Receipt: Date of Report: A: A: 223 Comments (see below) None None None None Lab ID-Version : raw ct. spores/m3 raw ct. spores/m3 raw ct. spores/m3 raw ct. spores/m3 Alternaria Arthrinium Ascospores* 3 80 Aureobasidium Basidiospores* Bipolaris/Drechslera group Botrytis Chaetomium Cladosporium Curvularia Epicoccum Fusarium Myrothecium Nigrospora Other brown Other colorless Penicillium/Aspergillus types 1 53 Pithomyces 1 13 Rusts* Smuts*, Periconia, Myxomycetes* Stachybotrys Stemphylium Torula Ulocladium Zygomycetes Background debris (1-4+) Sample volume (liters) TOTAL SPORE/m Comments: * Most of these spore types are not seen with culturable methods (Andersen sampling), although some may appear as non-sporulating fungi. Most of the basidiospores are "mushroom" spores while the rusts and smuts are plant pathogens. The spores of Aspergillus and Penicillium (and others such as Acremonium, Paecilomyces) are small and round with very few distinguishing characteristics. They cannot be differentiated by non-viable sampling methods. Also, some species with very small spores are easily missed, and may be undercounted. Background debris indicates the amount of non-biological particulate matter present on the trace (dust in the air) and the resulting visibility for the analyst. It is rated from 1+ (low) to 4+ (high). Counts from areas with 4+ background debris should be regarded as minimal counts and may be higher then reported. It is important to account for samples volumes when evaluating dust levels. The Limit of Detection is the product of a raw count of 1 and 100 divided by the percent read. The analytical sensitivity (counts/m3) is the product of the Limit of Detection and 1000 divided by the sample volume. A "Version" greater than 1 indicates amended data. Total Spores/m3 has been rounded to two significant figures to reflect analytical precision. TestAmerica Environmental Microbiology Laboratory, Inc. EMLab ID: , Page 1 of 3

34 Client: Aurora Industrial Hygiene, Inc. C/O: Ms. Karen Shockley Re: UCSD-Literature Building EMLab P&K 1010 N Central Avenue, Glendale, CA (866) Fax (858) Date of Sampling: Date of Receipt: Date of Report: SPORE TRAP REPORT: NON-VIABLE METHODOLOGY Location: A: A: A: A: 427 Comments (see below) None None None None Lab ID-Version : raw ct. spores/m3 raw ct. spores/m3 raw ct. spores/m3 raw ct. spores/m3 Alternaria 1 13 Arthrinium Ascospores* 1 53 Aureobasidium Basidiospores* 1 13 Bipolaris/Drechslera group Botrytis Chaetomium Cladosporium Curvularia Epicoccum Fusarium Myrothecium Nigrospora Other brown Other colorless Penicillium/Aspergillus types 1 53 Pithomyces Rusts* 1 13 Smuts*, Periconia, Myxomycetes* Stachybotrys Stemphylium Torula Ulocladium Zygomycetes Background debris (1-4+) Sample volume (liters) TOTAL SPORE/m Comments: * Most of these spore types are not seen with culturable methods (Andersen sampling), although some may appear as non-sporulating fungi. Most of the basidiospores are "mushroom" spores while the rusts and smuts are plant pathogens. The spores of Aspergillus and Penicillium (and others such as Acremonium, Paecilomyces) are small and round with very few distinguishing characteristics. They cannot be differentiated by non-viable sampling methods. Also, some species with very small spores are easily missed, and may be undercounted. Background debris indicates the amount of non-biological particulate matter present on the trace (dust in the air) and the resulting visibility for the analyst. It is rated from 1+ (low) to 4+ (high). Counts from areas with 4+ background debris should be regarded as minimal counts and may be higher then reported. It is important to account for samples volumes when evaluating dust levels. The Limit of Detection is the product of a raw count of 1 and 100 divided by the percent read. The analytical sensitivity (counts/m3) is the product of the Limit of Detection and 1000 divided by the sample volume. A "Version" greater than 1 indicates amended data. Total Spores/m3 has been rounded to two significant figures to reflect analytical precision. TestAmerica Environmental Microbiology Laboratory, Inc. EMLab ID: , Page 2 of 3

35 Client: Aurora Industrial Hygiene, Inc. C/O: Ms. Karen Shockley Re: UCSD-Literature Building EMLab P&K 1010 N Central Avenue, Glendale, CA (866) Fax (858) Date of Sampling: Date of Receipt: Date of Report: SPORE TRAP REPORT: NON-VIABLE METHODOLOGY Location: A: A: Outdoors, near south end of bldg Comments (see below) None None Lab ID-Version : raw ct. spores/m3 raw ct. spores/m3 Alternaria Arthrinium Ascospores* 1 13 Aureobasidium Basidiospores* Bipolaris/Drechslera group Botrytis Chaetomium Cladosporium Curvularia Epicoccum Fusarium Myrothecium Nigrospora Other brown 2 27 Other colorless Penicillium/Aspergillus types Pithomyces Rusts* Smuts*, Periconia, Myxomycetes* Stachybotrys Stemphylium Torula Ulocladium Zygomycetes Background debris (1-4+) Sample volume (liters) TOTAL SPORE/m Comments: * Most of these spore types are not seen with culturable methods (Andersen sampling), although some may appear as non-sporulating fungi. Most of the basidiospores are "mushroom" spores while the rusts and smuts are plant pathogens. The spores of Aspergillus and Penicillium (and others such as Acremonium, Paecilomyces) are small and round with very few distinguishing characteristics. They cannot be differentiated by non-viable sampling methods. Also, some species with very small spores are easily missed, and may be undercounted. Background debris indicates the amount of non-biological particulate matter present on the trace (dust in the air) and the resulting visibility for the analyst. It is rated from 1+ (low) to 4+ (high). Counts from areas with 4+ background debris should be regarded as minimal counts and may be higher then reported. It is important to account for samples volumes when evaluating dust levels. The Limit of Detection is the product of a raw count of 1 and 100 divided by the percent read. The analytical sensitivity (counts/m3) is the product of the Limit of Detection and 1000 divided by the sample volume. A "Version" greater than 1 indicates amended data. Total Spores/m3 has been rounded to two significant figures to reflect analytical precision. TestAmerica Environmental Microbiology Laboratory, Inc. EMLab ID: , Page 3 of 3

36 Client: Aurora Industrial Hygiene, Inc. C/O: Ms. Karen Shockley Re: UCSD-Literature Building EMLab P&K 1150 Bayhill Drive, Suite 100, San Bruno, CA (866) Fax (650) Date of Sampling: Date of Receipt: Date of Report: CULTURABLE AIR FUNGI REPORT Location: B: Outdoors, near B: B: B: 223 main entrance Comments (see below) None None None None Lab ID-Version : raw ct. cfu*/m3 raw ct. cfu*/m3 raw ct. cfu*/m3 raw ct. cfu*/m3 Acremonium Alternaria Aspergillus flavus Aspergillus fumigatus Aspergillus nidulans Aspergillus niger Aspergillus ochraceus Aspergillus versicolor Aureobasidium Basidiomycetes Bipolaris/Drechslera group Botrytis Chaetomium Cladosporium Curvularia Epicoccum Fusarium Non-sporulating fungi Paecilomyces Penicillium Phoma Rhizopus Stachybotrys chartarum Ulocladium Yeasts 1 12 Positive Hole Sample volume (liters) TOTAL CFU*/M * cfu = colony forming units Positive hole correction chart used for all calculations Comments: Note: Interpretation is left to the company and/or persons who conducted the field work. Variation is an inherent part of biological sampling. The presence or absence of a few genera in small numbers should not be considered abnormal. NORMAL SPORE LEVELS: Indoor spore levels usually average 30 to 80% of the outdoor spore level at the time of sampling, with the same general distribution of spore types. Filtered air, air-conditioned air, or air remote from outside sources may average 5 to 15% of the outside air at the time of sampling. (These percentages are guidelines, only. A major factor is the accessibility of outdoor air. A residence with open doors and windows and heavy foot traffic may average 95% of the outdoor level while high rise office buildings with little air exchange may average 2%. Dusty interiors may exceed 100% of the outdoors to some degree, but will still mirror the outdoor distribution of spore types.) PROBLEM INTERIORS: A substantial increase of one or two spore types which are inconsistent with and non-reflective of the outside distribution of spore types is usually indicative of an indoor reservoir of mold growth. The Limit of Detection is the product of a raw count of 1 and 100 divided by the percent read. The analytical sensitivity (counts/m3) is the product of the Limit of Detection and 1000 divided by the sample volume. A "Version" greater than 1 indicates amended data. Total CFU/m3 has been rounded to two significant figures to reflect analytical precision. TestAmerica Environmental Microbiology Laboratory, Inc. EMLab ID: , Page 1 of 3

37 Client: Aurora Industrial Hygiene, Inc. C/O: Ms. Karen Shockley Re: UCSD-Literature Building EMLab P&K 1150 Bayhill Drive, Suite 100, San Bruno, CA (866) Fax (650) Date of Sampling: Date of Receipt: Date of Report: CULTURABLE AIR FUNGI REPORT Location: B: B: B: B: 427 Comments (see below) None None None None Lab ID-Version : raw ct. cfu*/m3 raw ct. cfu*/m3 raw ct. cfu*/m3 raw ct. cfu*/m3 Acremonium Alternaria Aspergillus flavus Aspergillus fumigatus Aspergillus nidulans Aspergillus niger Aspergillus ochraceus Aspergillus versicolor Aureobasidium Basidiomycetes Bipolaris/Drechslera group Botrytis Chaetomium Cladosporium Curvularia Epicoccum Fusarium Non-sporulating fungi Paecilomyces Penicillium 1 12 Phoma Rhizopus Stachybotrys chartarum Ulocladium Yeasts Positive Hole Sample volume (liters) TOTAL CFU*/M3 12 < 12 < * cfu = colony forming units Positive hole correction chart used for all calculations Comments: Note: Interpretation is left to the company and/or persons who conducted the field work. Variation is an inherent part of biological sampling. The presence or absence of a few genera in small numbers should not be considered abnormal. NORMAL SPORE LEVELS: Indoor spore levels usually average 30 to 80% of the outdoor spore level at the time of sampling, with the same general distribution of spore types. Filtered air, air-conditioned air, or air remote from outside sources may average 5 to 15% of the outside air at the time of sampling. (These percentages are guidelines, only. A major factor is the accessibility of outdoor air. A residence with open doors and windows and heavy foot traffic may average 95% of the outdoor level while high rise office buildings with little air exchange may average 2%. Dusty interiors may exceed 100% of the outdoors to some degree, but will still mirror the outdoor distribution of spore types.) PROBLEM INTERIORS: A substantial increase of one or two spore types which are inconsistent with and non-reflective of the outside distribution of spore types is usually indicative of an indoor reservoir of mold growth. The Limit of Detection is the product of a raw count of 1 and 100 divided by the percent read. The analytical sensitivity (counts/m3) is the product of the Limit of Detection and 1000 divided by the sample volume. A "Version" greater than 1 indicates amended data. Total CFU/m3 has been rounded to two significant figures to reflect analytical precision. TestAmerica Environmental Microbiology Laboratory, Inc. EMLab ID: , Page 2 of 3

38 Client: Aurora Industrial Hygiene, Inc. C/O: Ms. Karen Shockley Re: UCSD-Literature Building CULTURABLE AIR FUNGI REPORT Location: EMLab P&K 1150 Bayhill Drive, Suite 100, San Bruno, CA (866) Fax (650) Date of Sampling: Date of Receipt: Date of Report: B: 428 Comments (see below) None None B: Outdoors, near south end of bldg Lab ID-Version : raw ct. cfu*/m3 raw ct. cfu*/m3 Acremonium Alternaria Aspergillus flavus Aspergillus fumigatus Aspergillus nidulans Aspergillus niger Aspergillus ochraceus Aspergillus versicolor Aureobasidium 1 12 Basidiomycetes Bipolaris/Drechslera group Botrytis Chaetomium Cladosporium Curvularia Epicoccum Fusarium Non-sporulating fungi 1 12 Paecilomyces Penicillium Phoma Rhizopus Stachybotrys chartarum Ulocladium Yeasts Positive Hole Sample volume (liters) TOTAL CFU*/M * cfu = colony forming units Positive hole correction chart used for all calculations Comments: Note: Interpretation is left to the company and/or persons who conducted the field work. Variation is an inherent part of biological sampling. The presence or absence of a few genera in small numbers should not be considered abnormal. NORMAL SPORE LEVELS: Indoor spore levels usually average 30 to 80% of the outdoor spore level at the time of sampling, with the same general distribution of spore types. Filtered air, air-conditioned air, or air remote from outside sources may average 5 to 15% of the outside air at the time of sampling. (These percentages are guidelines, only. A major factor is the accessibility of outdoor air. A residence with open doors and windows and heavy foot traffic may average 95% of the outdoor level while high rise office buildings with little air exchange may average 2%. Dusty interiors may exceed 100% of the outdoors to some degree, but will still mirror the outdoor distribution of spore types.) PROBLEM INTERIORS: A substantial increase of one or two spore types which are inconsistent with and non-reflective of the outside distribution of spore types is usually indicative of an indoor reservoir of mold growth. The Limit of Detection is the product of a raw count of 1 and 100 divided by the percent read. The analytical sensitivity (counts/m3) is the product of the Limit of Detection and 1000 divided by the sample volume. A "Version" greater than 1 indicates amended data. Total CFU/m3 has been rounded to two significant figures to reflect analytical precision. TestAmerica Environmental Microbiology Laboratory, Inc. EMLab ID: , Page 3 of 3

39

40

41 EMLab P&K Report for: Ms. Karen Shockley Aurora Industrial Hygiene, Inc Cudahy Place Suite 120 San Diego, CA Regarding: Project: UCSD-Literature Bldg EML ID: Approved by: Dates of Analysis: Spore trap analysis: Lab Manager Malcolm Moody Project SOPs: Spore trap analysis (I100000) This coversheet is included with your report in order to comply with AIHA and ISO accreditation requirements. For clarity, we report the number of significant digits as calculated; but, due to the nature of this type of biological data, the number of significant digits that is used for interpretation should generally be one or two. All samples were received in acceptable condition unless noted in the Report Comments portion in the body of the report. Due to the nature of the analyses performed, field blank corrections of results is not a standard practice. The results relate only to the items tested. EMLab P&K ("the Company") shall have no liability to the client or the client's customer with respect to decisions or recommendations made, actions taken or courses of conduct implemented by either the client or the client's customer as a result of or based upon the Test Results. In no event shall the Company be liable to the client with respect to the Test Results except for the Company's own willful misconduct or gross negligence nor shall the Company be liable for incidental or consequential damages or lost profits or revenues to the fullest extent such liability may be disclaimed by law, even if the Company has been advised of the possibility of such damages, lost profits or lost revenues. In no event shall the Company's liability with respect to the Test Results exceed the amount paid to the Company by the client therefor. Document Number: Revision Number: 5

42 Client: Aurora Industrial Hygiene, Inc. C/O: Ms. Karen Shockley Re: UCSD-Literature Bldg SPORE TRAP REPORT: NON-VIABLE METHODOLOGY Location: : Outdoors, east of bldg : : 453 EMLab P&K 1010 N Central Avenue, Glendale, CA (866) Fax (858) Date of Sampling: Date of Receipt: Date of Report: : : 451 Comments (see below) None None None None None Lab ID-Version : raw ct. spores/m3 raw ct. spores/m3 raw ct. spores/m3 raw ct. spores/m3 raw ct. spores/m3 Alternaria 1 13 Arthrinium Ascospores* Aureobasidium Basidiospores* Bipolaris/Drechslera group Botrytis Chaetomium Cladosporium Curvularia Epicoccum Fusarium Myrothecium Nigrospora Other brown 2 27 Other colorless Penicillium/Aspergillus types 1 53 Pithomyces Rusts* Smuts*, Periconia, Myxomycetes* Stachybotrys Stemphylium Torula Trichocladium Ulocladium Zygomycetes Background debris (1-4+) Sample volume (liters) TOTAL SPORE/m Comments: * Most of these spore types are not seen with culturable methods (Andersen sampling), although some may appear as non-sporulating fungi. Most of the basidiospores are "mushroom" spores while the rusts and smuts are plant pathogens. The spores of Aspergillus and Penicillium (and others such as Acremonium, Paecilomyces) are small and round with very few distinguishing characteristics. They cannot be differentiated by non-viable sampling methods. Also, some species with very small spores are easily missed, and may be undercounted. Background debris indicates the amount of non-biological particulate matter present on the trace (dust in the air) and the resulting visibility for the analyst. It is rated from 1+ (low) to 4+ (high). Counts from areas with 4+ background debris should be regarded as minimal counts and may be higher then reported. It is important to account for samples volumes when evaluating dust levels. The Limit of Detection is the product of a raw count of 1 and 100 divided by the percent read. The analytical sensitivity (counts/m3) is the product of the Limit of Detection and 1000 divided by the sample volume. A "Version" greater than 1 indicates amended data. Total Spores/m3 has been rounded to two significant figures to reflect analytical precision. TestAmerica Environmental Microbiology Laboratory, Inc. EMLab ID: , Page 1 of 11

43 Client: Aurora Industrial Hygiene, Inc. C/O: Ms. Karen Shockley Re: UCSD-Literature Bldg EMLab P&K 1010 N Central Avenue, Glendale, CA (866) Fax (858) Date of Sampling: Date of Receipt: Date of Report: SPORE TRAP REPORT: NON-VIABLE METHODOLOGY Location: : : : : 434 Comments (see below) None None None None Lab ID-Version : raw ct. spores/m3 raw ct. spores/m3 raw ct. spores/m3 raw ct. spores/m3 Alternaria Arthrinium Ascospores* Aureobasidium Basidiospores* Bipolaris/Drechslera group Botrytis Chaetomium Cladosporium Curvularia Epicoccum Fusarium Myrothecium Nigrospora Other brown Other colorless Penicillium/Aspergillus types Pithomyces Rusts* 1 13 Smuts*, Periconia, Myxomycetes* 1 13 Stachybotrys Stemphylium Torula Trichocladium Ulocladium Zygomycetes Background debris (1-4+) Sample volume (liters) TOTAL SPORE/m < 13 Comments: * Most of these spore types are not seen with culturable methods (Andersen sampling), although some may appear as non-sporulating fungi. Most of the basidiospores are "mushroom" spores while the rusts and smuts are plant pathogens. The spores of Aspergillus and Penicillium (and others such as Acremonium, Paecilomyces) are small and round with very few distinguishing characteristics. They cannot be differentiated by non-viable sampling methods. Also, some species with very small spores are easily missed, and may be undercounted. Background debris indicates the amount of non-biological particulate matter present on the trace (dust in the air) and the resulting visibility for the analyst. It is rated from 1+ (low) to 4+ (high). Counts from areas with 4+ background debris should be regarded as minimal counts and may be higher then reported. It is important to account for samples volumes when evaluating dust levels. The Limit of Detection is the product of a raw count of 1 and 100 divided by the percent read. The analytical sensitivity (counts/m3) is the product of the Limit of Detection and 1000 divided by the sample volume. A "Version" greater than 1 indicates amended data. Total Spores/m3 has been rounded to two significant figures to reflect analytical precision. TestAmerica Environmental Microbiology Laboratory, Inc. EMLab ID: , Page 2 of 11

44 Client: Aurora Industrial Hygiene, Inc. C/O: Ms. Karen Shockley Re: UCSD-Literature Bldg EMLab P&K 1010 N Central Avenue, Glendale, CA (866) Fax (858) Date of Sampling: Date of Receipt: Date of Report: SPORE TRAP REPORT: NON-VIABLE METHODOLOGY Location: : : : : 354 Comments (see below) None None None None Lab ID-Version : raw ct. spores/m3 raw ct. spores/m3 raw ct. spores/m3 raw ct. spores/m3 Alternaria 1 13 Arthrinium Ascospores* Aureobasidium Basidiospores* 3 40 Bipolaris/Drechslera group Botrytis Chaetomium Cladosporium Curvularia Epicoccum Fusarium Myrothecium Nigrospora Other brown 1 13 Other colorless Penicillium/Aspergillus types 1 53 Pithomyces Rusts* Smuts*, Periconia, Myxomycetes* 1 13 Stachybotrys Stemphylium Torula Trichocladium Ulocladium Zygomycetes Background debris (1-4+) Sample volume (liters) TOTAL SPORE/m < Comments: * Most of these spore types are not seen with culturable methods (Andersen sampling), although some may appear as non-sporulating fungi. Most of the basidiospores are "mushroom" spores while the rusts and smuts are plant pathogens. The spores of Aspergillus and Penicillium (and others such as Acremonium, Paecilomyces) are small and round with very few distinguishing characteristics. They cannot be differentiated by non-viable sampling methods. Also, some species with very small spores are easily missed, and may be undercounted. Background debris indicates the amount of non-biological particulate matter present on the trace (dust in the air) and the resulting visibility for the analyst. It is rated from 1+ (low) to 4+ (high). Counts from areas with 4+ background debris should be regarded as minimal counts and may be higher then reported. It is important to account for samples volumes when evaluating dust levels. The Limit of Detection is the product of a raw count of 1 and 100 divided by the percent read. The analytical sensitivity (counts/m3) is the product of the Limit of Detection and 1000 divided by the sample volume. A "Version" greater than 1 indicates amended data. Total Spores/m3 has been rounded to two significant figures to reflect analytical precision. TestAmerica Environmental Microbiology Laboratory, Inc. EMLab ID: , Page 3 of 11

Indiana University Environmental Health & Safety Beau Middaugh 2427 E. 2nd street Bloomington, IN USA (812)

Indiana University Environmental Health & Safety Beau Middaugh 2427 E. 2nd street Bloomington, IN USA (812) Indiana University Environmental Health & Safety Beau Middaugh 2427 E. 2nd street Bloomington, IN 47401 USA (812) 855-6316 Approved by: Dates of Analysis: MoldReport Spore trap: 12-19-2018 Technical Manager

More information

A Healthy Home, LLC West Center Dr. Lakewood, CO

A Healthy Home, LLC West Center Dr. Lakewood, CO Mold Inspection and Testing Summary A Healthy Home, LLC 13520 West Center Dr. Lakewood, CO. 80228 303-989-6809 Robert Boyd, is certified by the American Council of Accredited Certification (ACAC), as a

More information

AIRBORNE MOLD SPORE ANALYSIS

AIRBORNE MOLD SPORE ANALYSIS 11080 SW Allen Blvd, Suite, Beaverton, OR 97005 P: 503.292.5346 F: 503.203.1516 Tuesday, May 23, 2017 Ken Studnick Address: 38875 N 1st Ave, Scio, OR 97374 Projects 17-16079 and 16-14152 Dear Ken: SUMMARY

More information

Environmental Assessment, Timothy Dwight Elementary School 1600 Redding Road, Fairfield, Connecticut

Environmental Assessment, Timothy Dwight Elementary School 1600 Redding Road, Fairfield, Connecticut COMMITMENT & INTEGRITY DRIVE RESULTS 40 Shattuck Road Suite 110 Andover, Massachusetts 01810 www.woodardcurran.com T 866.702.6371 T 978.557.8150 F 978.557.7948 Via Electronic Mail November 6, 2018 Thomas

More information

No visible mold or water intrusion/damage was found on the day of testing.

No visible mold or water intrusion/damage was found on the day of testing. January th, 0 Mr. Marty Foutch Facilities Director Bixby Public Schools 9 N. Armstrong Bixby, OK 008 CC: RE: Jarred Doubrava Operations Support Manager/District Safety Coordinator Bixby Northeast Elementary

More information

Indiana University Environmental Health & Safety Beau Middaugh 2427 E. 2nd street Bloomington, IN USA (812)

Indiana University Environmental Health & Safety Beau Middaugh 2427 E. 2nd street Bloomington, IN USA (812) Indiana University Environmental Health & Safety Beau Middaugh 2427 E. 2nd street Bloomington, IN 47401 USA (812) 855-6316 Approved by: Dates of Analysis: MoldReport Spore trap: 11-08-2018 Technical Manager

More information

Analysis Report prepared for Quest Air

Analysis Report prepared for Quest Air contact@hayesmicrobial.com http://hayesmicrobial.com/ Analysis Report prepared for 103 Carnegie Center Suite 300 Princeton, NJ. 08540 Job Name: 76 Federal City Road Date Sampled: 05-30-2017 Date Analyzed:

More information

MOLD INSPECTION REPORT

MOLD INSPECTION REPORT MOLD INSPECTION REPORT Conducted at: 407 Canyon East Conducted for: Town of Taos Prepared By: Gary O leary Klean Force Project Number: #21054 Inspection Date: 02/04/2015 Report Date: 02/13/2015 915-474-0299

More information

RLB CIH, LLC. Final Report Microbial Contamination Sampling Taos Recreation Center Taos, New Mexico. March 9, 2007

RLB CIH, LLC. Final Report Microbial Contamination Sampling Taos Recreation Center Taos, New Mexico. March 9, 2007 Final Report Microbial Contamination Sampling Taos Recreation Center Taos, New Mexico RLB CIH, LLC Ronald L. Beethe, CIH 505-268-5829 400 Alvarado NE FAX 256-9554 Albuquerque, NM 87108 rlbcih@comcast.net

More information

Mastertech North Jersey

Mastertech North Jersey contact@hayesmicrobial.com http://hayesmicrobial.com/ Analysis Report prepared for Mastertech North Jersey Mount Arlington, NJ. 07856 Phone: (973) 346-650 I 18 MT1 Job Name: Indiana 18 Date Sampled: 03-09-018

More information

FUNGAL (MOLD) TESTING RESULT REPORT* Cover Page

FUNGAL (MOLD) TESTING RESULT REPORT* Cover Page FUNGAL (MOLD) TESTING RESULT REPORT* Cover Page RESULT TABLES ANALYTICAL REPORT (Spore trap report) MOLD BRIEF DESCRIPTIONS (In a separate file) Verified By: Wei Cohen, B.S. Approved By: Jian (Young) Bao,

More information

Indiana University Environmental Health & Safety Beau Middaugh 2427 E. 2nd street Bloomington, IN USA (812)

Indiana University Environmental Health & Safety Beau Middaugh 2427 E. 2nd street Bloomington, IN USA (812) Indiana University Environmental Health & Safety Beau Middaugh 2427 E. 2nd street Bloomington, IN 47401 USA (812) 855-6316 Approved by: Dates of Analysis: MoldReport Spore trap: 10-31-2018 and 10-31-2018

More information

RE: Total Airborne Mould Spore Sampling Brookside Junior High 2239 Prospect Road, Hatchet Lake, NS

RE: Total Airborne Mould Spore Sampling Brookside Junior High 2239 Prospect Road, Hatchet Lake, NS 20 Duke Street, Suite 109 Tel: (902) 835-3727 Bedford, Nova Scotia Fax: (902) 835-5266 B4A 2Z5 Email: email@toalltech.com September 9 th, 2015 Tom Drury Assistant Regional Manager Operations Services Halifax

More information

March 01, Re: Mold Sampling. Dear Mr. Jon Lewis,

March 01, Re: Mold Sampling. Dear Mr. Jon Lewis, 1990 S. Garrison St. Suite 6 Lakewood, CO 80227 Office 303-980-4401 Fax 303-980-4402 March 01, 2013 Re: Mold Sampling Dear Mr. Jon Lewis, Aspen Environmental, Inc. representatives completed the mold air

More information

1251 Weatherstone Ct. Reston,VA Mold Reduction Report

1251 Weatherstone Ct. Reston,VA Mold Reduction Report GreenClean Air Weatherstone Ct. Reston,VA 094 70.97.7 Steve@GreenCleanAir.com Mold Reduction Report November, 0 Rodney Fugitt Strategic Property Systems 077 Alyssia Lane Waldorf, MD 060 Re: 90 Messina

More information

AIRBORNE FUNGAL STRUCTURE SAMPLE ANALYSIS Results reported as Structures per Cubic Meter of Air (structures/m 3 )

AIRBORNE FUNGAL STRUCTURE SAMPLE ANALYSIS Results reported as Structures per Cubic Meter of Air (structures/m 3 ) Field #: TM042709 Project #: 141186 Description: Background, Outside, Main Lab #: 1504110 Entrance Eagle #: E15042809 Results reported as per Cubic Meter of Air Structure Identification ascospores (undifferentiated)

More information

M. A. CECIL & ASSOCIATES, INC Shannon Way, Port Republic, Maryland (301) INDUSTRIAL HYGIENE AND ENVIRONMENTAL HEALTH

M. A. CECIL & ASSOCIATES, INC Shannon Way, Port Republic, Maryland (301) INDUSTRIAL HYGIENE AND ENVIRONMENTAL HEALTH M. A. CECIL & ASSOCIATES, INC. 4475 Shannon Way, Port Republic, Maryland 20676 (301) 855-7710 INDUSTRIAL HYGIENE AND ENVIRONMENTAL HEALTH October 17, 2013 Mr. Sean Yarup Montgomery County Public Schools

More information

Certificate of Mold Analysis (941) (941) SAMPLE REPORT

Certificate of Mold Analysis (941) (941) SAMPLE REPORT BUILDING INSPECTION OF FLORIDA PO BOX 380955 MURDOCK, FL 33938 Certificate of Mold Analysis Prepared for: Phone Number: Fax Number: BUILDING INSPECTION OF FLORIDA (941)743-3164 (941)743-4236 Currently

More information

Indoor Air Quality Testing. Horry County Schools

Indoor Air Quality Testing. Horry County Schools ! Report of: Indoor Air Quality Testing Horry y Schools Conway, SC Palme5o EHS Report No: 2018376 Submi5ed Prepared for: Horry y Schools Prepared By: Palme5o EHS, LLC 100 Old Cherokee Rd. Suite F, Box

More information

Air Sampling and Analysis for Mold in Hills Building UMass

Air Sampling and Analysis for Mold in Hills Building UMass Air Sampling and Analysis for Mold in Hills Building UMass Christine Rogers, PhD Environmental Health Science SPHHS First Floor Hills North Introduction Upon request, all of the rooms on the first floor

More information

Regulatory Compliance 245 Albany Avenue Thornwood, New York (914) Indoor Air Quality Screening At. Scarsdale UFSD

Regulatory Compliance 245 Albany Avenue Thornwood, New York (914) Indoor Air Quality Screening At. Scarsdale UFSD Regulatory Compliance 245 Albany Avenue Thornwood, New York 10594 (914) 439-6513 Indoor Air Quality Screening At DRAFT Scarsdale UFSD High School 1057 East post Road Scarsdale, NY 10583 Various Rooms RegCom

More information

EMLab P&K MOLD REPORT Mr. Quality Control 1150 Bayhill Drive Suite 100 San Bruno, CA USA (650)

EMLab P&K MOLD REPORT Mr. Quality Control 1150 Bayhill Drive Suite 100 San Bruno, CA USA (650) EMLab P&K MOLD REPORT Mr. Quality Control 1150 Bayhill Drive Suite 100 San Bruno, CA 94066 USA (650) 829-5800 Approved by: Dates of Analysis: MoldReport Spore trap: 05-22-2014 Technical Manager Murali

More information

Legally Defensible Strategies for Mold Investigations

Legally Defensible Strategies for Mold Investigations Legally Defensible Strategies for Mold Investigations Metro New York AIHA Bull Moose Meeting September 10, 2014 Jack Springston, CIH, CSP TRC Environmental, Inc. www.trcsolutions.com Disclaimer The contents

More information

Certificate of Mold Analysis

Certificate of Mold Analysis HEARTLAND INSPECTIONS 3515 HUMBOLDT AVE SO MINNEAPOLIS, MN 55408 Certificate of Mold Analysis Prepared for: HEARTLAND INSPECTIONS Phone Number: (612) 860-4578 Fax Number: Project Name: CORRIGAN Test Location:

More information

Certificate of Mold Analysis

Certificate of Mold Analysis BULLSEYE INSPECTION 1802 INGRAM AVE SARASOTA, FL 34232 Certificate of Mold Analysis Prepared for: BULLSEYE INSPECTION Phone Number: (941)341-0577 Fax Number: (941)341-0577 Project Name: SARASOTA, FL 34238

More information

Certificate of Mold Analysis

Certificate of Mold Analysis COASTAL ENVIRONMENTAL PO BOX 167 HAMMONTON, NJ 08330 Certificate of Analysis Prepared for: COASTAL ENVIRONMENTAL Phone Number: (609) 820-9312 Fax Number: (609) 561-6197 Project Name: Test Location: NORTH

More information

Certificate of Mold Analysis

Certificate of Mold Analysis WILCOX INSPECTIONS Certificate of Mold Analysis Prepared for: Phone Number: Fax Number: Project Name: Test Location: WILCOX INSPECTIONS Chain of Custody #: Received Date: September 4, 2015 Report Date:

More information

AGENDA REQUEST. November 7, 2016

AGENDA REQUEST. November 7, 2016 AGENDA HEADING: Unfinished Business AGENDA REQUEST COMMISSION MEETING DATE: November 7, 2016 AGENDA ITEM NO: BY City Auditor and Clerk Pamela M. Nadalini Tonya Erbland, CIAQP, Senior Environmental Scientist,

More information

Certificate of Mold Analysis

Certificate of Mold Analysis COASTAL ENVIRONMENTAL PO BOX 167 HAMMONTON, NJ 08330 Certificate of Mold Analysis Prepared for: COASTAL ENVIRONMENTAL Phone Number: (609) 820-9312 Fax Number: (609) 561-6197 Project Name: LEEDS CLEARANCE

More information

Certificate of Mold Analysis

Certificate of Mold Analysis CHICAGO INSPECTION AGENCY 815 N SCHOOL ST PROSPECT HEIGHTS, IL 60070 Certificate of Mold Analysis Prepared for: CHICAGO INSPECTION AGENCY Phone Number: (847) 459-9387 Fax Number: (847) 459-9443 Project

More information

January 31, Mr. Mark LaFleur Director of Plant Operations Town of Needham 1330 Highland Avenue Needham, MA 02492

January 31, Mr. Mark LaFleur Director of Plant Operations Town of Needham 1330 Highland Avenue Needham, MA 02492 OccuHealth, Inc. 44 Wood Avenue Mansfield, MA 02048 Occupational Health & Safety, Environmental Consultants Tel. (508) 9-9119 Tel. (800) 729-105 Fax (508) 9-289 thamilton@occuhealth.com January 1, 2007

More information

DATE: September 15, TO: Sarah Johnston, Director

DATE: September 15, TO: Sarah Johnston, Director DATE: September 15, 2015 TO: Sarah Johnston, Director SUBJECT: Purnell Service Center - IAQ - Air Test - Room 105, 4 Director's offices & Secretary office area. On Saturday 9/12, I received an E-mail from

More information

Airborne Mould Sampling Moncton High School 207 Church Street Moncton, NB E1C 5A3. November 01, 2013

Airborne Mould Sampling Moncton High School 207 Church Street Moncton, NB E1C 5A3. November 01, 2013 Project # 18578 Airborne Mould Sampling Moncton High School 207 Church Street Moncton, NB E1C 5A3 November 01, 2013 Attention: Serge Melanson Transportation and Infrastructure Facilities Management Moncton

More information

Tape Lift and Swab Sampling of Items found at Glenwood Middle School Project #J15-876

Tape Lift and Swab Sampling of Items found at Glenwood Middle School Project #J15-876 October 21, 2015 Mr. Jeff Klenk Howard County Public School System 10910 Route 108 Ellicott City, MD 21043 RE: Tape Lift and Swab Sampling of Items found at Glenwood Middle School Project #J15-876 Dear

More information

DATE: May 23, TO: Tommy Ellington, Executive Director

DATE: May 23, TO: Tommy Ellington, Executive Director DATE: May 23, 2016 TO: Tommy Ellington, Executive Director SUBJECT: SSAB- IAQ - Initial Contact - Sherah Robinson's office, Cinnamon Dilts' office and Storeroom SE corner On Wednesday 5/18, I received

More information

EXPANDED FUNGAL REPORT

EXPANDED FUNGAL REPORT EXPANDED FUNGAL REPORT Prepared Exclusively For Report Date: 11/29/2007 Project: Accceditation"This report was generated in the EMSL Test Lab Page 1 of 23 1. Description of Analysis Analytical Laboratory

More information

FUNGAL PARTICULATE AIR SAMPLING

FUNGAL PARTICULATE AIR SAMPLING November 19, 2016 Chuck Doan Yakima School District #7 104 N 4th Avenue Yakima, WA 98902 Via email: Regarding: doan.chuck@yakimaschools.org Fungal Sample Results Blue Wall Room 509 and Room 617 Eisenhower

More information

Certificate of Mold Analysis

Certificate of Mold Analysis CHICAGO INSPECTION AGENCY 815 N SCHOOL ST PROSPECT HEIGHTS, IL 60070 Certificate of Mold Analysis Prepared for: CHICAGO INSPECTION AGENCY Phone Number: (847)459-9387 Fax Number: (847)459-9443 Project Name:

More information

Certificate of Mold Analysis

Certificate of Mold Analysis COASTAL ENVIRONMENTAL PO BOX 167 HAMMONTON, NJ 08330 Certificate of Mold Analysis Prepared for: COASTAL ENVIRONMENTAL Phone Number: (609) 820-9312 Fax Number: (609) 561-6197 Project Name: PVIL MIDDLE SCHOOL

More information

Certificate of Mold Analysis

Certificate of Mold Analysis PRISTINE HOME INSPECTIONS 1817 S NEIL #104-2 CHAMPAIGN, IL 61820 Certificate of Mold Analysis Prepared for: PRISTINE HOME INSPECTIONS Phone Number: (217) 722-5883 Fax Number: (217) 2-9851 Project Name:

More information

Certificate of Mold Analysis

Certificate of Mold Analysis ACE ENVIRONMENTAL 49 SHADOWCREEK WAY ORMOND BEACH, FL 32174 Certificate of Mold Analysis Prepared for: ACE ENVIRONMENTAL Phone Number: (904) 859-9211 Fax Number: Project Name: PINNAMENENI Test Location:

More information

C e r t i f i c a te o f m o ld Ana l y s i s

C e r t i f i c a te o f m o ld Ana l y s i s 3 3 0 1 N.W. 5 5 th S t., F t. Lauderdale, FL 3 3 3 0 9 ( 8 8 8 ) 8 5 4-0 4 7 7 C e r t i f i c a te o f m o ld Ana l y s i s P R E PARED F O R : TLC Home Inspections Phone Number: (512) 900-2191 Email:

More information

Certificate of Mold Analysis

Certificate of Mold Analysis COASTAL ENVIRONMENTAL PO BOX 167 HAMMONTON, NJ 08330 Certificate of Mold Analysis Prepared for: COASTAL ENVIRONMENTAL Phone Number: (609) 820-9312 Fax Number: (609) 561-6197 Project Name: SOUTH MAIN CLEAR

More information

Mold Technologies Mr. Dennis Ragain 3491 Wildwood Ct. NW Salem, OR USA

Mold Technologies Mr. Dennis Ragain 3491 Wildwood Ct. NW Salem, OR USA Mold Technologies Mr. Dennis Ragain 3491 Wildwood Ct. NW Salem, OR 97304 USA Page 1 of 18 Table of Contents Thank you for choosing MoldREPORT from Our mission is to provide industry leadership for the

More information

Certificate of Mold Analysis

Certificate of Mold Analysis ACE ENVIRONMENTAL 49 SHADOWCREEK WAY ORMOND BEACH, FL 32174 Certificate of Mold Analysis Prepared for: ACE ENVIRONMENTAL Phone Number: (904) 859-9211 Fax Number: Project Name: NIA NETANE Test Location:

More information

EMLab P&K MOLD REPORT Mr. Quality Control 1150 Bayhill Drive Suite 100 San Bruno, CA USA (650)

EMLab P&K MOLD REPORT Mr. Quality Control 1150 Bayhill Drive Suite 100 San Bruno, CA USA (650) EMLab P&K MOLD REPORT Mr. Quality Control 1150 Bayhill Drive Suite 100 San Bruno, CA 94066 USA (650) 829-5800 Approved by: Dates of Analysis: MoldReport Direct exam: 05-22-2014 Technical Manager Murali

More information

Based on our review, the following primary chemical constituents were identified for sampling: Acetone Toluene Xylenes Heptane

Based on our review, the following primary chemical constituents were identified for sampling: Acetone Toluene Xylenes Heptane December 15, 2017 Mr. Jeremy McDevitt Kenston Local Schools 1719 Snyder Road Chagrin Falls, Ohio 44022 RE: Indoor Air Quality Evaluation Kenston Middle School, 17425 Snyder Road, Kenston, Ohio OH41465

More information

AladdinEnvironmentalLLC

AladdinEnvironmentalLLC "" 1 AladdinEnvironmentalLLC 321 W. Josephine * San Antonio. TX 78212 * 2107361826x218 * Fax 2107323667 Texas Mold Assessment Consultant MAC0383 June 16,2008 San Antonio Housing Authority Attn: Bart Swider,

More information

Certificate of Mold Analysis

Certificate of Mold Analysis Certificate of Mold Analysis Prepared for: Phone Number: Fax Number: Project Name: Test Location: TEXINSPEC Chain of Custody #: Received Date: November 6, 2018 Report Date: November 6, 2018 Elena Santiago,

More information

Certificate of Mold Analysis

Certificate of Mold Analysis ACE ENVIRONMENTAL 49 SHADOWCREEK WAY ORMOND BEACH, FL 32174 Certificate of Mold Analysis Prepared for: ACE ENVIRONMENTAL Phone Number: (904) 859-9211 Fax Number: Project Name: TOM HARTSFIELD Test Location:

More information

INDOOR AIR QUALITY CLEARANCE SAMPLING

INDOOR AIR QUALITY CLEARANCE SAMPLING 5 Route, Suite C4 Brewster, NY 0509 845.78.770 90 State Street, Suite 700 Albany, NY 07 58.874.067 967 Wehrle Drive, Suite One Buffalo, NY 4 76..4580 E-mail: adelaidemail@adelaidellc.com Fax: 845.78.7750

More information

Certificate of Mold Analysis

Certificate of Mold Analysis Tri-State Smart Home Solutions LLC CHRIS FARVER GALLIPOLIS, OH 45631 Certificate of Analysis Prepared for: CHRIS FARVER Phone Number: (74) 28-3966 Fax Number: Project Name: Test Location: Address City,

More information

Certificate of Mold Analysis

Certificate of Mold Analysis COASTAL ENVIRONMENTAL PO BOX 167 HAMMONTON, NJ 08330 Certificate of Mold Analysis Prepared for: COASTAL ENVIRONMENTAL Phone Number: Fax Number: Project Name: DECANTOR AVE SCHOOL Test Location:, Chain of

More information

MYCOLOGY REPORT. Report: / 3503 Wgaon Wheel, Wichita Falls, TX

MYCOLOGY REPORT. Report: / 3503 Wgaon Wheel, Wichita Falls, TX MYCOLOGY REPORT Date: May 28, 15 Flint Inspection Consulting Services, Inc. Report: 6315-1694 15-036 / 3503 Wgaon Wheel, Wichita Falls, TX This document shall be considered a duly signed original report

More information

CERTIFICATE OF MOLD ANALYSIS

CERTIFICATE OF MOLD ANALYSIS CERTIFICATE OF MOLD ANALYSIS PREPARED FOR: Doc Shane Test Client Account Phone Number: (888) 854-0478 Email: docshane@inspectorlab.com Test Location: Max Headroom 1234 John Muir Street Hayward, CA 94544

More information

Airborne Mould Sampling Moncton High School 207 Church Street Moncton, NB E1C 5A3. November 25, 2013

Airborne Mould Sampling Moncton High School 207 Church Street Moncton, NB E1C 5A3. November 25, 2013 Project # 18578 Airborne Mould Sampling Moncton High School 207 Church Street Moncton, NB E1C 5A3 November 25, 2013 Attention: Serge Melanson Transportation and Infrastructure Facilities Management Moncton

More information

DATE: February 14, TO: Amy Acosta, Principal

DATE: February 14, TO: Amy Acosta, Principal DATE: February 14, 2017 TO: Amy Acosta, Principal SUBJECT: Timber Creek ES - IAQ - Initial Contact - Media Room, Hallway between Principal Office & Library and Library On Friday 2/10, I received W.O. #403088:

More information

DATE: September 12, TO: Curtis Martin, Principal. SUBJECT: Tom Hicks ES - IAQ - Air Test Results - Nurses' Office, Main Admin Office

DATE: September 12, TO: Curtis Martin, Principal. SUBJECT: Tom Hicks ES - IAQ - Air Test Results - Nurses' Office, Main Admin Office DATE: September 12, 2017 TO: Curtis Martin, Principal SUBJECT: Tom Hicks ES - IAQ - Air Test Results - Nurses' Office, Main Admin Office On Tuesday 9/5, Apex-Titan Air tested the Nurses Office and the

More information

SUBJECT: Administration Building - IAQ - Initial Contact report - Room 217, Hallway outside Room 217, Room 201, Room 225, Room 212

SUBJECT: Administration Building - IAQ - Initial Contact report - Room 217, Hallway outside Room 217, Room 201, Room 225, Room 212 DATE: February 15, 2016 TO: Sandi Maddox, Director SUBJECT: Administration Building - IAQ - Initial Contact report - Room 217, Hallway outside Room 217, Room 201, Room 225, Room 212 I received Work Order

More information

CONCENTRATIONS OF VIABLE FUNGAL SPORES ON PAPER DOCUMENTS

CONCENTRATIONS OF VIABLE FUNGAL SPORES ON PAPER DOCUMENTS 1 INTRODUCTION CONCENTRATIONS OF VIABLE FUNGAL SPORES ON PAPER DOCUMENTS This work was performed as part of a broader Indoor Air Quality (IAQ) response action, which lasted in excess of eight months. A

More information

Regulatory Compliance 245 Albany Avenue Thornwood, New York (914) Indoor Air Quality Screening At. Scarsdale UFSD

Regulatory Compliance 245 Albany Avenue Thornwood, New York (914) Indoor Air Quality Screening At. Scarsdale UFSD Regulatory Compliance 245 Albany Avenue Thornwood, New York 10594 (914) 439-6513 Indoor Air Quality Screening At Scarsdale UFSD Greenacres School 41 Huntington Avenue Scarsdale, NY 10583 RegCom s Project

More information

SanAir Technologies Laboratory. Analysis Report. Hudson Valley Property Inspections, LLC

SanAir Technologies Laboratory. Analysis Report. Hudson Valley Property Inspections, LLC SanAir Technologies Laboratory Analysis Report prepared for Hudson Valley Property Inspections, LLC 8/3/2011 SanAir ID#: 804.897.1177 www.sanair.com August 3, 2011 SanAir ID # Dear Kevin Michaels, We at

More information

Certificate of Mold Analysis

Certificate of Mold Analysis HOLMES INSPECTION COMPANY PO BOX 12787 SHAWNEE MISSION, KS 66282 Certificate of Mold Analysis Prepared for: HOLMES INSPECTION COMPANY Phone Number: (816) 455-8787 Fax Number: (267) 222-7185 Project Name:

More information

test address: P R E PAR E D F OR : CalPro Inspection Group Phone Number: (800)

test address: P R E PAR E D F OR : CalPro Inspection Group Phone Number: (800) 3 3 0 1 N.W. 5 5 th S t., F t. Lauderdale, FL 3 3 3 0 9 ( 8 8 8 ) 8 5 4-0 4 7 7 prepared for: test address: CalPro Inspection Group 1234 Any Name St. Sacrameto, Ca 95835 C e r t i f i c a t e o f m o l

More information

Introduction: PCR Air Sampling: November 12, Carrie E Tompkins Elementary School PCR Fungi Study:

Introduction: PCR Air Sampling: November 12, Carrie E Tompkins Elementary School PCR Fungi Study: 23 STATE STREET OSSINING, NEW YORK 10562 TEL.: (914) 762-6333 FAX: (914) 762-5578 W W W. E M S O F N Y. C O M November 12, 2014 Environmental Science Safety Engineering Industrial Hygiene Environmental

More information

C E R T I F I C A T E O F M O L D A N A L Y S I S

C E R T I F I C A T E O F M O L D A N A L Y S I S C E R T I F I C A T E O F M O L D A N A L Y S I S PREPARED FOR: A Plus Inspections of Texas Phone Number: (713) 249-2618 Email: paul@inspec4.net Test Location: Phil Homebuyer 123 Mold City Dr Houston,

More information

Certificate of Mold Analysis

Certificate of Mold Analysis ACE ENVIRONMENTAL 300 BELLA HARBOR CT #111 PALM COAST, FL 32137 Certificate of Mold Analysis Prepared for: ACE ENVIRONMENTAL Phone Number: (904) 859-9211 Fax Number: Project Name: Test Location: 1745 WINDSONG

More information

IAQ & MOLD AIR SAMPLING REPORT

IAQ & MOLD AIR SAMPLING REPORT IAQ & MOLD AIR SAMPLING REPORT LINCOLNSHIRE-PRAIRIE VIEW SCHOOL DISTRICT #103 Project Location: HALF DAY SCHOOL 239 Olde Half Day Road Testing Dates: January 10 17, 2018 MEC PROJECT #: 17-12-968-I.H. EXECUTIVE

More information

C e r t i f i c a t e o f m o l d A n a l y s i s

C e r t i f i c a t e o f m o l d A n a l y s i s 3 3 0 1 N.W. 5 5 t h S t., F t. L a u d e r d a l e, F L 3 3 3 0 9 3301 N.W. 55th St., Ft. Lauderdale, ( 8 0 0 ) 5FL 4 433309-8 1 5 6888-854-0477 C e r t i f i c a t e o f m o l d A n a l y s i s P R E

More information

NYS Mold Assessor License #00742

NYS Mold Assessor License #00742 Client Information: Name: John Doe Address: 90 Fake Road, Malta, NY Phone: 518-555-5555 Time of Assessment: 530PM Date of Assessment: 8/23/17 Date of Report: 8/24/17, 7/26/17-Rev1 NYS Mold Assessor License

More information

CITY OF FORT PIERCE HOUSING REHABILATION PROJECT FOR 2802 AVENUE I BID NO ADDENDUM NO. 4

CITY OF FORT PIERCE HOUSING REHABILATION PROJECT FOR 2802 AVENUE I BID NO ADDENDUM NO. 4 March 10, 2015 CITY OF FORT PIERCE HOUSING REHABILATION PROJECT FOR 2802 AVENUE I BID NO. 2015-022 ADDENDUM NO. 4 The purpose of this addendum is to extend the bid due date from 3:00PM, Tuesday, March

More information

STC Environmental Services Inc. Environmental Scientists and Engineers

STC Environmental Services Inc. Environmental Scientists and Engineers Environmental Services Inc. Environmental Scientists and Engineers 4754 RESEARCH DRIVE SAN ANTONIO, TEXAS 78240 Office (210) 69tHi286/ FAX (210) 696-8761 May 3, 2007 Mr. Henry A. Alvarez III SAHA 818 S.

More information

Joseph T. Burkeson. Tuesday, November 19th, Total Professional Installation 1293 N. 60th St Tampa Fl, 33619

Joseph T. Burkeson. Tuesday, November 19th, Total Professional Installation 1293 N. 60th St Tampa Fl, 33619 Tuesday, November 19th, 2013 Total Professional Installation 1293 N. 60th St Tampa Fl, 33619 Mold Sample Survey 37612 Oak Terrace, St Petersburg, FL 33703 On Friday, November 15th, 2013 I performed a Mold

More information

DATE: April 21, TO: Lisa Moore, Executive Director

DATE: April 21, TO: Lisa Moore, Executive Director DATE: April 21, 2017 TO: Lisa Moore, Executive Director SUBJECT: Bolin - IAQ - Results report - Payroll - Moore Office - Dragisic Office - Large Room, Storage Room, Copy Room On Tuesday 4/4 and Friday

More information

Occupational Health & Safety, Environmental Consultants Tel. (508) Tel. (800) Fax (508)

Occupational Health & Safety, Environmental Consultants Tel. (508) Tel. (800) Fax (508) OccuHealth, Inc. 44 Wood Avenue Mansfield, MA 02048 Occupational Health & Safety, Environmental Consultants Tel. (508) 339-9119 Tel. (800) 729-1035 Fax (508) 339-2893 t_hamilton@occuhealth.com December

More information

Certificate of Analysis

Certificate of Analysis YOUR GREAT COMPANY 1234 ANY STREET CHICAGO, IL 60616 Certificate of Analysis Prepared for: YOUR GREAT COMPANY Phone Number: (888) 765-4321 Fax Number: (888) 123-4567 Email Address: your_email@email.com

More information

Certificate of Analysis

Certificate of Analysis YOUR GREAT COMPANY 1234 ANY STREET CHICAGO, IL 60616 Certificate of Analysis Prepared for: YOUR GREAT COMPANY Phone Number: (888) 765-4321 Fax Number: (888) 123-4567 Email Address: your_email@email.com

More information

Cer tif ica te of mold Anal y sis

Cer tif ica te of mold Anal y sis 3301 N.W. 55th S t., Ft. Lauderdale, FL 3 3 3 0 9 ( 8 0 0 ) 5 4 4-8 1 5 6 Cer tif ica te of mold Anal y sis P REPARED FOR : Professional Home Inspections Phone Number: (423) 306-0508 Email: kc@prohitn.com

More information

Analysis Report prepared for Mold-Spec

Analysis Report prepared for Mold-Spec contact@hayesmicrobial.com http://hayesmicrobial.com/ Analysis Report prepared for Ormond Beach, FL. 3173 Date Sampled: 03-06-018 Date Analyzed: 03-08-018 Report Date: 03-08-018 EPA Laboratory ID# VA01419

More information

Certificate of Mold Analysis

Certificate of Mold Analysis INDOOR AIR QUALITY CORPORATION 1675 N COMMERCE PKWY WESTON, FL 33326 Certificate of Mold Analysis Prepared for: INDOOR AIR QUALITY CORPORATION Phone Number: (407) 463-8666 Fax Number: (954) 332-1005 Project

More information

MSES consultants, inc.

MSES consultants, inc. MSES consultants, inc. 609 West Main Street P.O. Drawer 190 Clarksburg, WV 26302-0190 304.624.9700 304.622.0981 304.842.3325 http://www.msesinc.com Office December 30, 2013 Project Number: 13-441 Mr. Joe

More information

PRO-TEC MOLD REPORT. Mold Evaluation

PRO-TEC MOLD REPORT. Mold Evaluation PRO-TEC MOLD REPORT CLIENT & SITE INFORMATION: DATE OF INSPECTION: 09/17/20. CLIENT NAME:. NUMBER & STREET: CITY/STATE/ZIP: Reston VA 20191. INSPECTED BY: Rob Hopkin. CLIMATIC CONDITIONS: WEATHER: Clear.

More information

STC Environmental Services Inc. Environmental Scientists and Engineers

STC Environmental Services Inc. Environmental Scientists and Engineers Environmental Services nc. Environmental Scientists and Engineers 4754 RESEARCH DRVE SAN ANTONO, TEXAS 78240 Office (210) 69(Hi286/ FAX (210) 696-8761 May 3, 2007 Mr. Henry A. Alvarez SAHA 818 S. Flores

More information

Certificate of Analysis

Certificate of Analysis YOUR GREAT COMPANY 1234 ANY STREET CHICAGO, IL 60616 Certificate of Analysis Prepared for: YOUR GREAT COMPANY Phone Number: (888) 765-4321 Fax Number: (888) 123-4567 Email Address: your_email@email.com

More information

MSES consultants, inc.

MSES consultants, inc. MSES consultants, inc. 609 West Main Street P.O. Drawer 190 Clarksburg, WV 26302-0190 304.624.9700 304.622.0981 304.842.3325 http://www.msesinc.com Office December 5, 2013 Project Number: 13-441 Mr. Joe

More information

Submitted By: test test Submittal Date: 2/2/2017 1:47:53 PM Sample Date: 2/1/2017 Lab Job No.: Page 1 1

Submitted By: test test Submittal Date: 2/2/2017 1:47:53 PM Sample Date: 2/1/2017 Lab Job No.: Page 1 1 CLIENT INFORMATION Moldlab 2501 Mayes Road Suite #110 Project No.: 555 PROJECT INFORMATION John Smith 123 North Street This test report contains the following sections: Chain of Custody, Report (and optionally

More information

MSES consultants, inc.

MSES consultants, inc. MSES consultants, inc. 609 West Main Street P.O. Drawer 190 Clarksburg, WV 26302-0190 304.624.9700 304.622.0981 304.842.3325 http://www.msesinc.com Office September 13, 2012 Project Number: 12-437 Mr.

More information

Certificate of Mold Analysis

Certificate of Mold Analysis CERTIFIED INSPECTION SERVICES 1211 NE 19TH TER. CAPE CORAL, FL 33909 Certificate of Mold Analysis Prepared for: CERTIFIED INSPECTION SERVICES Phone Number: (239) 458-9876 Fax Number: (239) 673-7964 Project

More information

Forensic Analytical Environmental Services Division The Case of the Phantom Mold

Forensic Analytical Environmental Services Division   The Case of the Phantom Mold Forensic Analytical Environmental Services Division www.forensica.com The Case of the Phantom Mold Interpretation of Carpet Microvacuum Results in a Litigated Matter Presented by: Ben Kollmeyer, MPH, CIH

More information

Schneider Laboratories Global, Inc

Schneider Laboratories Global, Inc Received PO 195016-001 1 Library - Middle 12/6/2016 Torula 9 75 9 75 5 75 4 75 50 Non-fungal particulates present. *4 387 spores/m3 120 spores/m3 67 spores/m3 53 spores/m3 667 spores/m3 195016-002 2 Library

More information

Mycotech Biological, Inc.

Mycotech Biological, Inc. AIHA EMPAT NO: 03006 00 Main Street Any City, TX Andersen Malt /2/04 /0/04 Sample No: (0) A- Sample No: (02) A-2 Sample No: (03) A-3 (Living Area) Sample No: (04) A-4 (Bedroom) //04 //04 //04 //04 Date

More information

Schneider Laboratories Global, Inc

Schneider Laboratories Global, Inc Analysis Report Schneider Laboratories Global, Inc 2512 W. Cary Street Richmond, Virginia 23220-5117 804-353-6778 800-785-LABS (5227) Fax 804-359-1475 Customer Asbestos Science Technologies, Inc (4038)

More information

April 28, Town of Wilton Board of Education 395 Danbury Road Wilton, CT 06897

April 28, Town of Wilton Board of Education 395 Danbury Road Wilton, CT 06897 Town of Wilton Board of Education 395 Danbury Road Wilton, CT 06897 RE: Indoor Air Quality Assessment Report Miller-Driscoll School 217 Wolf Pit Road, Wilton, Connecticut TRC Project No. 215883.1000 Board

More information

Energy & Environmental Solutions, Inc. Mold Facts/Fiction/Who Knows

Energy & Environmental Solutions, Inc. Mold Facts/Fiction/Who Knows Energy & Environmental Solutions, Inc. Mold Facts/Fiction/Who Knows Cincinnati Bar Association - Construction Law Committee September 14, 2004 Hi, my name is Introductions Brian J. O Connell, Esq. Dinsmore

More information

This test report contains the following four sections: Chain of Custody, Data Detail, Frequently Asked Questions, and Glossary.

This test report contains the following four sections: Chain of Custody, Data Detail, Frequently Asked Questions, and Glossary. This test report contains the following four sections: Chain of Custody, Data Detail, Frequently Asked Questions, and Glossary. Direct Exam Chain of Custody Page 1 1 Results apply only to samples tested.

More information

The CAP Method for Assessing Surface Dust Samples for Mold

The CAP Method for Assessing Surface Dust Samples for Mold Slide 1 The CAP Method for Assessing Surface Dust Samples for Mold An Alternative to ERMI Joe C. Spurgeon, Ph.D. jospur46@gmail.com www.expertonmold.com All Rights Reserved by Author 1 Slide 2 Presumption

More information

THE USE OF DNA TESTING IN MOULD INVESTIGATIONS ANN DORTE PØRNEKI, M.SC.

THE USE OF DNA TESTING IN MOULD INVESTIGATIONS ANN DORTE PØRNEKI, M.SC. THE USE OF DNA TESTING IN MOULD INVESTIGATIONS ANN DORTE PØRNEKI, M.SC. ADP@HOUSETEST.COM EXPERIENCES FROM SCANDINAVIA Many years with strict insulation requirements Increase in number of damp and mouldy

More information

Dealing With Dampness in Buildings

Dealing With Dampness in Buildings Dealing With Dampness in Buildings Excessive Moisture and its Affect on the Home Environment 1of 68 How Long Has Mold Been a Problem? Leviticus 14:45 A house desecrated by mildew, mold, or fungus would

More information

EXPANDED FUNGAL REPORT

EXPANDED FUNGAL REPORT EXPANDED FUNGAL REPORT Prepared Exclusively For Report Date: 1/6/2011 Project: Accceditation"This report was generated in the EMSL Test Lab Page 1 of 23 1. Description of Analysis Analytical Laboratory

More information

Influence of Environmental Parameters on Mold Sampling Results

Influence of Environmental Parameters on Mold Sampling Results University of South Florida Scholar Commons Graduate Theses and Dissertations Graduate School June 2017 Influence of Environmental Parameters on Mold Sampling Results Benjamin Fishman University of South

More information